Plan Review Details - Permit 01101293
Plan Review Stops For Permit 01101293
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-05-29 Cont ID  
Sent By jwitmer Date 2002-05-29 Time 14:26 Rev Time 2.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-12-24 Cont ID  
Sent By jwitmer Date 2001-12-24 Time 08:42 Rev Time 8.00
Received By jwitmer Date 2001-12-24 Time 08:42 Sent To  
Notes
2001-12-24 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01101293
 400 NORTHPOINT PKWAY / 403
 BUTTERS CONSSTRUCTION
 CONTACT: FRANK GAMBENO
 TEL: (954) 570-8111
 FAX: (954) 570-8844
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- PLANS INDICATE A MERCANTILE OCCUPAN-
 CY.THE AMOUNT OF FLAMMABLE/ COMBUSTIBLE
 LIQUIDS EXCEEDS THE AMOUNTS ALLLOWABLE
 IN TABLE 308.2B, FOR SPRINKLERED BUILD-
 ING, NOT IN A CABINET.
 THE TYPE OCCUPANCY SHALL BE A "H2 OCCU-
 PANCY" DEFLAGRATION HAZARDS, CLASS I,
 II AND III-A FLAMMABLE OR COMBUSTIBLE
 LIQUIDS.
  
 2)- 408.6 STORAGE OF HAZARDOUS PRODUC-
 TION MATERIAL
 ROOMS USED TO THE STORAGE OF HPM IN QUAN
 ITIES GREATER THAN SET FORTH IN TABLE
 408.3.3.B EXCEPT FOR THE PERMITTED
 WITHIN A FABRICATION AREA, SHALL COMPLY
 WITH THE PROVISIONS OF NFPA 30 PROVIDED
 THAT THE AREA OF AN HPM CUTOFF ROOM
 SHALL NOT EXCEED 6,000 SQ. FT.
  
 TO COMPLY WITH SECTIONS 408.6.1-408.6.7
  
 SEE NFPA 30 FOR ADDITIONAL INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-11-05 Cont ID  
Sent By jwitmer Date 2001-11-05 Time 08:57 Rev Time 2.25
Received By jwitmer Date 2001-11-05 Time 08:57 Sent To  
Notes
2001-11-05 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01101293
 400 NORTHPOINT # 403
 CONT: BUTTERS CONT
 (954) 570-8111
  
 SBC= STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- TO BE ABLE TO IDENTIFY THE TYPE OF
 BUILDING OCCUPANCY, THE CITY REQUEST
 ADDITIONAL INFORMATION, MSDS SHEETS FOR
 THE VARIOUS CHEMICALS PAINTS, THINNERS,
 SOLVENTS, THE QUANITIES OF EACH. DEPEND-
 ING ON THIS INFORMATION AND SBC TABLE
 308.B THE CITY WILL BE ABLE TO DETERMINE
 THE OCCUPANCY CLASS.
 WILL THIS SPACE BE FIRE SPRINKLERED.
 PLANS INDICATE THAT IT WILL BE SUBMIT
 FIRE SPRINKLER LAYOUT, DROPPED CEILING
 AREA INDICATE FIRE SPRINKLERS.
  
 2)- WILL THE AREA ABOVE THE OFFICE SPACE
 BE USED FOR STORAGE.
  
 3)- WAREHOUSE (STORAGE AREA 108) HOW
 WILL THE RAW AND FINISHED PRODUCT BE
 STORED? HEIGHT OF RACKS?CLEAR HEIGTH
 BETWEEN THE RACK AREA FOR STORAGE &
 THE BOTTOM OF SPRINKLER HEAD?
  
 4)- MIXING ROOM DETAIL "C", THIS DETAIL
 INDICATES A LIQUID TIGHT CURB ON ALL 4
 SIDES OF THE ROOM, WILL THE CURB RUN
 ALSO UNDERNEATH THE DOORWAYS? WHAT MATER
 IAL WILL BE USED TO SEAL THE FLOOR AND
 CURB? HOW WILL SPILLAGE BE REMOVED?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096X8412

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-08-07 Cont ID  
Sent By btrobaug Date 2002-08-07 Time 16:34 Rev Time 0.00
Received By btrobaug Date 2002-08-07 Time 16:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-04-30 Cont ID  
Sent By dpalmer Date 2002-04-30 Time 19:25 Rev Time 0.00
Received By dpalmer Date 2002-04-30 Time 19:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-12-27 Cont ID  
Sent By dpalmer Date 2001-12-27 Time 10:49 Rev Time 0.00
Received By dpalmer Date 2001-12-27 Time 10:49 Sent To  
Notes
2001-12-27 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT DUE TO THE
 ADDITIONAL INFORMATION OF USE OF
 PROPERTY.
 PLANS WILL NEED MORE INFORMATION FOR
 TYPE OF STORAGE MATERIALS AND CLASS OF
 LOCATION.
  
 PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-10-30 Cont ID  
Sent By dpalmer Date 2001-10-30 Time 23:25 Rev Time 0.00
Received By dpalmer Date 2001-10-30 Time 23:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-05-14 Cont ID  
Sent By mcarsill Date 2002-05-14 Time 11:22 Rev Time 0.00
Received By mcarsill Date 2002-05-14 Time 11:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-12-27 Cont ID  
Sent By mcarsill Date 2001-12-10 Time 12:36 Rev Time 0.00
Received By mcarsill Date 2001-12-10 Time 12:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-10-22 Cont ID  
Sent By mcarsill Date 2001-10-22 Time 17:29 Rev Time 0.00
Received By mcarsill Date 2001-10-22 Time 17:29 Sent To  
Notes
2001-10-22 00:00:001) PLEASE EXPLAIN COLOR TINT ROOM.
 WHAT PROCESSES ARE INVOLVED IN THIS
 LOCATION.
 2) MORE DETAILS REQUIRED FOR SPRAY
 BOOTH. WHAT WILL THE SPRAY BOOTH
 BE USED FOR. ALL OF THE PRESCRIPTIVE
 CODE REQUIREMENTS INCLUDING FIRE
 PROTECTION WILL BE REQUIRED IF
 FLAMMABLE OR COMBUSTIBLE LIQUIDS ARE
 SPRAYED.
 3) IS THE EXISTING BUILDING FIRE
 SPRINKLER PROTECTED. IF SO, WHERE ARE
 THE SPRINKLER DRAWINGS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-05-30 Cont ID  
Sent By ndenmark Date 2002-05-29 Time 13:23 Rev Time 0.50
Received By ndenmark Date 2002-05-29 Time 13:23 Sent To  
Notes
2002-05-29 00:00:00PROVISO
 REVISION INDICATES A NEW CUT OFF ROOM
 THIS ROOM IS FOR STORAGE ONLY, ANY OCCUP
 ANCY WOULD REQUIRE VENTILATION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-11-08 Cont ID  
Sent By ndenmark Date 2001-11-08 Time 13:14 Rev Time 0.33
Received By ndenmark Date 2001-11-08 Time 13:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-06-19 Cont ID  
Sent By kstevens Date 2002-06-19 Time 17:28 Rev Time 0.00
Received By kstevens Date 2002-06-19 Time 17:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-05-24 Cont ID  
Sent By kstevens Date 2002-05-24 Time 19:15 Rev Time 0.00
Received By kstevens Date 2002-05-24 Time 19:15 Sent To  
Notes
2002-05-24 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) FROM PREVIOUS REVIEW. EMERGENCY EYE
 WASH AND SHOWER REQUIRED PER MSMD SHEETS
 SUBMITTED. A FLOOR DRAIN WITH A TRAP
 PRIMER IS REQUIRED NEAR THE BASE SHOWER
 TO DRAIN SHOWER & EYE WASH
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-12-23 Cont ID  
Sent By kstevens Date 2001-12-23 Time 06:14 Rev Time 1.25
Received By kstevens Date 2001-12-23 Time 06:14 Sent To  
Notes
2001-12-23 00:00:00DENIED
  
 EMERGENGY SHOWER AND EYE WASH REQUIRED
 PER MSMD SHEETS SUBMITTED. ALSO A FLOOR
 DRAIN NEAR BASE OF SHOWER WITH A TRAP
 PRIMER IS REQUIRED TO DRAIN SHOWER AND
 EYE WASH.
  
 REVIEW BY KEN STEVENS
 (561) 569-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-11-07 Cont ID  
Sent By kstevens Date 2001-11-07 Time 12:40 Rev Time 1.25
Received By kstevens Date 2001-11-07 Time 12:39 Sent To  
Notes
2001-11-07 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PAGE A1 SPC TABLE 407 MINIMUM FACIL-
 ITIES REQUIRE 2 W/C'S AND 2 LAVS FOR
 FEMALES.
 2) PAGE A4 HDCP RESTROOMS, DOORS SHALL
 NOT OPEN INTO CLEAR FLOOR SPACE OR UN-
 OBSTRUCTED TURNING RADIUS PER FACBC SEC
 4.22.3.
 3) PAGE A4 TOILET ELEVATIONS, W/C TO BE
 1'6" TO C/L OFF FINISHED WALL.
 4) PAGE P0.1 PLUMBING NOTES #13, AIR
 CHAMBERS ARE "QUICK FIX" AND IF INSTALL-
 ED SHALL COMPLY WITH SPC SEC 607.8.3 AND
 BE RECHARGEABLE AND ACCESSIBLE. WATER
 HAMMER ARRESTORS SHALL BE INSTALLED PER
 WH-PDI 201 AND MANUFACTURE INSTALL. INST
 AND BE PLACED CLOSE TO FIXTURE.
 5) P2.1 CONDENSATE LINE, SHOW DETAIL OF
 SUPPORT FOR CONDENSATE LINE. SHOW HOW
 SUPPORTS ARE ATTACHED TO ROOF. PVC LINES
 SHALL BE PAINTED TO PROTECT PIPES FROM
 U.V. RAYS PER MANUF. SPECS.
 6) PAGE P2.1 RPZ BACKFLOW REQUIRED TO BE
 INSTALLED NO HIGHER THAN 4' AFF TO BE
 ACCESSIBLE. DRAIN TO FLOOR SINK WITH
 TRAP PRIMER, OR TO MOP SINK INDIRECTLY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377