Plan Review Stops For Permit 01101293 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2002-05-29 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-05-29 |
Time |
14:26 |
Rev Time |
2.50 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2001-12-24 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-12-24 |
Time |
08:42 |
Rev Time |
8.00 |
Received By |
jwitmer |
Date |
2001-12-24 |
Time |
08:42 |
Sent To |
|
|
Notes |
2001-12-24 00:00:00 | BUILDING PLAN REVIEW | | PERMIT # 01101293 | | 400 NORTHPOINT PKWAY / 403 | | BUTTERS CONSSTRUCTION | | CONTACT: FRANK GAMBENO | | TEL: (954) 570-8111 | | FAX: (954) 570-8844 | | | | SBC= 1997 STANDARD BUILDING CODE | | SBC*= AMENDMENTS/ STANDARD BUILDING CODE | | | | 1)- PLANS INDICATE A MERCANTILE OCCUPAN- | | CY.THE AMOUNT OF FLAMMABLE/ COMBUSTIBLE | | LIQUIDS EXCEEDS THE AMOUNTS ALLLOWABLE | | IN TABLE 308.2B, FOR SPRINKLERED BUILD- | | ING, NOT IN A CABINET. | | THE TYPE OCCUPANCY SHALL BE A "H2 OCCU- | | PANCY" DEFLAGRATION HAZARDS, CLASS I, | | II AND III-A FLAMMABLE OR COMBUSTIBLE | | LIQUIDS. | | | | 2)- 408.6 STORAGE OF HAZARDOUS PRODUC- | | TION MATERIAL | | ROOMS USED TO THE STORAGE OF HPM IN QUAN | | ITIES GREATER THAN SET FORTH IN TABLE | | 408.3.3.B EXCEPT FOR THE PERMITTED | | WITHIN A FABRICATION AREA, SHALL COMPLY | | WITH THE PROVISIONS OF NFPA 30 PROVIDED | | THAT THE AREA OF AN HPM CUTOFF ROOM | | SHALL NOT EXCEED 6,000 SQ. FT. | | | | TO COMPLY WITH SECTIONS 408.6.1-408.6.7 | | | | SEE NFPA 30 FOR ADDITIONAL INFORMATION. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561) 659-8096 X8412 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2001-11-05 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-11-05 |
Time |
08:57 |
Rev Time |
2.25 |
Received By |
jwitmer |
Date |
2001-11-05 |
Time |
08:57 |
Sent To |
|
|
Notes |
2001-11-05 00:00:00 | BUILDING PLAN REVIEW | | PERMIT # 01101293 | | 400 NORTHPOINT # 403 | | CONT: BUTTERS CONT | | (954) 570-8111 | | | | SBC= STANDARD BUILDING CODE | | SBC*= AMENDMENTS/ STANDARD BUILDING CODE | | | | 1)- TO BE ABLE TO IDENTIFY THE TYPE OF | | BUILDING OCCUPANCY, THE CITY REQUEST | | ADDITIONAL INFORMATION, MSDS SHEETS FOR | | THE VARIOUS CHEMICALS PAINTS, THINNERS, | | SOLVENTS, THE QUANITIES OF EACH. DEPEND- | | ING ON THIS INFORMATION AND SBC TABLE | | 308.B THE CITY WILL BE ABLE TO DETERMINE | | THE OCCUPANCY CLASS. | | WILL THIS SPACE BE FIRE SPRINKLERED. | | PLANS INDICATE THAT IT WILL BE SUBMIT | | FIRE SPRINKLER LAYOUT, DROPPED CEILING | | AREA INDICATE FIRE SPRINKLERS. | | | | 2)- WILL THE AREA ABOVE THE OFFICE SPACE | | BE USED FOR STORAGE. | | | | 3)- WAREHOUSE (STORAGE AREA 108) HOW | | WILL THE RAW AND FINISHED PRODUCT BE | | STORED? HEIGHT OF RACKS?CLEAR HEIGTH | | BETWEEN THE RACK AREA FOR STORAGE & | | THE BOTTOM OF SPRINKLER HEAD? | | | | 4)- MIXING ROOM DETAIL "C", THIS DETAIL | | INDICATES A LIQUID TIGHT CURB ON ALL 4 | | SIDES OF THE ROOM, WILL THE CURB RUN | | ALSO UNDERNEATH THE DOORWAYS? WHAT MATER | | IAL WILL BE USED TO SEAL THE FLOOR AND | | CURB? HOW WILL SPILLAGE BE REMOVED? | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561) 659-8096X8412 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2002-08-07 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-08-07 |
Time |
16:34 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-08-07 |
Time |
16:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2002-04-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-04-30 |
Time |
19:25 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-04-30 |
Time |
19:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2001-12-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-12-27 |
Time |
10:49 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-12-27 |
Time |
10:49 |
Sent To |
|
|
Notes |
2001-12-27 00:00:00 | *************** UNSAT ************** | | | | 1)NOTE: PLEASE NOTE THAT DUE TO THE | | ADDITIONAL INFORMATION OF USE OF | | PROPERTY. | | PLANS WILL NEED MORE INFORMATION FOR | | TYPE OF STORAGE MATERIALS AND CLASS OF | | LOCATION. | | | | PLEASE CALL IF THERE ARE ANY QUESTIONS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2001-10-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-10-30 |
Time |
23:25 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-10-30 |
Time |
23:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2002-05-14 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-05-14 |
Time |
11:22 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-05-14 |
Time |
11:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2001-12-27 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-12-10 |
Time |
12:36 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-12-10 |
Time |
12:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2001-10-22 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-10-22 |
Time |
17:29 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-10-22 |
Time |
17:29 |
Sent To |
|
|
Notes |
2001-10-22 00:00:00 | 1) PLEASE EXPLAIN COLOR TINT ROOM. | | WHAT PROCESSES ARE INVOLVED IN THIS | | LOCATION. | | 2) MORE DETAILS REQUIRED FOR SPRAY | | BOOTH. WHAT WILL THE SPRAY BOOTH | | BE USED FOR. ALL OF THE PRESCRIPTIVE | | CODE REQUIREMENTS INCLUDING FIRE | | PROTECTION WILL BE REQUIRED IF | | FLAMMABLE OR COMBUSTIBLE LIQUIDS ARE | | SPRAYED. | | 3) IS THE EXISTING BUILDING FIRE | | SPRINKLER PROTECTED. IF SO, WHERE ARE | | THE SPRINKLER DRAWINGS. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2002-05-30 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2002-05-29 |
Time |
13:23 |
Rev Time |
0.50 |
Received By |
ndenmark |
Date |
2002-05-29 |
Time |
13:23 |
Sent To |
|
|
Notes |
2002-05-29 00:00:00 | PROVISO | | REVISION INDICATES A NEW CUT OFF ROOM | | THIS ROOM IS FOR STORAGE ONLY, ANY OCCUP | | ANCY WOULD REQUIRE VENTILATION. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2001-11-08 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2001-11-08 |
Time |
13:14 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
2001-11-08 |
Time |
13:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2002-06-19 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-06-19 |
Time |
17:28 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-06-19 |
Time |
17:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2002-05-24 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-05-24 |
Time |
19:15 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2002-05-24 |
Time |
19:15 |
Sent To |
|
|
Notes |
2002-05-24 00:00:00 | DENIED | | REFERENCE: SPC-94-FACBC-97 | | | | 1) FROM PREVIOUS REVIEW. EMERGENCY EYE | | WASH AND SHOWER REQUIRED PER MSMD SHEETS | | SUBMITTED. A FLOOR DRAIN WITH A TRAP | | PRIMER IS REQUIRED NEAR THE BASE SHOWER | | TO DRAIN SHOWER & EYE WASH | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2001-12-23 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-12-23 |
Time |
06:14 |
Rev Time |
1.25 |
Received By |
kstevens |
Date |
2001-12-23 |
Time |
06:14 |
Sent To |
|
|
Notes |
2001-12-23 00:00:00 | DENIED | | | | EMERGENGY SHOWER AND EYE WASH REQUIRED | | PER MSMD SHEETS SUBMITTED. ALSO A FLOOR | | DRAIN NEAR BASE OF SHOWER WITH A TRAP | | PRIMER IS REQUIRED TO DRAIN SHOWER AND | | EYE WASH. | | | | REVIEW BY KEN STEVENS | | (561) 569-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-11-07 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-11-07 |
Time |
12:40 |
Rev Time |
1.25 |
Received By |
kstevens |
Date |
2001-11-07 |
Time |
12:39 |
Sent To |
|
|
Notes |
2001-11-07 00:00:00 | DENIED | | REFERENCE: SPC-94 - FACBC-97 | | | | 1) PAGE A1 SPC TABLE 407 MINIMUM FACIL- | | ITIES REQUIRE 2 W/C'S AND 2 LAVS FOR | | FEMALES. | | 2) PAGE A4 HDCP RESTROOMS, DOORS SHALL | | NOT OPEN INTO CLEAR FLOOR SPACE OR UN- | | OBSTRUCTED TURNING RADIUS PER FACBC SEC | | 4.22.3. | | 3) PAGE A4 TOILET ELEVATIONS, W/C TO BE | | 1'6" TO C/L OFF FINISHED WALL. | | 4) PAGE P0.1 PLUMBING NOTES #13, AIR | | CHAMBERS ARE "QUICK FIX" AND IF INSTALL- | | ED SHALL COMPLY WITH SPC SEC 607.8.3 AND | | BE RECHARGEABLE AND ACCESSIBLE. WATER | | HAMMER ARRESTORS SHALL BE INSTALLED PER | | WH-PDI 201 AND MANUFACTURE INSTALL. INST | | AND BE PLACED CLOSE TO FIXTURE. | | 5) P2.1 CONDENSATE LINE, SHOW DETAIL OF | | SUPPORT FOR CONDENSATE LINE. SHOW HOW | | SUPPORTS ARE ATTACHED TO ROOF. PVC LINES | | SHALL BE PAINTED TO PROTECT PIPES FROM | | U.V. RAYS PER MANUF. SPECS. | | 6) PAGE P2.1 RPZ BACKFLOW REQUIRED TO BE | | INSTALLED NO HIGHER THAN 4' AFF TO BE | | ACCESSIBLE. DRAIN TO FLOOR SINK WITH | | TRAP PRIMER, OR TO MOP SINK INDIRECTLY. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|