2002-02-12 00:00:00 | CHECKLIST: |
| 1-REVISED ENERGY CALCULATIONS ARE WRONG |
| AGAIN. SEE SQUARE FOOTAGES ENTERED FOR |
| A/C AREA AND UNDER ATTIC AREA. |
| -PROVIDE CORRECT UNDER ATTIC AREA AS |
| REQUIRED BY SEC. 604.1.A.1 OF FLORIDA |
| ENERGY EFFICIENCY CODE. 1997 ED. |
| -NOTE: THIS IS A MODEL HOUSE. PREVIOUS |
| ENERGY CALCULATIONS WERE DONE TO WORST |
| CASE SCENARIO. NOW, THIS ONE IS NOT. |
| CLARIFY IF USING WORST CASE SCENARIO |
| OR IF ENERGY CALCULATIONS WILL BE |
| CALCULATED FOR EACH HOUSE. |
| 2-PLANS SUBMITTED AT TIME OF APPLICATION |
| SHOW GARAGE AT RIGHT HAND SIDE. NOW, |
| PLANS RESUBMITTED SHOW GARAGE AT LEFT |
| HAND SIDE. PROVIDE REVISED SURVEY FOR |
| ZONING AND BUILDING RE-REVIEW. |
| 3-SPECIFY ON FLOOR PLAN 1 HR FIRE RATED |
| GLASS BLOCK ASSEMBLY AT ZERO LOT LINE |
| WALL AND REVISE GLASS BLOCK DETAILS ON |
| SHEET 5 TO MATCH 1 HR ASSEMBLY AS PER |
| UL LISTING. SEE ATTACHED COPY THAT WAS |
| SUBMITTED BY CONTRACTOR. |
| 4-TRUSS DRAWINGS: |
| A)TRUSS ENGINEER TO SIGN, SEAL AND DATE |
| TRUSS LAYOUT. |
| B)UPDATE GENERAL DETAILS AS REQUIRED. |
| USE CURRENT CODES AND CORRECT MPH |
| WIND LOAD. |
| C)THERE ARE 2 ENGINEER'S SEALS ON |
| GENERAL DETAILS. REVISE AS REQUIRED. |
| D)GENERAL DETAILS ARE NOT LEGIBLE. |
| E)SPECIFY ON ENGINEERED TRUSSES WHAT |
| EDITION OF SBC WAS USED FOR DESIGN. |
| IT SHALL BE SBC 1997. |
| F)MIXING AND MATCHING ASCE 7-98 AND SBC |
| 1997 IS NOT ALLOWED. REVISE AS REQ'D. |
| G)RIGHT WIND ZONE USING ASCE 7-98 IS |
| 140 MPH. REVISE AS REQUIRED. |
| 5-SPECIFY CEILING INSTALLATION AT FRONT |
| AND BACK PORCH. SEE ASTM C-926 AND |
| ASTM C-1063 AND PROVIDE SPECS AS REQ'D |
| (SEC. 2504.2 SBC 1997). |
| 6-SEE COMMENTS ON PLANS. |
| 7-CLEARLY SPECIFY SIZE OF ANCHOR ON DWG |
| 3B. EG: HETA 16, 20 OR 24 ETC. |