Plan Review Details - Permit 01101462
Plan Review Stops For Permit 01101462
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-01-07 Cont ID  
Sent By dpalmer Date 2002-01-07 Time 18:26 Rev Time 0.00
Received By dpalmer Date 2002-01-07 Time 18:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-12-18 Cont ID  
Sent By dpalmer Date 2001-12-18 Time 16:40 Rev Time 0.00
Received By dpalmer Date 2001-12-18 Time 16:40 Sent To  
Notes
2001-12-18 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE NOTE, SOME ITEMS FROM
 FIRST REVIEW WERE NOT ADDRESSED.
 PLEASE NOTE CIRCUITING ON PLANS ARE
 REQ`D. MUST CORRELATE WITH PANEL SCHED.
  
  
 2)NOTE: PLEASE NOTE NO CLARIFICATION
 GIVEN FOR EM LTS OR EXIT LTS, EXISTING
 OR NEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-10-29 Cont ID  
Sent By dpalmer Date 2001-10-29 Time 18:01 Rev Time 0.00
Received By dpalmer Date 2001-10-29 Time 18:01 Sent To  
Notes
2001-10-29 00:00:00******************** UNSAT************
  
 1)NOTE: PLEASE NOTE ON PLANS THAT THE
 ELECTRICAL RISER SHOWN IS EXISTING.
  
 2)NOTE: PLEASE NOTE THAT ALL COMMERCIAL
 PLANS ARE TO HAVE BRANCH CIRCUITING ON
 PLANS AND CORRELATE WITH A SUBMITTED
 PANEL SCHEDULE.
  
 3)NOTE: PLEASE NOTE THAT UNDER FS/FAC
 ALL PLANS THAT CONTAIN TITLE BLOCK(S)
 FOR ARCH/ENG OF RECORD, MUST BE SIGNED,
 DATED AND SEALED BY THAT PERSON.F.S.
 481.221/ 471.025.
  
 4)NOTE: PLEASE CLARIFY OTHER ELECTRICAL
 EXISTING? EXIT LTS, EM LTS ETC.
  
 5)NOTE: PLEASE NOTE THAT PLANS THAT
 PLANS NEED TO HAVE RECEPTS IN BATHS
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372