Plan Review Details - Permit 01101288
Plan Review Stops For Permit 01101288
Review Stop B BUILDING (STRUCTURAL)
Rev No 29 Status P Date 2004-03-30 Cont ID  
Sent By shill Date 2004-03-30 Time 10:30 Rev Time 0.50
Received By shill Date 2004-03-30 Time 10:30 Sent To  
Notes
2004-03-30 00:00:00IMPACT BARRIER DETAIL FOR P3 GLASS
 PREPARED BY HERBERT GOPMAN, PE

Review Stop B BUILDING (STRUCTURAL)
Rev No 28 Status P Date 2004-03-18 Cont ID  
Sent By csiegber Date 2004-03-25 Time 15:20 Rev Time 0.50
Received By shill Date 2004-03-18 Time 10:11 Sent To P
Notes
2004-03-18 00:00:00REV 2.06, 3.03 DATED 3/15/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 27 Status P Date 2004-03-18 Cont ID  
Sent By csiegber Date 2004-03-17 Time 14:10 Rev Time 5.00
Received By shill Date 2004-03-16 Time 16:36 Sent To  
Notes
2004-03-18 00:00:00REVISIONS DATED 9/3/3 AND 3/9/4, #10 &
 #11

Review Stop B BUILDING (STRUCTURAL)
Rev No 26 Status P Date 2004-03-16 Cont ID  
Sent By csiegber Date 2004-03-16 Time 15:40 Rev Time 0.50
Received By shill Date 2004-03-16 Time 09:50 Sent To  
Notes
2004-03-16 00:00:00INTERIOR DESIGN DRAWINGS
 PROVISO - IN ACCORDANCE WITH APPROVED
 PLAN AND SBC

Review Stop B BUILDING (STRUCTURAL)
Rev No 25 Status P Date 2004-03-04 Cont ID  
Sent By csiegber Date 2004-03-16 Time 09:19 Rev Time 0.50
Received By shill Date 2004-03-04 Time 13:14 Sent To  
Notes
2004-03-04 00:00:00LETTER DATED 3/2/04 PREPARED BY ALBERT
 SHUB, PE IN REGARDS TO ENERGY CALCS
 (INTERSTITIAL SPACE EXCEEDS
 REQUIREMENTS ON EN CALC SO REVISED
 CALCS ARE UNNECESSARY)

Review Stop B BUILDING (STRUCTURAL)
Rev No 24 Status P Date 2004-03-03 Cont ID  
Sent By shill Date 2004-03-03 Time 10:41 Rev Time 2.00
Received By shill Date 2004-03-03 Time 10:41 Sent To  
Notes
2004-03-03 00:00:00REVISED A2.11 AND 7.04 DATED 2/2/04
 PROVISO - PROVIDE REVISED ENERGY CALCS

Review Stop B BUILDING (STRUCTURAL)
Rev No 23 Status P Date 2004-03-01 Cont ID  
Sent By shill Date 2004-03-01 Time 13:42 Rev Time 1.00
Received By shill Date 2004-03-01 Time 13:42 Sent To  
Notes
2004-03-01 00:00:00L2.02.,L4.01-4.04
 SPRINKLER REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 22 Status P Date 2004-02-18 Cont ID  
Sent By csiegber Date 2004-02-20 Time 16:05 Rev Time 0.50
Received By shill Date 2004-02-18 Time 08:26 Sent To  
Notes
2004-02-18 00:00:00FLOOR ELEVATIONS PREPARED BY CRAVEN-
 THOMPSON DATED 1/27/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 21 Status F Date 2004-02-11 Cont ID  
Sent By shill Date 2004-02-11 Time 17:41 Rev Time 0.50
Received By shill Date 2004-02-11 Time 17:41 Sent To  
Notes
2004-02-11 00:00:00****CORRECTIONS****
  
 TYPICAL WALL RAIL
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PROVIDE THE CONNECTION DETAIL.
  
 2.)PROVIDE CALCULATIONS TO COMPLY
 WITH FBC1608.2.1.
  
 3.)SPECIFY THE MATERIAL; PROVIDE A
 DETAIL TO COMPLY WITH FBC1007.5.3.

Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status F Date 2004-02-09 Cont ID  
Sent By csiegber Date 2004-02-11 Time 14:06 Rev Time 1.00
Received By shill Date 2004-02-09 Time 14:29 Sent To  
Notes
2004-02-09 00:00:00*****CORRECTIONS****
  
 INTERIOR DESIGN DETAILS PREPARED BY
 INTERIORS BY STEVEN G. INC.
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 SEE ATTACHED FAC61G1-16 IN REGARDS
 TO TITLE BLOCK, SEAL AND SIGNATURE.
 CORRECT AS NOTED AND RESUBMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status P Date 2004-02-04 Cont ID  
Sent By shill Date 2004-02-04 Time 13:20 Rev Time 0.50
Received By shill Date 2004-02-04 Time 13:20 Sent To  
Notes
2004-02-04 00:00:00ROOF WIND PRESSURE AND ATTACHMENT
 DESIGN SUBMITTAL PREPARED BY HERBERT
 GOPMAN, PE AND ATLANTIC & CARIBBEAN
 ROOF CONSULTING LLC 1/19/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status F Date 2004-01-27 Cont ID  
Sent By csiegber Date 2004-01-28 Time 16:09 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2004-01-27 00:00:00REVISIONS SHOWN AS #10 HAVING VARYING
 DATES.
  
 SHEET A 7.06 SPEAKS TO "NON-COMBUSTIBLE
 FOAM" WHICH HAS NOT BEEN ESTABLISHED TO
 DATE.THIS STATEMENT SHOULD BE REMOVED
 FROM THE PLANS SINCE THE PRODUCTS
 INSTALLED ON THE BUILDING TO DATE ARE
 NOT NON-COMBUSTIBLE AS DEFINED IN THE
 1997 STANDARD BUILDING CODE OR THE 2001
 FLORIDA BUILDING CODE.
  
 THE REQUESTED DOCUMENTS FOR THE
 ATTACHMENT METHODS USED FOR THE FOAM
 TRIM DEMONSTRATING WIND LOAD COMPLIANCE
 HAVE NOT BEEN PROVIDED.A COPY OF THE
 11/06/03 REVIEW NOTES ARE ATTACHED.
  
 THE FIRE SPRINKLER PLANS DONOT CLEARLY
 REFLECT THE APPLICATION OF THE
 SPECIALTY FIRE SPRINKLER HEADS THAT
 WILL PROVIDE THE TWO HOUR FIRE RATING
 REQUIRED IN THE VARIANCE GRANTED BY THE
 BOARD OF ADJUSTMENTS.
  
 NO HEADS ARE SHOWN AT THE FIXED WINDOWS
 IN THE GUEST ROOMS.
  
 HEADS ARE SHOWN ON THE EXTERIOR SIDE OF
 THE BALCONY DOORS, BUT NOT AT THE
 INTERIOR SIDE.
  
 PLEASE REVISE AS NECESSARY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status P Date 2004-01-14 Cont ID  
Sent By shill Date 2004-01-14 Time 09:30 Rev Time 0.50
Received By shill Date 2004-01-14 Time 09:30 Sent To  
Notes
2004-01-14 00:00:00STOREFRONT CALCS PREPARED BY ERIC
 VANHORN PE DATED 11/6/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2004-01-14 Cont ID  
Sent By shill Date 2004-01-14 Time 09:20 Rev Time 0.50
Received By shill Date 2004-01-14 Time 09:20 Sent To  
Notes
2004-01-14 00:00:00ROOF SCUTTLE SHOP DRAWINGS PREPARED BY
 BILCO

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2004-01-12 Cont ID  
Sent By shill Date 2004-01-12 Time 15:24 Rev Time 0.50
Received By shill Date 2004-01-12 Time 15:24 Sent To  
Notes
2004-01-12 00:00:00FRAMING FOR PRE-CAST HEADER, EAST
 ENTRANCE PREPARED BY KELAHER PE

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2004-01-12 Cont ID  
Sent By shill Date 2004-01-12 Time 14:56 Rev Time 0.50
Received By shill Date 2004-01-12 Time 14:56 Sent To  
Notes
2004-01-12 00:00:00ELEVATOR HOIST BEAM SUBMITTAL PREPARED
 BY DIXIE METAL PRODUCTS DATED 11/12/03.

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status F Date 2003-11-06 Cont ID  
Sent By csiegber Date 2004-01-05 Time 08:57 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-11-06 00:00:00UNIVERSAL FOAM INC. LETTER DATED
 10/10/03.
  
 PLEASE PROVIDE AN ENGINEERING
 INVESTIGATION THAT THE ATTACHMENT
 METHODS RECOMMENDED IN THE LETTER WILL
 RESIST WIND AND ANY OTHER FORCES
 IMPOSED UPON THE TRIM THAT MAY OCCUR IN
 THE END APPLICATION OF THE PRODUCT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2003-11-04 Cont ID  
Sent By csiegber Date 2003-11-05 Time 15:27 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-11-04 00:00:00REVISION #10

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2003-08-08 Cont ID  
Sent By csiegber Date 2003-10-28 Time 08:37 Rev Time 0.00
Received By hpiskura Date 2003-08-08 Time 13:56 Sent To Z
Notes
2003-08-08 00:00:00REVISONS 6,7,8,9 A SHEETS AND FP SHEETS.
 REVISONS 6,7,8&9 A SHEETS AND FP SHEETS

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2003-07-21 Cont ID  
Sent By hpiskura Date 2003-07-21 Time 08:23 Rev Time 0.00
Received By hpiskura Date 2003-07-21 Time 08:23 Sent To  
Notes
2003-07-21 00:00:00SUFFOLK TRANSMITTAL #01360 RE: ADVANCED
 ROOFING, INC.
  
 A SEPARATE PERMIT FOR ROOFING IS
 REQUIRED WHEN THE COMPLETE INFORMATION
 IS NOT PROVIDED WITH THE ORIGINAL PRIME
 BUILDING PERMIT.
  
 THE BILCO TYPE S ROOF SCUTTLE INCLUDED
 IN THAT PACKAGE HAS A SPECIFICATION OF
 20 PSF UPLIFT WHICH IS INADEQUATE FOR
 THIS BUILDING HEIGHT.PLEASE REVISE
 AS NECESSARY AND INCLUDE TEST AND/OR
 PRODUCT ACCEPTANCE REPORTS FOR THE ROOF
 SCUTTLE.
  
 CC: DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status N Date 2003-06-04 Cont ID  
Sent By shernand Date 2003-07-11 Time 11:18 Rev Time 0.00
Received By shernand Date 2003-06-04 Time 15:48 Sent To  
Notes
2003-06-04 00:00:00SUBMITTAL OF 5/7/03 OK PER HP FOR
 WATERPROOFING SUBMITTAL AND ALUMINUM
 RAILS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2003-05-06 Cont ID  
Sent By hpiskura Date 2003-05-06 Time 08:53 Rev Time 0.00
Received By hpiskura Date 2003-05-06 Time 08:53 Sent To  
Notes
2003-05-06 00:00:00DIXIE METAL PRODUCTS DRAWINGS DATED
 10/23/02.
  
 THE PROPOSED TREAD WIDTH FOR THE
 ALUMINUM STAIR SHOWN ON SHEET 13 DOES
 NOT COMPLY WITH FBC 1007.3, #3.
  
 SHEET 16
 THE SPACING OF THE HANDRAILS DOES NOT
 APPEAR TO COMPLY WITH FBC 1007.5.7

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status C Date 2003-04-04 Cont ID  
Sent By shernand Date 2003-05-05 Time 11:35 Rev Time 0.00
Received By hpiskura Date 2003-04-04 Time 11:27 Sent To  
Notes
2003-04-04 00:00:00ARCHITECTURAL REVISIONS 6,7 & 8.
 SHEET A2.05 WHAT WILL THE NEWLY DEMISED
 AREA ADJACENT TO THE EXPANDED PUMP ROOM
 BE USED FOR?
  
 THE CITY PERMIT SET DOES NOT HAVE
 REVISON #5 ON MANY OF THE SHEETS.WHAT
 TOOK PLACE?
  
 STRUCTURAL PAGES IN THE CITY PERMIT SET
 GO TO REVISION #2 DATED 1/15/02, THIS
 SUBMITTAL HAS SEVEN.PLEASE PROVIDE A
 BRIEF NARRATIVE OF THE CHANGES THAT
 OCCURED SUBSEQUENT TO PERMIT ISSUED
 IN 8/02.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2003-02-21 Cont ID  
Sent By dpalmer Date 2003-03-25 Time 09:49 Rev Time 0.00
Received By hpiskura Date 2003-02-21 Time 10:48 Sent To  
Notes
2003-02-21 00:00:00REVISONS SUBMITTED AS SHOP DRAWINGS WITH
 JOSE SUAREZ, ARCHITECT COVER LETTER
 DATED 2/14/03
  
 THE ARCHITECT REQUESTS THAT POLYSTYRENE
 FOAM PRODUCTS BE SUBSTITUTED FOR THE
 PRECAST CONCRETE TRIM THAT WAS APPROVED
 ON THE PERMIT PLANS.THIS TRIM IS TO
 BE APPLIED TO THE EXTERIOR WALLS OF THE
 BUILDING.
  
 THE ARCHITECT CITES SBC 803.2 AS A BASIS
 FOR COMPLIANCE.THIS IS WITHOUT
 STANDING SINCE 803.2 IS FOR INTERIOR
 FINISHES. THE FIRE TEST METHOD OF E-84
 CITED IN 803.2 IS NOT USED TO DEFINE
 NON-COMBUSTIBLE, ASTM E 136 IS.
  
 SBC 202, AS WELL AS THE CURRENT FBC
 CLEARLY DEFINE NON-COMBUSTIBLE.ONE IS
 CAUTIONED THAT THE SECOND PART OF THAT
 DEFINITION CITES E 84 FOR SURFICIAL
 COATINGS NOT MORE THAN 1/8" THICK, WHEN
 APPLIED TO A STRUCTURAL BASE MEETING E
 136.
  
 IN THE CASE OF THE UNIVERSAL FOAM
 PRODUCT PROVIDED, THE POLYSTYRENE FOAM
 MUST MEET E 136 AND THE POLYURETHANE
 COATING ON THAT FOAM OF 1/8" THICKNESS
 OR LESS, NEED MEET ONLY E 84
 REQUIREMENTS.
  
 THE APPLICABLE CODE SECTION IS SBC 1404
 AND THE CITY'S AMENDMENT TO THE SBC
 INVOKING APPENDIX F, FIRE DISTRICT
 REQUIREMENTS.BRIEFLY, THESE CODE
 SECTIONS REQUIRE EXTERIOR TRIM TO BE
 NON-COMBUSTIBLE OR OF FIRE RETARDANT
 TREATED LUMBER.THE FAVORED NATURE AND
 CHARACTERISTICS OF FIRE RETARDANT
 TREATED LUMBER UNDER FIRE CONDITIONS,
 DEMONSTRATED BY TESTING, FAR EXCEED
 THOSE EXHIBITED BY THE FOAM PRODUCT
 THAT IS REQUESTED AS A SUBSTITUTION.
  
 SEVERAL OF THE TEST REPORTS PROVIDED
 SAY THE MATERIAL MELTED AND FELL TO
 THE FLOOR OF THE TEST CHAMBER AND
 BURNED BEFORE THE CONCLUSION OF THE
 REQUIRED TEST PERIOD.THE EVALUATION
 REPORTS REFERENCED, SOME OF WHICH ARE
 OBSOLETE, ARE FOR TESTS USING SPECIFIC
 THICKNESSES, SYSTEMS AND UNIQUE
 ASSEMBLAGES.
  
 USING PRUDENCE AND CODE EXPERIENCE,
 TOGETHER WITH THE INFORMATION PROVIDED
 THUS FAR,IT CANNOT BE REASONED THAT
 THIS IS AN EQUAL AND ALTERNATE MATERIAL
 FOR THE PURPOSE INTENDED, AND BE
 SUBSTITUTED FOR NON-COMBUSTIBLE
 MATERIAL AS SUCH.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2002-10-07 Cont ID  
Sent By btrobaug Date 2002-12-05 Time 16:22 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-10-07 00:00:00SUFFOLK SUBMITTAL #00459 RE: MASONRY
 PRODUCTS.
  
 THE CSR RINKER LETTERS CITE COMPLIANCE
 WITH THE S. FLORIDA BUILDING CODE.THE
 DESIGN MUST COMPLY WITH SBCCI 1997, THE
 CODE UNDER WHICH THE BUILDING WAS
 PERMITTED.PLEASE PROVIDE WRITTEN
 ASSURANCE OF COMPLIANCE WITH THE DESIGN
 STANDARDS CONTAINED IN SBCCI 1997 OR
 FBC 2001.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-08-02 Cont ID  
Sent By hpiskura Date 2002-08-02 Time 15:18 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2002-07-25 Cont ID  
Sent By hpiskura Date 2002-07-25 Time 10:49 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-07-25 00:00:00THIS IS THE THIRD REQUEST FOR ATTACHMENT
 DETAILS FOR THE CAST STONE TO BE
 APPLIED TO THE BUILDING.THE ARCHITECT
 HAS REPRODUCED CODE TEXT ON SHEET A4.02
 (SBC 1403.2.6)THIS IS NOT SPECIFIC
 DESIGN INFORMATION.SEE SBC 104.2.1
 REGARDING THE PROHIBITION OF CITING THE
 CODE IN LIEU OF SPECIFIC DESIGN
 INFORMATION.THIS CAVEAT WAS NOTED ON
 PREVIOUS APPLICATION REJECTIONS ALSO.
  
 THIS IS THE THIRD REQUEST FOR
 INFORMATION ON THE SPRINKLER HEADS THAT
 WILL PROVIDE EQUIVALENT PROTECTION FOR
 FIRE RATED OPENING PROTECTIVES.
  
 SHEET SP8, PREPARED BY ALBERT SHUB, PE
 SHOWS A "WS VERTICAL CENTRAL" HEAD AT
 "EXTERIOR WALL & INTERIOR OF FIXED
 GLASS" AND "AT EXTERIOR WALL & INTERIOR
 OF SLIDING GLASS DOORS".
  
 THERE IS NOTHING MORE ON THE FIRE
 PROTECTION SYSTEM ENGINEERING DOCUMENTS
 THAT ADDRESSES THIS SPECIAL APPLICATION
 WINDOW SPRINKLER.
  
 THE CENTRAL, WS, 3-01, MODEL WS SPECIFIC
 APPLICATION WINDOW SPRINKLERS TYCO FIRE
 PRODUCTS, TECHNICAL DATA SHEET #6-2.0
 PRINTED 3/01 CONTAINS THE FOLLOWING
 INFORMATION.
  
 UNDER GENERAL DESCRIPTION IT STATES THAT
 THE WS HEAD CAN BE USED AS INTERIOR
 PROTECTION OF GLAZING.IT GOES ON TO
 ALLOW THE USE OF THE HEAD AS AN "OPEN"
 SPRINKLER FOR EXTERIOR APPLICATIONS,
 AND USING THE DESIGN REQUIREMENTS OF
 NFPA.THE ENGINEERED DESIGN DOCUMENTS
 DO NOT ADDRESS THIS.
  
 UNDER "WARNING" IN THE SAME CENTRAL TECH
 DATA IT SAYS THE HEAD MUST BE INSTALLED
 & MAINTAINED ISN COMPLIANCE WITH THE
 DATA SHEET, NFPA, AND ANY OTHER
 APPLICABLE STANDARDS.CHAPTER 4-7,
 NFPA13-99 OUTSIDE SPRINKLERS, SOME OF
 THE CRITERIA IS FOR AN INDEPENDENT
 CONTROL VALVE, CORROSION RESISTANCE AND
 A PRESSURE GAUGE.THESE ARE NOT
 INDICATED ON THE ENGINEERED DESIGN
 DOCUMENTS.
  
 THE CENTRAL WS TECH DATA UNDER "DESIGN
 CRITERIA" DECLARES THE HEADS TO BE OPEN
 SPRINKLERS FOR OUTSIDE USE.
  
 SAME CENTRAL WS TECH DATA SHEET UNDER
 "AREA OF USE" IT STATES THAT THE WS MAY
 BE USED TO PROTECT NON-OPERABLE WINDOWS.
 THE ENGINEERED DESIGN DOCUMENTS PROPOSE
 THE USE OF THE HEADS ON SLIDING GLASS
 DOORS, (OPERABLE), FOR INTERIOR AND
 EXTERIOR.
  
 SAME CENTRAL DATA SHEET UNDER "MINIMUM
 CLEARANCE FROM FACE OF GLASS TO
 COMBUSTIBLE MATERIALS" FOR THE USE OF A
 36" PONY WALL OR SIMILAR METHOD.
 NOTHING SHOWN ON THE ENGINEERED DESIGN
 DOCUMENTS.
  
 SAME CENTRAL DATA SHEET UNDER
 RECOMMENDED HYDRAULIC REQUIREMENTS IS A
 SPECIFIC FORMULA THAT PROVIDES FOR AN
 INCREASED HYDRAULIC DEMAND TO BE
 ADDITIVE TO THE MOST DEMANDING
 HYDRAULIC DESIGN AREA.FURTHER THE
 OPEN EXTERIOR HEADS ARE CALCULATED AS A
 A DELUGE SYSTEM IN ACCORDANCE WITH NFPA.
  
 NER-516, NATIONAL EVALUATION REPORT FOR
 THIS PARTICULAR SPRINKLER HEAD, (A
 RECOGNIZED LISTING AGENCY) WAS SHARED
 WITH THE BUILDING DESIGNERS IN A
 MEETING PRIOR TO THE PREPARATION OF
 THESE DRAWINGS.THAT REPORT INVOKES
 THE CENTRAL DATA SHEET REFERENCED ABOVE.
  
  
 RULE 61G15-32.003 (4) COMMON
 REQUIREMENTS TO ALL FIRE PROTECTION
 ENGINEERING
 DOCUMENTS. OF THE FLORIDA ADOMINSTRATIVE
 CODE READS IN PART:WHEN CODES AND
 STANDARDS ARE NOT AVAILABLE OR
 APPLICABLE, AND SAID LAYOUT DOCUMENTS
 ARE TO BE BASED ON ENGINEERING
 JUDGMENT, ANY REASONS AND ASSUMPTIONS
 MADE TO DEVELOP THE FIRE PROTECTION
 CONCEPT SHALL BE IDENTIFIED ON THE FIRE
 PROTECTION SYSTEM ENGINEERING
 DOCUMENTS.
  
 THE REASONS AND ASSUMPTIONS FOR THE
 DIVERSION FROM THE LISTING OF THE
 SPRINKLER ARE NOT READILY APPARENT ON
 THE FIRE PROTECTION SYSTEM ENGINEERING
 DOCUMENTS.
  
 THIS IS THE THIRD REQUEST FOR
 CALCULATIONS TO SUPPORT THE DESIGN OF
 THE PRESSURIZED STAIRS.A PARTIAL
 STATEMENT APPEARS ON SHEET AC 10
 CONTAINS THE STATEMENT "STAIR SHALL BE
 PRESSURIZED TO 0.05" W.G. RELATIVE TO
 ATMOSPHERE, INCLUDING ANY STACK EFFECT
 FOR THE REST OF THE BUILDING."
  
 THIS STATEMENT IS SUGGESTIVE OF SBC 412.
 11 (5) BUT DOES NOT ACCOMPLISH A
 DEMONSTRATION OF HOW THE DESIGN WAS
 ARRIVED AT. PLEASE PROVIDE CALCULATIONS
 DEMOSTRATING COMPLIANCE WITH SBC 412.11
 (5)
  
 THE AC PLANS INDICATE FIRE DAMPERS FOR
 THE MISCELLANEOUS EQUIPMENT PENETRATING
 THE FIRE RATED WALL ON THE SOUTH SIDE
 OF THE BUILDING.SBC 705.1.3.1
 REQUIRESLISTED DEVICES TO BE TESTED IN
 ACCORDANCE WITH NFPA 80 AND FIRE
 DAMPERS ARE TESTED TO UL 555, PLEASE
 ENSURE WITH NOTES, SPECIFICATIONS OR
 DETAILS THAT SBC 705.1.3.1 WILL BE
 COMPLIED WITH FOR ALL PENETRATIONS
 WHERE APPLICABLE.
  
 FL STATUTE 553.8(2)(B) MANDATES THE
 IMPOSITION OF A FEE FOR PLANS THAT ARE
 REJECTED THREE OR MORE TIMES FOR THE
 SAME CODE VIOLATION.A PRINTED COPY IS
 ATTACHED FOR USE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-04-15 Cont ID  
Sent By hpiskura Date 2002-04-15 Time 07:29 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-04-15 00:00:00AS NOTED ON THE 11/16/02 LIST OF CODE
 COMMENTS, THE FLORIDA ACCESSIBILITY
 CODE FOR BUILDING CONSTRUCTION, SECTION
 4.1.2 (5) REQUIRES SIX ACCESSIBLE
 SPACES, SECTION 4.6.3 OF THE FACBC
 REQUIRES
 THEM TO BE TWELVE FEET WIDE WITH AN
 ADJACENT FIVE FEET WIDE AISLE. PLEASE
 REVISE AS NECESSARY.
  
 THE DOOR SCHEDULES DO NOT SHOW THE RATED
 DOORS FOR THE ELEVATOR LOBBIES AS
 REQUIRED BY SBC 412.6.1.(20 MINUTES)
  
 THE 4TH LEVEL FLOOR PLAN ON SHEET A2.06,
 SHADED HATCHED AREA INDICATES A STEP AT
 THE DOOR FROM ELEVATOR LOBBY #1 TO THE
 SPA AREA.THIS IS PROHIBITED BY SBC
 1012.1.3.
  
 SHEET A4.02 IS STILL MISSING
 INFORMATION FOR THE ATTACHMENT OF THE
 PRECAST CONCRETE.SEE SBC 1403.2.
  
 THE PLANS DEPICT THE USE OF"EIFS" TRIM
 IN VARIOUS PLACES.SBC F102.2.7
 REQUIRES ARCHITECTURAL TRIM TO BE OF
 NON-COMBUSTIBLE OR FIRE RETARDANT
 TREATED WOOD.
 EIFS MEETS NEITHER OF THESE DESCRIPTIONS
  
 SHEET S19 INDICATES A COMBINATION OF
 WIND TUNNEL TESTING AND THE ANALYTICAL
 PROCEDURE.ASCE 7-95 SECTION 6.4.1.1
 REQUIRES THATONLY ONE OF THE
 PROCEDURES BE USED.
  
 SHEET A6.01 SHOWS ROOF MOUNTED STAIR
 PRESSURIZATION FAN.AC-1 SHOWS A SUPPLY
 FAN AT THE LOBBY LEVEL.AC-6 SHOWS A
 4650 CFM SUPPLYDUCT AND A 2500 CFM
 EXHAUST DUCT.PROVIDE CALCULATIONS AND
 A NARRATIVE DESCRIBING THE SEQUENCE OF
 OPERATION TO DEMONSTRATE COMPLIANCE WITH
 SBC 412.11 (5) AS PREVIOUSLY REQUESTED.
  
 PLEASE PROVIDE THE DATA FOR THE
 SPRINKLER HEADS THAT WILL PROVIDE AN
 "EQUIVALENT ALTERNATE" FOR FIRE RATED
 OPENING PROTECTIVES.SECTION 553.79 OF
 THE FLORIDA STATUTES REQUIRES THE FIRE
 PROTECTION INFORMATION TO BE ON THE
 PERMIT PLANS AS WELL AS SBC 104.2 AND
 NFPA 13 CHAPTER 6, (OR 8 IN THE 1999
 EDITION)

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-11-16 Cont ID  
Sent By hpiskura Date 2001-11-16 Time 09:07 Rev Time 0.00
Received By hpiskura Date 2001-11-13 Time 16:00 Sent To  
Notes
2001-11-16 00:00:00THE SHEET TITLED TABULAR DATA NOTES 3
 HANDICAP PARKING SPACES USING THE
 FORMULA OF 2% OF THE TOTAL.THAT IS
 INCORRECT.THE FACBC 4.1.2 (5)
 REQUIRES A MINIMUM OF 5 SPACES FOR
 PARKING LOTS HAVING 101 TO 150 TOTAL
 SPACES.
  
 SHOW THE VAN ACCESSIBLE SPACE REQUIRED
 BY FACBC 4.1.2 (5) (B).
  
 SHEET A2.01 SHOWS THE HC SPACES PROPOSED
 TO BE 8'-8" WIDE.THE FACBC 4.6.3
 MANDATES 12' WIDE PARKING SPACES.
 PLEASE REVISE AS NECESSARY.SEE ALSO 4.
 6.5 FOR VERTICAL CLEARANCES.
  
 SHEET A2.01EGRESS FROM THE PARKING
 SPACES ON THE WEST SIDE RAMP DOES NOT
 COMPLY WITH SBC 1004.1.3, COMMON PATH
 OFTRAVEL TO AND EXIT MUST BE 75' OR
 LESS.THE ROLL DOWN DOOR DOES NOT
 COMPLY WITHSBC 1012.1 AND THEREFORE IS
 NOT AN EXIT. REVISE AS NECESSARY.
  
 SHEET A2.02. HANDRAILS ARE REQUIRED ON
 THE RAMP IN STAIR #1.SEE SBC 1013.6.
  
 SHEET A2.01.SBC 412.6.1 REQUIRES
 ELEVATOR LOBBIES FOR ALL ELEVATORS ON
 ALL FLOORS W/ CERTAIN EXCEPTIONS.THE
 GARAGE LEVELS, THE 4TH LEVEL SPA DECK
 ELEVATOR #1 AND THE SERVICE ELEVATOR
 WEST SIDE ON FLOORS 5 THROUGH 15 DO NOT
 QUALIFY FOR THE EXCEPTION.REVISE AS
 NECESSARY.
  
 THE INDIVIDUAL APARTMENTS MUST COMPLY
 WITH SBC 412.6.2, ACCESS TO AN EXIT
 WITHOUT TRAVEL THROUGH AN ELEVATOR
 LOBBY.
  
 STAIRS #1 AND #2 DO NOT MEET THE 1/2
 DIAGONAL DISTANCE SEPARATION
 REQUIREMENT OF SBC 1004.1.4. ON ALL
 FLOORS WITH THE EXCEPTION OF THE
 SUBTERRANEAN LEVEL.PLEASE REVISE AS
 NECESSARY.
  
 SHEET A6.02 NOTES, CALLS FOR THE STAIRS
 TO COMPLY WITH THE SFBC.PLEASE REVISE
 TO INCLUDE AND ENSURE COMPLIANCE WITH
 THE 1997 SBC.
  
 SHEET A3.07 DOOR NOTES #3. UNDERCUTTING
 OF FIRE RATED DOORS MUST BE IN
 ACCORDANCE WITH NFPA 80.
  
 SHOW A SPECIFIC CONNECTION DETAIL FOR
 THE PRECAST STONE DEPICTED ON SHEET
 4.02 AND ELSEWHERE.IF THE DESIGN IS
 DELEGATED TO A SPECIALTY ENGINEER
 INDICATE THE LOCATION, NATURE,
 MAGNITUDE AND DIRECTION OF THE FORCES
 TO BE RESISTED.SEE SBC 104.2.
  
 THE EIFS SHOWN IN DETAIL #50, SHEET
 A7.05 MUST COMPLY WITH SBC 1404.3
 AND SBC APPENDIX F102.7.REVISE AS
 NECESSARY.
  
 SHEET A705 DETAIL 53.WHAT IS THE
 PARAPET HEIGHT THAT SERVES AS A
 GUARDRAIL?THE REFERENCE TO THE
 LANDSCAPE PAGES IS NOT CLEAR.SEE SBC
 1015.
  
 SHEET A6.05.PROVIDE CALCULATIONS FOR
 THE GUARDRAIL AT THE WINDOW
 DEMONSTRATING COMPLIANCE WITH SBC
 1608.2.3.
  
 GIVEN THE CITY'S REQUIREMENT FOR
 HURRICANE MISSILE IMPACT GLAZING, HOW
 WILL COMPLIANCE WITH SBC 1405 BE
 ACCOMPLISHED?PARTICULARLY, BUT NOT
 LIMITED TO, GARAGE
 LEVELS 2 AND 3.
  
 SHEET S18 CITES THE SFBC FOR DESIGN OF
 RAILS.DESIGN MUST BE TO SBC 1997 WITH
 SPECIFIC DESIGN CRITERIA AND NOT A CODE
 SECTION.SEE SBC 104.2.1.
  
 SHEET S19 STRUCTURAL LOADS, DECLARES
 THAT THAT STRUCTURAL ANALYSIS IS PER
 ASCE 7-95 AND THAT COMPONENTS AND
 CLADDING IS BY WIND TUNNEL TESTING.
 ASCE 7-95 6.4.1.1 PROHIBITS THE MIXING
 OF THE METHODS ANALYSIS.IT APPEARS
 THAT THIS SITE IS SUBJECT TO UPWIND
 OBSTRUCTIONS, CHANNELING, BUFFETING,
 ETC. AS DESCRIBED IN SECTION 6.4.2.1
 LIMITATIONS OF ANALYTICAL PROCEDURE,
 THAT A COMPLETE WIND TUNNEL
 INVESTIGATION IS IN ORDER.
  
 SHOW THE DESIGN LOADS FOR THE WALKS
 ALONG THE ARC FORMED ON GRID LINE 4,
 SUBTENDED BY GRID LINE B, IN ACCORDANCE
 WITH SBC 1604.9.
  
 PROVIDE A NARRATIVE FOR THE METHODS OF
 TESTING REQUIRED BY SBC 412.1.2 FOR
 SMOKE REMOVAL AND STAIR PRESSURIZATION
 ON THE STANDBY POWER SYSTEM.
  
 SHEET E10 FIRE ALARM, DOES NOT SHOW THE
 APARTMENT UNIT SMOKE DETECTORS LINKED
 INTO THE SYSTEM AS PROVIDED FOR IN SBC
 412.2.2 AND SBC 412.2.1 (5).
  
 PLEASE PROVIDE CALCULATIONS
 DEMONSTRATING COMPLIANCE WITH SBC
 412.11 (5) IF THAT IS THE INTENDED
 OPTION OR COMPLY WITH SBC 1005.6.
  
 THE CONSTRUCTION BOARD OF ADJUSTMENTS
 AND APPEALS GRANTED TWO VARIANCES AT
 THEIR MAY 10, 2001 MEETING.ONE OF THE
 STIPULATIONS OF THE BOARD WAS THAT "THE
 SPRINKLER HEADS MEET THE RATING
 REQUIREMENTS"AND BE OF AN "EQUIVALENT
 ALTERNATE" PLEASE PROVIDE
 TESTING
 FROM A RECOGNIZED SOURCE THAT
 DEMONSTRATES COMPLIANCE WITH SBC
 705.1.3 (NFPA 80) FOR THE SPRINKLERS.
  
 PROVIDE CALCULATIONS DEMONSTRATING
 COMPLIANCE WITH 411.4.2 FOR THE SIX AIR
 CHANGES PER HOUR IN THE GARAGE.
  
 THE SP DRAWINGS SHOW A RISER/STANDPIPE
 IN A STAIR #3.WHAT IS THE INTENT OF
 THIS?

Review Stop E ELECTRICAL
Rev No 16 Status P Date 2004-03-05 Cont ID  
Sent By dpalmer Date 2004-03-05 Time 16:55 Rev Time 1.00
Received By dpalmer Date 2004-03-05 Time 16:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 15 Status P Date 2004-01-08 Cont ID  
Sent By dpalmer Date 2004-01-08 Time 16:44 Rev Time 1.50
Received By dpalmer Date 2004-01-08 Time 07:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 14 Status P Date 2003-11-03 Cont ID  
Sent By dpalmer Date 2003-11-03 Time 08:05 Rev Time 0.50
Received By dpalmer Date 2003-11-03 Time 08:05 Sent To  
Notes
2003-11-03 00:00:00REV FOR 7C7 AND 7E8

Review Stop E ELECTRICAL
Rev No 13 Status P Date 2003-10-21 Cont ID  
Sent By dpalmer Date 2003-10-21 Time 06:41 Rev Time 1.75
Received By dpalmer Date 2003-10-21 Time 06:14 Sent To  
Notes
2003-10-21 00:00:00*** NOTEREDLINED ****
  
 *** TYPICAL**
  
 WATER HEATER MAY REQUIRE DISC.
 "LOCK OFF" DEVICE TO BE APPROVED BY AHJ.

Review Stop E ELECTRICAL
Rev No 12 Status F Date 2003-08-21 Cont ID  
Sent By dpalmer Date 2003-08-21 Time 07:22 Rev Time 0.50
Received By dpalmer Date 2003-08-21 Time 07:22 Sent To  
Notes
2003-08-21 00:00:00**************** UNSAT ************
  
 1)NOTE: PLEASE SUBMIT ALL REVISIONS FOR
 LIGHTNING PROTECTION SYSTEM UNDER THAT
 PERMIT. (#02121457)
  
 2)NOTE: PLEASE PROVIDE A COPY OF THE
 CONTRACT FOR COMPLETE LIGHTNING PROTECT-
 -ION SYSTEM. ORIG VALUE WAS ISSUED AT
 $8800.???
 PLEASE NOTE, THIS IS TO INCLUDE ALL
 LABOR AND MATERIALS.104.6.5 FBC/FAC/CITY
 ADMIN CODE. ETC.
  
 PLEASE NOTE, PATRICK POWER IS CONT WHO
 PULLED ORIG PERMIT.
  
 PLEASE ALSO NOTE, PERMIT FOR LIGHTNING
 PROTECTION HAS BEEN PUT ON HOLD UNTIL
 COMMENTS ARE ADDRESSED.
  
 PLEASE PROVIDE SUBMITTALS/ SPECS FOR
 EQUIPMENT SHOWN AND BEING INSTALLED.
 ALL EQUIPMENT MUST BE LISTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2003-07-31 Cont ID  
Sent By alange Date 2003-08-08 Time 16:12 Rev Time 1.50
Received By dpalmer Date 2003-07-31 Time 08:42 Sent To  
Notes
2003-07-31 00:00:00ELEC REVISIONS

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2003-07-18 Cont ID  
Sent By dpalmer Date 2003-07-18 Time 15:02 Rev Time 2.00
Received By dpalmer Date 2003-07-18 Time 15:02 Sent To  
Notes
2003-07-18 00:00:00LIGHTING SUBMITTALS ONLY.

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2003-04-08 Cont ID  
Sent By shernand Date 2003-06-20 Time 11:57 Rev Time 6.00
Received By dpalmer Date 2003-04-08 Time 07:20 Sent To  
Notes
2003-04-08 00:00:00******** ******* UNSAT *************
  
 1)NOTE: PLEASE SEE A-SHEETS NOT ORIG
 SIGNATURE ON PLANS UNDER FS/ FAC
 481.221.
 PLEASE ALSO SEE SHEET E-1A IN ONE SET,
 BOTH SEAL AND SIGNATURE IS A COPY.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 PLEASE NOTE, OTHER SHEETS AHVE BEEN
 STAMPED BUT SHOULD NOT COME OUT UNTIL
 ALL SHEETS IN ALL SETS .
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2002-12-26 Cont ID  
Sent By dpalmer Date 2002-12-26 Time 16:50 Rev Time 1.00
Received By dpalmer Date 2002-12-26 Time 16:50 Sent To  
Notes
2002-12-26 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE ALL SPECS SHEETS
 MUST SHOW A LISTING FROM A RECOGNIZED
 TESTING LAB. 110-3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2002-12-26 Cont ID  
Sent By dpalmer Date 2002-12-26 Time 16:05 Rev Time 0.75
Received By dpalmer Date 2002-12-26 Time 16:05 Sent To  
Notes
2002-12-26 00:00:00SUBMITTALS FOR TRANSFER SWITH ONLY.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2002-12-26 Cont ID  
Sent By dpalmer Date 2002-12-26 Time 13:56 Rev Time 0.25
Received By dpalmer Date 2002-12-26 Time 13:56 Sent To  
Notes
2002-12-26 00:00:00************* UNSAT **************
 SUBMITTAL FOR LIGHTING PROTECTION
 SYSTEM REQ`D TO BE SUBMITTED SEPARATELY
 UNDER SEPARATE PERMIT.
 NOT A PART OF ORIG PLANS/BLDG.
  
 PLEASE SUBMIT PLANS/SPECS AND PERMIT
 APPLICATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2002-10-15 Cont ID  
Sent By dpalmer Date 2002-10-15 Time 16:06 Rev Time 0.50
Received By dpalmer Date 2002-10-15 Time 16:06 Sent To  
Notes
2002-10-15 00:00:00SUBMITTALS FOR GENERATOR

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-09-04 Cont ID  
Sent By dpalmer Date 2002-09-04 Time 14:39 Rev Time 0.50
Received By dpalmer Date 2002-09-04 Time 14:39 Sent To  
Notes
2002-09-04 00:00:00ELECTRICAL SPEC BOOKS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-07-19 Cont ID  
Sent By dpalmer Date 2002-07-19 Time 12:55 Rev Time 0.00
Received By dpalmer Date 2002-07-19 Time 06:02 Sent To  
Notes
2002-07-19 00:00:00************** NOTES ****************
  
 NOTES REDLINED ON PLANS FOR WATER
 HEATER DISCONNECTING MEANS. DISC MAY BE
 REQ`D. "LOCK OFF" DEVICE TO BE USED
 MUST BE REVIEWED BY THE CHEIF ELECTRICAL
 INSPECTOR AND MYSELF BEFORE INSTALLING.
 PLEASE CALL IF THERE ARE ANY QUESTIONS,
 OR A MEETING TO VERIFY DEVICE.
 DISC MAY BE SOMETHING AS SIMPLE AS A
 TWO POLE SWITCH.
  
 PLEASE ALSO NOTE THAT DOORS ON MAIN
 ELECTRICAL ROOM AND GENERATOR ROOM
 MUST OPEN OUTWARDS.
  
  
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-04-17 Cont ID  
Sent By dpalmer Date 2002-04-17 Time 06:15 Rev Time 0.00
Received By dpalmer Date 2002-04-17 Time 06:15 Sent To  
Notes
2002-04-17 00:00:00***************** NOTE***************
  
 1)NOTE: PLEASE CALRIFY NO CONCRETE
 ENCASEMENT SHOWN FOR SERVICE ENTRANCE
 INTO MAIN FEEDING "XDP". BACK TO BACK??
 PER LOCAL AMENDMENT 230-70
  
 2)NOTE: PLEASE CLARIFY THAT MAIN FIRE
 PUMP SERVICE RATED ATS HAS AN EXTERNAL
 MANUAL MEANS OF DISCONNECT. PLEASE NOTE,
 THAT NOTE FOR THIS EQUIPMENT MENTIONS
 AN EXTERNAL "SURGE SUPPRESSION", BUT
 NOTHING ABOUT MAIN. 230-76/230-79
 PLEASE NOTE THAT MAIN FEEDING "XDP"
 MENTIONS A MAIN CIRCUIT BREAKER, IS THIS
 THE SAME SET UP?
 PLEASE CLARIFY OCP FOR FIRE PUMP MAIN?
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE NOTE THAT PLANS ARE IN
 GOOD SHAPE, BUT ARE COMING BACK FOR
 OTHER COMMENTS FROM OTHER REVIEWERS.
 IF THERE ARE ANY QUESTIONS/CLARIFICATION
 -S, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-11-06 Cont ID  
Sent By dpalmer Date 2001-11-06 Time 18:49 Rev Time 0.00
Received By dpalmer Date 2001-11-05 Time 22:27 Sent To  
Notes
2001-11-06 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE CLARIFY HOW FEEDS ARE
 COMING INTO "HDP" AND TO "TDP" PLEASE
 NOTE THEY DON'T BACK UP TO TRANSFORMER
 VAULT AND OTHER SERVICE ENTRANCE CONDUCT
 -ORS ARE ENCASED IN CONCRETE.
 PLEASE NOTE THAT NO MORE THAN 8' OF
 UN PROTECTED CONDUCTORS ARE ALLOWED
 "INSIDE" THE BLDG. PER LOCAL AMENDMENT;
 230-70.
  
 2)NOTE: PLEASE SUBMIT SCHEDULE FOR "HDP"
 ?
  
  
  
  
 4)NOTE: PLEASE CLARIFY MANUAL MEANS OF
 DISCONNECT AT ATS FROM FPL SERVICE,
 230-76,230-79
 PLEASE ALSO SHOW OCP FROM FPL LINE SIDE
  
  
 5)NOTE: PLEASE CLARIFYKW RATING FOR
 GENERATOR AND LOAD ? SEEMS LOAD SHOWN
 EXCEEDS GENERATOR RATING OF 833AMPS.
  
 6)NOTE: OCP FOR WATER HEATERS ON PANELS
 "HB" AND "HR". PLEASE NOTE 3KW WITH 30A
 OCP. 422-11 MIN 125% MAX 150%.
 PLEASE ADJUST.
  
 PLEASE SUBMIT THE ABOVEINFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2003-12-31 Cont ID  
Sent By mamini Date 2003-12-31 Time 08:52 Rev Time 0.50
Received By mamini Date 2003-12-31 Time 08:52 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2003-11-05 Cont ID  
Sent By mamini Date 2003-11-05 Time 14:05 Rev Time 0.50
Received By mamini Date 2003-11-05 Time 14:05 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2002-05-16 Cont ID  
Sent By btrobaug Date 2002-11-12 Time 16:56 Rev Time 1.00
Received By mamini Date 2002-05-16 Time 09:03 Sent To  
Notes
2002-05-16 00:00:00N/A:
 1. SEE PERMIT # 02050855 FOR CIVIL/SITE
 WORKS PERMIT.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2002-05-02 Cont ID  
Sent By mamini Date 2002-05-02 Time 10:25 Rev Time 1.00
Received By mamini Date 2002-05-02 Time 10:25 Sent To  
Notes
2002-05-02 00:00:00FAILED :
 1. A SEPARATE PERMIT APPLICATION AND
 FEES FOR CIVIL /SITE WORKS BY THE
 BUILDING DEPARTMENT IS REQUIRED.
 PLEASE SUBMIT THE LATEST CIVIL / SITE
 PLANS APPROVED BY PUBLIC UTILITIES
 ENGINEERING SERVICES DEPARTMENT FOR OUR
 REVIEW AND PERMITTING.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-11-09 Cont ID  
Sent By mamini Date 2001-11-09 Time 09:39 Rev Time 3.00
Received By mamini Date 2001-11-09 Time 09:39 Sent To  
Notes
2001-11-09 00:00:00FAILED:
 1. PER MY PHONE CONVERSATION WITH MR.
 ANDRE DUVAL OF CRAVEN * THOMPSON & ASSO.
 THE CIVIL PLANS THAT SUBMITTED ARE NOT
 FINAL. THE REVISED PLANS, APPROVED BY
 UTILITIES DEPT. WILL BE SUBMITTED FOR
 OUR REVIEW.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 17 Status P Date 2004-03-23 Cont ID  
Sent By nmccray Date 2004-03-23 Time 11:53 Rev Time 0.00
Received By nmccray Date 2004-03-23 Time 11:53 Sent To  
Notes
2004-03-23 00:00:00REVISION SP-1 DATED 3-18-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 16 Status P Date 2004-03-18 Cont ID  
Sent By nmccray Date 2004-03-18 Time 13:40 Rev Time 0.00
Received By nmccray Date 2004-03-18 Time 13:40 Sent To  
Notes
2004-03-18 00:00:00REVISION DATED 3-09-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 15 Status P Date 2004-03-16 Cont ID  
Sent By nmccray Date 2004-03-16 Time 13:15 Rev Time 0.00
Received By nmccray Date 2004-03-16 Time 13:15 Sent To  
Notes
2004-03-16 00:00:00REVISION DATED 02-25-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 14 Status P Date 2004-02-24 Cont ID  
Sent By nmccray Date 2004-02-24 Time 09:48 Rev Time 0.00
Received By nmccray Date 2004-02-24 Time 09:48 Sent To  
Notes
2004-02-24 00:00:00REVISION FOR FLOORING DATED 2-17-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 13 Status P Date 2004-02-20 Cont ID  
Sent By mcarsill Date 2004-02-20 Time 16:02 Rev Time 0.00
Received By mcarsill Date 2004-02-20 Time 16:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 12 Status P Date 2004-01-29 Cont ID  
Sent By mcarsill Date 2004-01-29 Time 15:10 Rev Time 0.00
Received By mcarsill Date 2004-01-29 Time 15:10 Sent To  
Notes
2004-01-29 00:00:001) INTERIOR FINISH MATERIALS ON WALLS
 AND CEILINGS SHALL COMPLY WITH
 BUILDING AND FIRE CODE REQUIREMENTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 11 Status P Date 2004-01-07 Cont ID  
Sent By mcarsill Date 2004-01-07 Time 09:29 Rev Time 0.00
Received By mcarsill Date 2004-01-07 Time 09:29 Sent To  
Notes
2004-01-07 00:00:001) ALL ARCHITECTURAL FOAM AND PANELS
 INSTALLED ON THE BUILDING SHALL BE
 MEET THE REQUIREMENTS FOR FIRE LIMIT
 LOCATIONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status P Date 2003-11-26 Cont ID  
Sent By mcarsill Date 2003-11-26 Time 17:17 Rev Time 0.00
Received By mcarsill Date 2003-11-26 Time 17:17 Sent To  
Notes
2003-11-26 00:00:001) PLEASE BE ADVISED THAT SOME
 LOCATIONS REQUIRE A WATER CURTAIN.
 PLEASE REVIEW INFORMATION FROM THE
 CONSTRUCTION BOARD OF ADJUSTMENT
 AND APPEALS AND PERFORM ACCORDINGLY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status P Date 2003-10-30 Cont ID  
Sent By mcarsill Date 2003-10-30 Time 16:35 Rev Time 0.00
Received By mcarsill Date 2003-10-30 Time 16:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2003-10-09 Cont ID  
Sent By mcarsill Date 2003-10-09 Time 17:33 Rev Time 0.00
Received By mcarsill Date 2003-10-09 Time 17:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2003-07-29 Cont ID  
Sent By mcarsill Date 2003-07-29 Time 17:23 Rev Time 0.00
Received By mcarsill Date 2003-07-29 Time 17:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status F Date 2003-05-01 Cont ID  
Sent By nmccray Date 2003-05-01 Time 10:19 Rev Time 0.00
Received By nmccray Date 2003-04-30 Time 10:48 Sent To  
Notes
2003-05-01 00:00:00*************DENIED*********************
 1) SEPARATION WITHIN PARKING STRUCTURE
 SHALL BE FIRE RATED NOT LESS THAN TWO
 HOURS.
  
 2) SMOKE EVACUATION SYSTEM WAS APPROVED
 NOT SMOKE CONTROL.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2002-11-08 Cont ID  
Sent By mcarsill Date 2002-11-08 Time 18:53 Rev Time 0.00
Received By mcarsill Date 2002-11-08 Time 18:53 Sent To  
Notes
2002-11-08 00:00:00SUBMITTALS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-08-02 Cont ID  
Sent By mcarsill Date 2002-08-02 Time 16:13 Rev Time 0.00
Received By mcarsill Date 2002-08-02 Time 16:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2002-07-25 Cont ID  
Sent By mcarsill Date 2002-07-25 Time 15:45 Rev Time 0.00
Received By mcarsill Date 2002-07-25 Time 15:45 Sent To  
Notes
2002-07-25 00:00:00THE "WS VERTICAL" CENTRAL FIRE
 SPRINKLER HEAD TECHNICAL DATA SHEET
 INDICATES THAT THE USE AND THEIR
 INSTALLATION DOES NOT FOLLOW THE
 LISTED MANUFACTURER'S CRITERIA. SUFFOLK
 CONSTRUCTION WAS CONTACTED BY TELEPHONE
 ON 7.25.02 AND ADVISED OF THIS.
 THE DESIGNER'S ARE TO REVIEW THE
 TECHNICAL DATA SHEET PROVIDED FOR THESE
 FIRE SPRINKLER HEADS AND ENSURE THAT
 THE FIRE SPRINKLER HEADS ARE INSTALLED
 PROPERLY WITH REGARDS TO THEIR
 INTENDED USE AND LISTINGS.
  
 2) ALL FIRE ALARM DEVICES ARE TO
 ACTIVATE THE STAIRWELL PRESSURIZATION
 FANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-05-03 Cont ID  
Sent By mcarsill Date 2002-05-03 Time 12:12 Rev Time 0.00
Received By mcarsill Date 2002-05-03 Time 12:12 Sent To  
Notes
2002-05-03 00:00:001) ELECTRONIC SWITCHES WILL BE REQUIRED
 ON FIRE PROTECTION BACKFLOW DEVICES.
  
 2) OCCUPANCY SEPARATIONS AND FIRE
 RESISTANCE OF WALLS INDICATES A ONE HOUR
 FIRE SEPARATION BETWEEN THE GARAGE AND
 THE BUILDING. A TWO HOUR FIRE SEPARATION
 IS REQUIRED.
  
 3) SEVERAL DOORS INCLUDING EXIT DOORS
 SWING OVER THE PROPERTY LINES FOR THE
 BUILDING.
  
 4) HOW DO THE EXIT DOORS THAT TERMINATE
 ON THE SOUTH SIDE OF THE BUILDING INTO
 THE ALLEY NOT BECOME OBSTRUCTED OR
 BLOCKED.
  
 5) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWING PAGE A4.02.
  
 6) THE PLAN REVIEW COMMENTS OMITTED THAT
 STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 7) ANY FIRE ALARM INITIATING DEVICE OR
 FIRE SPRINKLER HEAD ACTIVATIONS ARE TO
 INITIATE THE STAIRWELL PRESSURIZATION
 FANS.
  
 8) STAIR PRESSURIZATION IS 0.05 WATER
 COLUMN TO INCLUDE MAXIMUM ANTICIPATED
 STACK EFFECT FOR THE REST OF THE
 BUILDING.
  
 9) EIFS NOTED FOR BUILDING. PLEASE
 REVIEW APPENDIX F OF THE STANDARD
 BUILDING CODE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-10-24 Cont ID  
Sent By mcarsill Date 2001-10-24 Time 13:09 Rev Time 0.00
Received By mcarsill Date 2001-10-24 Time 13:09 Sent To  
Notes
2001-10-24 00:00:001) PLEASE BE ADVISED THAT THIS
 BUILDING WILL BE LOCATED IN THE CITY
 FIRE LIMITS. PLEASE BE ADVISED THAT
 CERTAIN RESTRICTIONS APPLY TO
 BUILDINGS LOCATED IN THESE LIMTS.
 PLEASE SEE APPENDIX F OF THE STANDARD
 BUILDING CODE AND CHAPTER 11 OF THE
 CITY CODE.
 2) SEPARATION BETWEEN THE PARKING
 GARAGE AND OTHER PORTIONS OF THE
 BUILDING SHALL BE AT LEAST TWO HOURS
 AND NOT ONE HOUR AS DEPICTED.
 3) WRONG LIFE SAFETY CODE REFERENCED
 ON THE PLANS. SHOULD READ 1985 EDITION
 INSTEAD OF 1997.
 4) FIRE HYDRANTS NOT SHOWN ON DRAWINGS.
 5) TEMPORARY STANDPIPES ARE REQUIRED
 DURING CONSTRUCTION WHEN THE BUILDING
 REACHES THREE STORIES AND FIFTY FEET
 IN HEIGHT. ALSO EXIT STAIRS ARE TO BE
 KEPT UP WITH CONSTRUCTION.
 6) PLEASE INDICATE LOCATION ON KNOX-BOX.
 7) PLEASE INDICATE COMPLIANCE WITH
 STRETCHER REQUIREMENTS OF THE STANDARD
 BUILDING CODE.
 8) FIRE COMMAND ROOM SHALL CONTAIN
 ALL OF THE PRESCRIPTIVE REQUIREMENTS
 OF THE STANDARD BUILDING CODE.
 9) PLEASE EXPLAIN PURPOSE OF GATES AT
 STAIRS ON THE ROOF.
 10) PLEASE INDICATE ON THE PLANS THE
 NUMBER OF AIR CHANGES REQUIRED FOR THE
 CLOSED PARKING GARAGE. ALSO INDICATE
 AIR EXHAUST VOLUMES.
 11) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 12) CANVAS CANOPIES TO BE FIRE
 RETARDANT.
 13) PLEASE VERIFY THAT THE FIRE
 SPRINKLER HEADS PLANNED FOR USE ARE NOT
 ON THE VOLUNTARY RECALL LIST PROVIDED.
 14) PLEASE INDICATE WHAT THE VOICE
 EVACUATION MESSAGE WILL SAY FOR THE
 FIRE ALARM SYSTEM.
 15) PLEASE FURTHER EXPLAIN # 15 ON DOOR
 SCHEDULE NOTES.
 16) HOW IS EXITING DIMINISHED WHEN THE
 GARAGE DOORS ARE CLOSED.
 17) PLEASE INDICATE WHAT THE HANDRAILS
 AND GUARDRAILS RATED FOR.
 18) PLEASE PROVIDE MORE INFORMATION ON
 THE INSULATION PLANNED FOR USE ON THE
 TRASH-CHUTE.
 19) PLEASE EXPLAIN WHY NO FIRE SPRINKLER
 HEADS ARE SHOWN IN THE WALKWAY AREA.
 20) NO PENETRATIONS ALLOWED IN THE
 STAIRWELLS EXCEPT FOR EMERGENCY LIGHTING
 AND FIRE PROTECTION SYSTEMS.
 21) PLEASE DEMONSTRATE COMPLAINCE FOR
 SEPARATION OF EXITS.
 22) PLEASE PROVIDE TESTING CRITERIA FOR
 THE STAIRWELL PRESSURIZATION EQUIPMENT
 CONTAINED WITHIN THE BUILDING.
 23) FIRE SPRINKLER DRAWINGS HAVE FIRE
 COMMAND ROOM AND VALET ROOM SWITCHED.
 24) CONDUIT SHAFTS ARE TO BE PROPERLY
 FIRE RATED. PLEASE INDICATE THIS ON
 THE PLANS.
 25) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEMS AND FIRE
 ALARM SYSTEMS.
 26) ELEVATORS TO COMPLY WITH ANSI A17.1.
 27) HOW IS COMBUSTIBLE LINT REMOVED FROM
 DRYER EXHAUST VENTS.
 28) ARE POOL CHEMICALS PLANNED TO BE
 STORED IN POOL EQUIPMENT ROOMS.
 29) ANY CHANGES IN ELEVATIONS LESS THAN
 21 INCHES SHALL BE BY RAMPS.
 30) FIRST FLOOR RETAIL SPACES ARE TO
 MEET MINIMUM FIRE SAFETY REQUIREMENTS
 PRIOR TO BUILDING RECEIVING APPROVALS.
 31) PLEASE DEMONSTRATE COMPLIANCE WITH
 SMOKE CONTROL REQUIREMENTS FROM THE
 STANDARD BUILDING CODE.
 32) WHAT WILL THE ACCESS PANEL DOOR
 BELOW THE MECHANICAL ROOM METAL
 ACCESS STAIR BE USED FOR.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 67 Status N Date 2004-03-25 Cont ID  
Sent By csiegber Date 2004-03-25 Time 15:20 Rev Time 0.00
Received By csiegber Date 2004-03-25 Time 15:20 Sent To B
Notes
2004-03-25 00:00:00TO SH DESK/SUBMITTAL/

Review Stop I INCOMING/PROCESSING
Rev No 66 Status N Date 2004-03-22 Cont ID  
Sent By csiegber Date 2004-03-22 Time 11:54 Rev Time 0.00
Received By csiegber Date 2004-03-22 Time 11:52 Sent To  
Notes
2004-03-22 00:00:00TO NEIL MELICK/LM BOX

Review Stop I INCOMING/PROCESSING
Rev No 65 Status N Date 2004-03-19 Cont ID  
Sent By csiegber Date 2004-03-19 Time 16:19 Rev Time 0.00
Received By csiegber Date 2004-03-19 Time 16:19 Sent To  
Notes
2004-03-19 00:00:00TO KS DESK/PER LM

Review Stop I INCOMING/PROCESSING
Rev No 64 Status N Date 2004-03-19 Cont ID  
Sent By csiegber Date 2004-03-19 Time 16:18 Rev Time 0.00
Received By csiegber Date 2004-03-19 Time 16:18 Sent To B
Notes
2004-03-19 00:00:00TO HP DESK/PER REQUEST

Review Stop I INCOMING/PROCESSING
Rev No 63 Status N Date 2004-03-16 Cont ID  
Sent By csiegber Date 2004-03-16 Time 15:40 Rev Time 0.00
Received By csiegber Date 2004-03-16 Time 15:40 Sent To B
Notes
2004-03-16 00:00:00TO SH DESK/REV/A2-06/A3-03

Review Stop I INCOMING/PROCESSING
Rev No 62 Status N Date 2004-03-16 Cont ID  
Sent By csiegber Date 2004-03-16 Time 15:29 Rev Time 0.00
Received By csiegber Date 2004-03-16 Time 15:29 Sent To B
Notes
2004-03-16 00:00:00TO SH DESK/SUBMITTAL/PRECAST POT

Review Stop I INCOMING/PROCESSING
Rev No 61 Status N Date 2004-03-17 Cont ID  
Sent By csiegber Date 2004-03-16 Time 09:19 Rev Time 0.00
Received By csiegber Date 2004-03-16 Time 09:19 Sent To B
Notes
2004-03-16 00:00:00TO COMM BD#50

Review Stop I INCOMING/PROCESSING
Rev No 60 Status N Date 2004-03-04 Cont ID  
Sent By csiegber Date 2004-03-04 Time 13:45 Rev Time 0.00
Received By csiegber Date 2004-03-04 Time 13:44 Sent To  
Notes
2004-03-04 00:00:00TO COMM BD#13

Review Stop I INCOMING/PROCESSING
Rev No 59 Status N Date 2004-03-01 Cont ID  
Sent By csiegber Date 2004-03-01 Time 12:25 Rev Time 0.00
Received By csiegber Date 2004-03-01 Time 12:25 Sent To P
Notes
2004-03-01 00:00:00TO KS BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 58 Status N Date 2004-03-01 Cont ID  
Sent By csiegber Date 2004-03-01 Time 12:10 Rev Time 0.00
Received By csiegber Date 2004-03-01 Time 12:10 Sent To P
Notes
2004-03-01 00:00:00TO KS BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 57 Status N Date 2004-03-01 Cont ID  
Sent By csiegber Date 2004-03-01 Time 11:30 Rev Time 0.00
Received By csiegber Date 2004-03-01 Time 11:30 Sent To  
Notes
2004-03-01 00:00:00TO COMM BD#28

Review Stop I INCOMING/PROCESSING
Rev No 56 Status N Date 2004-02-20 Cont ID  
Sent By csiegber Date 2004-02-20 Time 16:46 Rev Time 0.00
Received By csiegber Date 2004-02-20 Time 16:21 Sent To  
Notes
2004-02-20 00:00:00TO COMM BD# 33

Review Stop I INCOMING/PROCESSING
Rev No 55 Status N Date 2004-02-20 Cont ID  
Sent By csiegber Date 2004-02-20 Time 16:05 Rev Time 0.00
Received By csiegber Date 2004-02-20 Time 16:05 Sent To B
Notes
2004-02-20 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 54 Status N Date 2004-02-18 Cont ID  
Sent By csiegber Date 2004-02-18 Time 12:26 Rev Time 0.00
Received By csiegber Date 2004-02-18 Time 12:26 Sent To  
Notes
2004-02-18 00:00:00TO COMM BD#60

Review Stop I INCOMING/PROCESSING
Rev No 53 Status N Date 2004-02-12 Cont ID  
Sent By ptjomsto Date 2004-02-12 Time 08:05 Rev Time 0.00
Received By ptjomsto Date   Time   Sent To  
Notes
2004-02-12 00:00:00GIVEN TO KEN STEVENS

Review Stop I INCOMING/PROCESSING
Rev No 52 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 14:05 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 14:05 Sent To B
Notes
2004-02-11 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 51 Status N Date 2004-01-28 Cont ID  
Sent By csiegber Date 2004-01-28 Time 16:09 Rev Time 0.00
Received By csiegber Date 2004-01-28 Time 16:09 Sent To B
Notes
2004-01-28 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 50 Status N Date 2004-01-23 Cont ID  
Sent By csiegber Date 2004-01-22 Time 16:29 Rev Time 0.00
Received By csiegber Date 2004-01-23 Time 09:12 Sent To  
Notes
2004-01-22 00:00:00TO COMM BD#53

Review Stop I INCOMING/PROCESSING
Rev No 49 Status N Date 2004-01-05 Cont ID  
Sent By csiegber Date 2004-01-05 Time 08:57 Rev Time 0.00
Received By csiegber Date 2004-01-05 Time 08:57 Sent To B
Notes
2004-01-05 00:00:00TO SH DESK/SUBMITTAL FRAMING ARCH WALL

Review Stop I INCOMING/PROCESSING
Rev No 48 Status N Date 2003-12-30 Cont ID  
Sent By csiegber Date 2003-12-30 Time 15:51 Rev Time 0.00
Received By csiegber Date 2003-12-30 Time 15:51 Sent To  
Notes
2003-12-30 00:00:00TO COMM BD#55/3 ROLLS ON BACK SHELF

Review Stop I INCOMING/PROCESSING
Rev No 47 Status N Date 2003-12-29 Cont ID  
Sent By csiegber Date 2003-12-29 Time 10:05 Rev Time 0.00
Received By csiegber Date 2003-12-29 Time 10:05 Sent To B
Notes
2003-12-29 00:00:00TO HP DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 46 Status N Date 2003-11-24 Cont ID  
Sent By csiegber Date 2003-11-24 Time 13:41 Rev Time 0.00
Received By csiegber Date 2003-11-24 Time 13:41 Sent To B
Notes
2003-11-24 00:00:00TO HP DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 45 Status N Date 2003-11-05 Cont ID  
Sent By csiegber Date 2003-11-05 Time 15:27 Rev Time 0.00
Received By csiegber Date 2003-11-05 Time 15:27 Sent To B
Notes
2003-11-05 00:00:00TO HP DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 44 Status N Date 2003-10-28 Cont ID  
Sent By csiegber Date 2003-10-28 Time 08:37 Rev Time 0.00
Received By csiegber Date 2003-10-28 Time 08:37 Sent To B
Notes
2003-10-28 00:00:00HP DESK/SUBMITTAL/BALCONY RAILS
 SUBMITTAL/VEHICULAR CABLE RAIL
 SUBMITTAL/METAL DECKING & FASTENING

Review Stop I INCOMING/PROCESSING
Rev No 43 Status N Date 2003-10-28 Cont ID  
Sent By csiegber Date 2003-10-28 Time 08:32 Rev Time 0.00
Received By csiegber Date 2003-10-28 Time 08:32 Sent To B
Notes
2003-10-28 00:00:004 SUMBMITTALS
 SUBMITTAL/ROOF TILE
 SUBMITTAL/STAIR & HAND RAIL
 SUBMITTAL/GYPSUM CEILING PANELS
 SUBMITTAL/ROOF SHUTTLE CALCS

Review Stop I INCOMING/PROCESSING
Rev No 42 Status N Date 2003-10-27 Cont ID  
Sent By csiegber Date 2003-10-27 Time 15:10 Rev Time 0.00
Received By csiegber Date 2003-10-27 Time 15:10 Sent To  
Notes
2003-10-27 00:00:00TO DON NEELEY DESK

Review Stop I INCOMING/PROCESSING
Rev No 41 Status N Date 2003-10-14 Cont ID  
Sent By csiegber Date 2003-10-14 Time 08:55 Rev Time 0.00
Received By csiegber Date 2003-10-14 Time 08:55 Sent To M
Notes
2003-10-14 00:00:00TO PK BOX

Review Stop I INCOMING/PROCESSING
Rev No 40 Status N Date 2003-10-10 Cont ID  
Sent By csiegber Date 2003-10-10 Time 16:47 Rev Time 0.00
Received By csiegber Date 2003-10-10 Time 16:47 Sent To B
Notes
2003-10-10 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 39 Status N Date 2003-10-03 Cont ID  
Sent By csiegber Date 2003-10-03 Time 12:46 Rev Time 0.00
Received By csiegber Date 2003-10-03 Time 12:46 Sent To  
Notes
2003-10-03 00:00:00TO COMM BD#40/REV

Review Stop I INCOMING/PROCESSING
Rev No 38 Status N Date 2003-09-29 Cont ID  
Sent By csiegber Date 2003-09-29 Time 11:30 Rev Time 0.00
Received By csiegber Date 2003-09-29 Time 11:30 Sent To B
Notes
2003-09-29 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 37 Status N Date 2003-09-19 Cont ID  
Sent By csiegber Date 2003-09-19 Time 10:08 Rev Time 0.00
Received By csiegber Date 2003-09-19 Time 10:08 Sent To M
Notes
2003-09-19 00:00:00TO PK DESK/SMOKE EVAC DUCT

Review Stop I INCOMING/PROCESSING
Rev No 36 Status N Date 2003-09-15 Cont ID  
Sent By csiegber Date 2003-09-15 Time 14:27 Rev Time 0.00
Received By csiegber Date 2003-09-15 Time 14:27 Sent To B
Notes
2003-09-15 00:00:00TO HP DESK/FPL DOOR HDWR SCHD

Review Stop I INCOMING/PROCESSING
Rev No 35 Status N Date 2003-09-15 Cont ID  
Sent By csiegber Date 2003-09-15 Time 14:25 Rev Time 0.00
Received By csiegber Date 2003-09-15 Time 14:25 Sent To B
Notes
2003-09-15 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 34 Status N Date 2003-09-15 Cont ID  
Sent By csiegber Date 2003-09-15 Time 14:24 Rev Time 0.00
Received By csiegber Date 2003-09-15 Time 14:24 Sent To M
Notes
2003-09-15 00:00:00TO PK DESK

Review Stop I INCOMING/PROCESSING
Rev No 33 Status N Date 2003-09-05 Cont ID  
Sent By csiegber Date 2003-09-05 Time 15:57 Rev Time 0.00
Received By csiegber Date 2003-09-05 Time 15:57 Sent To B
Notes
2003-09-05 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 32 Status N Date 2003-08-14 Cont ID  
Sent By dbaxter Date 2003-08-14 Time 08:29 Rev Time 0.00
Received By dbaxter Date 2003-08-14 Time 08:29 Sent To P
Notes
2003-08-14 00:00:00TO KSTEVENS DESK.

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2003-08-14 Cont ID  
Sent By dbaxter Date 2003-08-14 Time 08:27 Rev Time 0.00
Received By dbaxter Date 2003-08-14 Time 08:27 Sent To M
Notes
2003-08-14 00:00:00TO PKRAUSS DESK.

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2003-08-08 Cont ID  
Sent By alange Date 2003-08-08 Time 16:12 Rev Time 0.00
Received By alange Date 2003-08-08 Time 16:12 Sent To E
Notes
2003-08-08 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2003-08-08 Cont ID  
Sent By alange Date 2003-08-08 Time 16:10 Rev Time 0.00
Received By alange Date 2003-08-08 Time 16:10 Sent To B
Notes
2003-08-08 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2003-08-08 Cont ID  
Sent By alange Date 2003-08-08 Time 16:07 Rev Time 0.00
Received By alange Date 2003-08-08 Time 16:07 Sent To B
Notes
2003-08-08 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2003-08-08 Cont ID  
Sent By alange Date 2003-08-08 Time 16:06 Rev Time 0.00
Received By alange Date 2003-08-08 Time 16:06 Sent To B
Notes
2003-08-08 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2003-07-11 Cont ID  
Sent By shernand Date 2003-07-11 Time 11:17 Rev Time 0.00
Received By shernand Date 2003-07-11 Time 11:17 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2003-07-11 Cont ID  
Sent By shernand Date 2003-07-11 Time 11:14 Rev Time 0.00
Received By shernand Date 2003-07-11 Time 11:14 Sent To B
Notes
2003-07-11 00:00:004 REVISIONS FOR HP DESK.

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2003-07-11 Cont ID  
Sent By shernand Date 2003-07-11 Time 11:12 Rev Time 0.00
Received By shernand Date 2003-07-11 Time 11:12 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2003-07-09 Cont ID  
Sent By shernand Date 2003-07-09 Time 14:20 Rev Time 0.00
Received By shernand Date 2003-07-09 Time 14:20 Sent To  
Notes
2003-07-09 00:00:00COMM BOARD #37. 2 MORE PLANS ON RACK
 NEXT TO CONF. ROOM.

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2003-06-20 Cont ID  
Sent By shernand Date 2003-06-20 Time 11:57 Rev Time 0.00
Received By shernand Date 2003-06-20 Time 11:57 Sent To E
Notes
2003-06-20 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2003-06-06 Cont ID  
Sent By shernand Date 2003-06-06 Time 16:16 Rev Time 0.00
Received By shernand Date 2003-06-06 Time 16:16 Sent To B
Notes
2003-06-06 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2003-05-08 Cont ID  
Sent By shernand Date 2003-05-08 Time 11:53 Rev Time 0.00
Received By shernand Date 2003-05-08 Time 11:53 Sent To  
Notes
2003-05-08 00:00:00COMM BOARD #42

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 11:35 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 11:35 Sent To B
Notes
2003-05-05 00:00:00GAVE TO BILL STAPLES PER CUSTOMER REQUES

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2003-05-02 Cont ID  
Sent By shernand Date 2003-05-02 Time 17:53 Rev Time 0.00
Received By shernand Date 2003-05-02 Time 17:53 Sent To P
Notes
2003-05-02 00:00:00KSTEVENS DESK. SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2003-05-02 Cont ID  
Sent By shernand Date 2003-05-02 Time 17:51 Rev Time 0.00
Received By shernand Date 2003-05-02 Time 17:51 Sent To M
Notes
2003-05-02 00:00:00PK DESK

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2003-05-02 Cont ID  
Sent By shernand Date 2003-05-02 Time 08:46 Rev Time 0.00
Received By shernand Date 2003-05-02 Time 08:46 Sent To B
Notes
2003-05-02 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2003-04-17 Cont ID  
Sent By shernand Date 2003-04-17 Time 14:05 Rev Time 0.00
Received By shernand Date 2003-04-17 Time 14:05 Sent To B
Notes
2003-04-17 00:00:00DON NEELY DESK

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2003-04-11 Cont ID  
Sent By shernand Date 2003-04-11 Time 08:56 Rev Time 0.00
Received By shernand Date 2003-04-11 Time 08:56 Sent To B
Notes
2003-04-11 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2003-03-26 Cont ID  
Sent By sthyng Date 2003-03-26 Time 14:47 Rev Time 0.00
Received By sthyng Date 2003-03-26 Time 14:47 Sent To  
Notes
2003-03-26 00:00:00TO COMM BOARD #19
 PLANS ON RACK, 5 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2003-03-25 Cont ID  
Sent By dpalmer Date 2003-03-25 Time 09:49 Rev Time 0.00
Received By dpalmer Date 2003-03-25 Time 09:49 Sent To B
Notes
2003-03-25 00:00:00SUBMITTALS TO HP`S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2003-03-10 Cont ID  
Sent By dpalmer Date 2003-03-10 Time 12:53 Rev Time 0.00
Received By dpalmer Date 2003-03-10 Time 12:52 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2003-03-10 Cont ID  
Sent By dpalmer Date 2003-03-10 Time 12:24 Rev Time 0.00
Received By dpalmer Date 2003-03-10 Time 12:24 Sent To B
Notes
2003-03-10 00:00:00TO HHP`S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2003-02-18 Cont ID  
Sent By dpalmer Date 2003-02-18 Time 17:34 Rev Time 0.00
Received By dpalmer Date 2003-02-18 Time 17:34 Sent To B
Notes
2003-02-18 00:00:00TO HHP'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2003-02-11 Cont ID  
Sent By dpalmer Date 2003-02-11 Time 11:36 Rev Time 0.00
Received By dpalmer Date 2003-02-11 Time 11:36 Sent To B
Notes
2003-02-11 00:00:00TO HHP'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-02-06 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 16:07 Rev Time 0.00
Received By dpalmer Date 2003-02-06 Time 16:07 Sent To B
Notes
2003-02-06 00:00:00TO HHP'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-02-04 Cont ID  
Sent By dpalmer Date 2003-02-04 Time 10:02 Rev Time 0.00
Received By dpalmer Date 2003-02-04 Time 10:01 Sent To B
Notes
2003-02-04 00:00:00SUBMITTALS TO HHP'S DESK,

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-02-04 Cont ID  
Sent By dpalmer Date 2003-02-04 Time 09:33 Rev Time 0.00
Received By dpalmer Date 2003-02-04 Time 09:33 Sent To B
Notes
2003-02-04 00:00:00TO HHP'S DESK.ELEV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-02-04 Cont ID  
Sent By dpalmer Date 2003-02-04 Time 09:03 Rev Time 0.00
Received By dpalmer Date 2003-02-04 Time 09:03 Sent To B
Notes
2003-02-04 00:00:00SUBMITTAL TO HHP`S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2002-12-05 Cont ID  
Sent By btrobaug Date 2002-12-05 Time 16:21 Rev Time 0.00
Received By btrobaug Date 2002-12-05 Time 16:21 Sent To B
Notes
2002-12-05 00:00:00TO HAROLD P./WRT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-11-12 Cont ID  
Sent By btrobaug Date 2002-11-12 Time 16:56 Rev Time 0.00
Received By btrobaug Date 2002-11-12 Time 16:56 Sent To ENG
Notes
2002-11-12 00:00:00TO MO./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-08 Cont ID  
Sent By btrobaug Date 2002-11-08 Time 16:28 Rev Time 0.00
Received By btrobaug Date 2002-11-08 Time 16:28 Sent To B
Notes
2002-11-08 00:00:00TO HAROLD P./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 15 Status P Date 2004-03-17 Cont ID  
Sent By pkrauss Date 2004-03-17 Time 06:51 Rev Time 0.00
Received By pkrauss Date 2004-03-08 Time 08:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 14 Status P Date 2004-01-20 Cont ID  
Sent By pkrauss Date 2004-01-20 Time 09:32 Rev Time 1.20
Received By pkrauss Date 2004-01-20 Time 09:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 13 Status P Date 2003-11-24 Cont ID  
Sent By pkrauss Date 2003-11-24 Time 10:14 Rev Time 0.45
Received By pkrauss Date 2003-11-24 Time 09:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 12 Status P Date 2003-11-04 Cont ID  
Sent By pkrauss Date 2003-11-04 Time 12:24 Rev Time 1.15
Received By pkrauss Date 2003-11-04 Time 12:23 Sent To  
Notes
2003-11-04 00:00:00UNIT REVISIONS

Review Stop M MECHANICAL (A/C)
Rev No 11 Status P Date 2003-10-15 Cont ID  
Sent By pkrauss Date 2003-10-15 Time 12:05 Rev Time 0.45
Received By pkrauss Date 2003-10-15 Time 12:05 Sent To  
Notes
2003-10-15 00:00:00SUBMITTAL - THE FLAMEBAR DUCT ON FOR
 THE SMOKE EXHAUST FOR THE LOBBY AREA.

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2003-10-07 Cont ID  
Sent By pkrauss Date 2003-10-07 Time 12:24 Rev Time 0.40
Received By pkrauss Date 2003-10-07 Time 12:24 Sent To  
Notes
2003-10-07 00:00:00SHOP DRAWING OF THE FLAMEBAR DUCT FOR
 THE SMOKE EVAC IN THE LOBBY AREA.

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2003-09-18 Cont ID  
Sent By pkrauss Date 2003-09-18 Time 07:25 Rev Time 2.50
Received By pkrauss Date 2003-09-18 Time 07:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2003-09-04 Cont ID  
Sent By pkrauss Date 2003-09-04 Time 11:47 Rev Time 0.35
Received By pkrauss Date 2003-09-04 Time 11:47 Sent To  
Notes
2003-09-04 00:00:00SUBMITTALS FOR SF-3 (ADDED TO LOBBY)
 AND BRAIDED HOSES FOR HEAT PUMPS

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2003-07-14 Cont ID  
Sent By pkrauss Date 2003-07-14 Time 10:16 Rev Time 0.35
Received By pkrauss Date 2003-07-14 Time 10:16 Sent To  
Notes
2003-07-14 00:00:00PROVISO:
  
 ADDITIONAL PERMIT REQUIRED FOR THE FUEL
 OIL. PLEASE PROVIDE PLANS & MANUFACTURER
 SUBMITTAL DATA FOR TANKS, PIPING AND
 EQUIPMENT PERTAINING TO THE FUEL OIL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2003-04-14 Cont ID  
Sent By shernand Date 2003-05-02 Time 17:52 Rev Time 4.14
Received By pkrauss Date 2003-04-14 Time 10:10 Sent To  
Notes
2003-04-14 00:00:00MECHANICAL REVISION PERMIT 01101289
  
 PLAN SHEETS AC-2 THROUGH AC-4A & AC-7
 THROUGH AC-9, ARE ALL APPROVED.
  
 AC-1 & AC-10 PENDING APPROVAL, NOT
 STAMPED DUE TO SUBMITTAL OF ALTERNATE
 METHODS.COMMENT "ALL CEILINGS ARE A
 SMOKE EVAC PLENUM NO COMB. MAT. ARE
 ALLOWED", PLEASE CLARIFY.
  
 PLAN SHEET AC-1A IS NOT SIGNED & SEALED
 BY ENGINEER, COPY SUBMITTED.
  
 PLAN SHEET AC-5, PLEASE CLARIFY THE
 BOTTOM ELEVATION OF EF-6 & THE TOP
 ELEVATION OF THE FLD IN THE ELECTRICAL
 ROOMS.(DISTANCE BETWEEN EXHAUST &
 LOUVERED DOOR IS LESS THAN 10 FT, WILL
 THE EXHAUST TERMINATION BE 2 FT ABOVE
 LOUVERED DOOR?). INDICATE WHAT WILL BE
 STORED IN POOL EQUIP & FOUNTAIN ROOMS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status   Date 2003-03-31 Cont ID  
Sent By pkrauss Date 2003-03-31 Time 15:51 Rev Time 0.35
Received By pkrauss Date 2003-03-31 Time 15:51 Sent To  
Notes
2003-03-31 00:00:00SUBMITTAL FOR LOBBY - CHANGE FROM SMOKE
 EVAC TO A SMOKE CONTROL.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-08-07 Cont ID  
Sent By pkrauss Date 2002-08-07 Time 07:16 Rev Time 0.40
Received By pkrauss Date 2002-08-07 Time 07:15 Sent To  
Notes
2002-08-07 00:00:00APPROVED 8/2/02

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2002-06-26 Cont ID  
Sent By pkrauss Date 2002-06-26 Time 14:44 Rev Time 0.50
Received By pkrauss Date 2002-06-26 Time 14:44 Sent To  
Notes
2002-06-26 00:00:00REFERENCE RESPONSE LETTER DATED JUNE
 12, 2002.
  
 RESPONSE TO COMMENT #1: A 2 HR ENCLOSURE
 WILL BE PROVIDED.SEE ARCHITECTURAL
 PLANS SHEET A-6.02 FOR 2 HR ENCLOSURE.
  
 PLAN SHEET A-6.02-INDICATE STAIR RISER
 & STAIR DETAIL, NO 2 HR ENCLOSURE
 SHOWN.PLEASE REVISE MECHANICAL PLANS
 WITH ANOTE INDICATING DUCT TO BE IN A
 RATED SHAFT PLEASE PROVIDE HR RATING.
 PLEASE REMOVE FIRE DAMPERS ON DUCT
 THAT IS TO BE IN THE SHAFT.
  
 RESPONSE TO COMMENT 2B: A DRYER BOOSTER
 FAN HAS BEEN ADDED TO ALL DRYERS.
  
 PLEASE NOTE SHOULD THE BOOSTER FAN BE
 USED ON THE DRYER EXHAUST A MEANS OF
 NOTIFICATION TO THE OWNER/TENANT WILL
 BE REQUIRED SHOULD THE BOOSTER FAN
 FAIL.
  
 RESPONSE TO COMMENT #4: AXUILIARY DRAIN
 PANS WILL BE PROVIDED FOR ALL HORIZONTAL
 HEAT PUMPS. SEE INSTALLATION DETAILS ON
 SHEET AC-6.
  
 INDICATE ON THE PLAN WHAT WILL SERVE
 AS PROTECTION FOR THE VERTICAL UNITS
 SHOULD THE PRIMARY DRAIN BE RESTRICTED
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-04-05 Cont ID  
Sent By pkrauss Date 2002-04-05 Time 10:15 Rev Time 0.00
Received By pkrauss Date 2002-04-04 Time 14:46 Sent To  
Notes
2002-04-05 00:00:00 
  
 1.PLEASE CLARIFY REVISED PLAN SHEET
 AC-1,EXHAUST DUCT PENETRATES LOBBY
 FLOOR & FIRST FLOOR.PLANS INDICATE
 FIRE DAMPERS AT EACH PENETRATION.
 PLAN SHEET AC-1 LOBBY LEVEL SHOWS
 TOILET EXHAUST TERMINATING ON THIRD
 FLOOR WITH FIRE DAMPERS AT FLOOR
 PENETRATIONS.AS PER 1997 SMC 610.4
 DUCTS EXTENDING THROUGH MORE THAN
 ONE FLOOR SHALL BE PROTECTED BY A
 SHAFT ENCLOSURE. ALSO PLAN SHEET
 AC-3 6" EXHAUST DUCT DOWN, NO FIRE
 DAMPER OR SHAFT INDICATED.
  
 2.DRYER & TOILET EXHAUST TERMINATING
 AT THE BALCONY.THIS CAN ONLY BE
 APPROVED IF THIS AREA IS OPEN TO THE
 OUTDOORS.NO SCREEN ENCLOSURE OR
 SLIDING GLASS DOORS PERMITTED.
 AS PER 1997 SMC 501.3, THE AIR
 REMOVED BY EVERY MECHANICAL EXHAUST
 SYSTEM SHALL BE DISCHARGED OUTDOORS
 AT A POINT WHERE IT WILL NOT CAUSE
 A NUISANCE.
  
 PLEASE NOTE DRYER EXHAUST SHALL BE
 A MINIMUM OF 4".THE MAXIMUM LENGTH
 SHALL BE 25 FT FROM DRYER LOCATION
 TO WALL CAP.5 FT DEDUCTION FOR
 EACH 90 DEGREE RAD. & 2 1/2 FT FOR
 EACH 45 DEGREE RAD.
  
 3.TESTING FOR STAIRWELL PRESSURIATION
 SHALL BE PREFORMED BY INDEPENDENT
 TEST & BALANCE COMPANY. TEST WILL
 CHECK PRESSURE DIFFERENTIAL WITH ALL
 DOORS CLOSED & WITHTHE DOOR AT
 LOWER LEVEL PROPPED OPEN AT APPROX.
 4" TO SIMILATE EXITING DURING AN
 EMERGENCY SITUATION.
  
 4.PLEASE NOTE AUXILIARY DRAIN PANS
 WITH OVERFLOW PROTECTION BY MEANS OF
 A FLOAT SWITCH OR SEPARATE DRAIN
 LINE TERMINATING AT A CONSPICUOUS
 POINT AS PER 1997 SMC 304.8.6.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-11-07 Cont ID  
Sent By pkrauss Date 2001-11-07 Time 14:06 Rev Time 8.00
Received By pkrauss Date 2001-11-05 Time 14:21 Sent To  
Notes
2001-11-07 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.PROVIDE MANUFACTURE SUBMITTAL DATA
 FOR ALL EQUIPMENT.
  
 2.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER ASHRAE 62-89.
  
 3.AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
  
 4.PROVIDE VENTILATION CALCULATIONS
 FOR THE GARAGE SHOWING COMPLIANCE
 WITH 1997 SBC 411.4.2 & 411.5.3
  
 5.INDICATE SMOKE EVACUATION ON PLAN
 FOR THE LOBBY AND COMMON AREAS USED
 FOR EGRESS ON RESIDENTIAL FLOORS.
  
 6.PROVIDE SEQUENCE OF OPERATION FOR
 SMOKE EVACUATION FOR LOBBY AREA AS
 WELL AS COMMON AREAS TO EACH FLOOR.
  
 7.TEST CRITERIA FOR SMOKE EVACUATION.
  
 8.PROVIDE STAIRWELL PRESSURIZATION
 CALCULATIONS.
  
 9.INDICATE ON PLAN DRYER EXHAUST.
 PROVIDE DETAIL OF RISER.
  
 10.CLARIFY LOBBY AREA RESIDENTIAL
 ENTRANCE AND PLAN SHEET AC-2 "OPEN
 TO BELOW".IS THIS AN "ATRIUM"?
  
 11.PROVIDE INFORMATION ON THE
 EMERGENCY GENERATOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 24 Status P Date 2004-03-22 Cont ID  
Sent By kstevens Date 2004-03-22 Time 08:16 Rev Time 0.50
Received By kstevens Date 2004-03-22 Time 08:16 Sent To  
Notes
2004-03-22 00:00:00REVISION OK - IRRIGATION CONTROLLER BOX
 LOCATION CHANGE

Review Stop P PLUMBING
Rev No 23 Status P Date 2004-03-20 Cont ID  
Sent By kstevens Date 2004-03-20 Time 13:06 Rev Time 0.50
Received By kstevens Date 2004-03-20 Time 13:06 Sent To  
Notes
2004-03-20 00:00:00REVISION OK - SHTS A2.06 & A3.03

Review Stop P PLUMBING
Rev No 22 Status P Date 2004-03-20 Cont ID  
Sent By kstevens Date 2004-03-20 Time 13:02 Rev Time 0.50
Received By kstevens Date 2004-03-20 Time 13:02 Sent To  
Notes
2004-03-20 00:00:00REVISION FOR SHT P-3 - ADDED SCUPPERS

Review Stop P PLUMBING
Rev No 21 Status P Date 2004-03-16 Cont ID  
Sent By kstevens Date 2004-03-16 Time 18:14 Rev Time 0.25
Received By kstevens Date 2004-03-16 Time 18:14 Sent To  
Notes
2004-03-16 00:00:00SUBMITTAL OK - ADA HI/LOW DRINKING
 FOUNTAIN

Review Stop P PLUMBING
Rev No 20 Status P Date 2004-03-13 Cont ID  
Sent By kstevens Date 2004-03-13 Time 07:14 Rev Time 0.50
Received By kstevens Date 2004-03-13 Time 07:14 Sent To  
Notes
2004-03-13 00:00:00REVISION OK - SHT P-16 REMOVE POOL TREN-
 CH DRAIN AND ADD 2 DECK DRAINS

Review Stop P PLUMBING
Rev No 19 Status P Date 2004-03-12 Cont ID  
Sent By kstevens Date 2004-03-12 Time 08:26 Rev Time 0.25
Received By kstevens Date 2004-03-12 Time 08:26 Sent To  
Notes
2004-03-12 00:00:00SUBMITTAL OK - P-TRAPS, WASTE & O/F

Review Stop P PLUMBING
Rev No 18 Status P Date 2004-03-10 Cont ID  
Sent By kstevens Date 2004-03-10 Time 18:46 Rev Time 4.00
Received By kstevens Date 2004-03-10 Time 18:46 Sent To  
Notes
2004-03-10 00:00:00REVISION OK - SHTS P-1, P-3, P-4, P-4A,
 P-6, P-14, P-15, & P-16

Review Stop P PLUMBING
Rev No 17 Status P Date 2004-02-12 Cont ID  
Sent By kstevens Date 2004-02-12 Time 10:47 Rev Time 1.00
Received By kstevens Date 2004-02-12 Time 10:47 Sent To  
Notes
2004-02-12 00:00:00AS BUILTS

Review Stop P PLUMBING
Rev No 16 Status F Date 2004-01-17 Cont ID  
Sent By kstevens Date 2004-01-17 Time 08:15 Rev Time 5.50
Received By kstevens Date 2004-01-17 Time 08:15 Sent To  
Notes
2004-01-17 00:00:00REVISION DENITE
 REFERENCE: SPC-94
  
 1) SHT P-5 COOLING TOWER OVERFLOW SHALL
 DRAIN INTO THE STORM SYSTEM NOT THE
 SANITARY SYSTEM.
 2) SHT P-11 SANITARY RISERS NUMBERS 6,
 AND 7. OFF SET VENTS REQUIRED PER SECT-
 ION 917.
 3) SHT P-12 SANITARY RISERS NUMBERS 8,
 11, 22, 23, 26, AND 28. OFFSET VENTS ARE
 REQUIRED PER SECTION 917.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 15 Status P Date 2003-12-05 Cont ID  
Sent By kstevens Date 2003-12-05 Time 18:08 Rev Time 1.00
Received By kstevens Date 2003-12-05 Time 18:08 Sent To  
Notes
2003-12-05 00:00:00REVISION OK - SHTS 8C7 & 8C8

Review Stop P PLUMBING
Rev No 14 Status P Date 2003-11-01 Cont ID  
Sent By kstevens Date 2003-11-01 Time 16:36 Rev Time 1.50
Received By kstevens Date 2003-11-01 Time 16:36 Sent To  
Notes
2003-11-01 00:00:00REVISIONS OK - UNIT REVISIONS

Review Stop P PLUMBING
Rev No 13 Status F Date 2003-08-14 Cont ID  
Sent By kstevens Date 2003-08-14 Time 11:23 Rev Time 0.50
Received By kstevens Date 2003-08-14 Time 11:23 Sent To  
Notes
2003-08-14 00:00:00SUBMITTAL DENIED - SUBMITTAL DOES NOT
 SHOW COMPLIANCE WITH APPROVED STANDARD
 FOR FITTINGS. SECTION 303.4
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 12 Status F Date 2003-07-21 Cont ID  
Sent By kstevens Date 2003-07-21 Time 15:27 Rev Time 10.00
Received By kstevens Date 2003-07-19 Time 17:16 Sent To  
Notes
2003-07-21 00:00:00DENIED
 REFERENCE: SPC-94
 FACBC-97
 FHA-AMEND 98 DESIGN MANUAL
  
 1) SHT P-1 NOT SIGNED, SEALED, & DATED.
 2) SHT P-1A IS THIS A REVISION FOR ALL
 TYPICAL "B" UNITS OR FOR A SPECIFIC UNIT
 3) SHT P-4 NOT SIGNED, SEALED, & DATED.
 4) SHT P-7 NOT SIGNED, SEALED, & DATED.
 5) SHT P-7A NOT SIGNED, SEALED, & DATED.
 5) SHT P-7B NOT SIGNED, SEALED, & DATED.
 6) SHT P-9 NOT SIGNED, SEALED, & DATED.
 7) SHT P-10 NOT SIGNED, SEALED, & DATED.
 8) SHT P-11 NOT SIGNED, SEALED, & DATED.
 9) SHT P-11 OFFSETS FOR STACKS 1, 4, 5,
 6, A RELIEF VENT FOR THE OFFSET SHALL BE
 INSTALLED AS PROVIDED IN CHAPTER 9 AND
 IN NO CASE SHALL A HORIZONTAL BRANCH
 CONNECT WITHIN THE OFFSET OR WITHIN 2FT
 ABOVE OR BELOW THE OFFSET. THE RELIEF
 VENTS SHALL COMPLY WITH SECTIONS 917,
 917.1, 917.2 & 917.3. - SEC 715.4(4)
 10) SHT P-11A NOT SIGNED, SEALED, & DAT-
 ED. RISERS #11, 13, & 18. OFFSET VENTS
 REQUIRED SEC. 917 & ALL SUBSECTIONS. EX-
 TRA FIXTURE UNITS NOT REFLECTED ON RISER
 DIAGRAM.
 11) SHT P-12 RISERS 22, 23, 28, & 26 -
 OFFSET RELIEF VENTS REQUIRED PER SECTION
 917. ALSO SEE SECTION 715.4(4).
 12) SHT P-15 NOT SIGNED, SEALED, & DATED
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 11 Status F Date 2003-08-14 Cont ID  
Sent By kstevens Date 2003-08-14 Time 10:48 Rev Time 1.50
Received By kstevens Date 2003-07-12 Time 15:09 Sent To  
Notes
2003-08-14 00:00:00SUBMITTALS DENIED
  
 WASTE & OVERFLOWS, P-TRAPS, & BASKET
 STRAINERS NOT SHOWING COMPLIANCE TO
 STANDARDS FOR THESE PLUMBING FITTINGS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 10 Status P Date 2003-05-27 Cont ID  
Sent By kstevens Date 2003-05-27 Time 14:01 Rev Time 1.00
Received By kstevens Date 2003-05-27 Time 14:00 Sent To Z
Notes
2003-05-27 00:00:00IRRIGATION SUBMITTALS OK -

Review Stop P PLUMBING
Rev No 9 Status P Date 2003-05-10 Cont ID  
Sent By kstevens Date 2003-05-10 Time 07:42 Rev Time 0.75
Received By kstevens Date 2003-05-10 Time 07:41 Sent To  
Notes
2003-05-10 00:00:00SUBMITTALS - OK - SUBJECT TO 303.4 SPC

Review Stop P PLUMBING
Rev No 8 Status F Date 2003-04-26 Cont ID  
Sent By shernand Date 2003-05-02 Time 17:53 Rev Time 9.50
Received By kstevens Date 2003-04-25 Time 17:56 Sent To  
Notes
2003-04-25 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) SHT P-1A ALL REVISED SHEET SHALL BE
 SIGNED AND SEALED. SEAL IS A COPY AND
 NOT RAISED.
 2) SHT P-2 NO REVISIONS INDICATED.
 STAMPED SET DATED 6-5-2 SHOWS REVISION
 #3 TRIANGLE. LATEST REVISION DATED 1-23-
 3 SHOWS #3 TRINAGLE ALSO. PLEASE CLAIRFY
 3) SHT P-3 4" HUB DRAIN NOT APPROVED.
 FLOOR SINK IS REQUIRED FOR ALL INDIRECT
 WASTE. PLEASE INDICATE WHAT IS BEING
 DRAINED INTO HUB DRAIN.
 4) SHT P-4 TRIANGLE #4. NO CHANGES IN-
 DICATED FOR THIS REVISION. PLEASE CLAIR-
 FY.
 5) P-4A LEVEL 11, PLEASE CLOUD AND DART
 ALL REVISIONS. MANY CHANGES FROM STAMPED
 SET NOT CLOUDED. THERE ARE TWO #3 TRI-
 ANGLES. PLEASE CLAIRFY. NO #6 TRIANGLE
 6) SHT P-4A INDICATE WHERE ELIMINATED
 3" RWL ARE BEING REROUTED TO. NO TRI-
 ANGLE #6 SHOWN ON REVISION SECTION.??
 7) PLEASE SHOW ALL REVISIONS ON REVISION
 SECTION AND CLOUD ALL CHANGES ON ALL
 SHEETS. REVISIONS ARE VAGUE AND UNCLEAR.
 BACKFLOW REQUIRED FOR NOTE #4
 8) SHT P-7B NEW UNIT BC COMBO, SANITARY
 RISER AND WATER RISER DIAGRAM REQUIRED.
 SPECIFICATION "A" OR "B" AND CLEAR FLOOR
 SPACE TO BE SHOWN ON PLANS.
 9) SHT P-8B NEW UNIT F, SANITARY RISER
 AND WATER RISER DIAGRAM REQUIRED. SPECI-
 FICATION "A" OR "B" AND CLEAR FLOOR
 SPACE TO BE SHOWN ON PLANS.
 10) NOTE: ALL CHANGES TO THE SANITARY,
 STORM, OR WATER SYSTEMS SHALL BE REFLEC-
 TED ON THE RISER DIAGRAM OF THE SYSTEM
 BEING REVISED. PLEASE REVISE RISER DIA-
 GRAMS
 11) NOTE: REVISION NUMBERS SHALL MATCH
 MATCH NUMBERS STATED AS REVISIONS. SOME
 SHEETS SHOW REVISION THAT THERE IS NO
 NUMBER FOR. SOME SHEETS SHOW A NUMBERED
 REVISION AND NO CHANGE IS FOUND. PLEASE
 CLAIRFY.
 12) CHANGES TO STRUCTURAL SHEETS S-1 AND
 S-2 INDICATE TRENCH DRAINS ADDED TO THE
 LOWER RAMP, AND AT NORTH ENTRANCE AT THE
 LOBBY LEVEL. THESE REVISIONS ARE NOT
 SHOWN ON THE PLUMBING SHEETS. PLEASE
 INDICATE HOW THESE WILL BE PIPED AND
 WHAT PLUMBING SHEETS THESE REVISIONS
 WILL BE ADDRESSED ON. ALSO INDICATE ON
 THE RISER THESE REVISIONS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 7 Status P Date 2002-11-02 Cont ID  
Sent By kstevens Date 2002-11-02 Time 15:16 Rev Time 0.50
Received By kstevens Date 2002-11-02 Time 15:15 Sent To  
Notes
2002-11-02 00:00:00SUBMITTAL - BACKWATER VALVE - ELEVATOR
 SUMP PUMP - CONDENSATE SUMP PUMP

Review Stop P PLUMBING
Rev No 6 Status P Date 2002-08-17 Cont ID  
Sent By kstevens Date 2002-08-17 Time 14:13 Rev Time 0.00
Received By kstevens Date 2002-08-17 Time 14:13 Sent To  
Notes
2002-08-17 00:00:00SUBMITTALS OK - INSULATION AND STAND

Review Stop P PLUMBING
Rev No 5 Status P Date 2002-08-08 Cont ID  
Sent By kstevens Date 2002-08-08 Time 13:15 Rev Time 0.00
Received By kstevens Date 2002-08-08 Time 13:15 Sent To  
Notes
2002-08-08 00:00:00SUBMITTAL OK - DRAINS, CORRUGATED PIPE,
 FILTER FABRIC, PIPE /STORM SANT COND,
 DOM. H2O, FUEL OIL. HANGERS, GARAGE SUMP
 PUMP.

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-08-02 Cont ID  
Sent By kstevens Date 2002-08-02 Time 16:26 Rev Time 0.00
Received By kstevens Date 2002-08-02 Time 16:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-07-15 Cont ID  
Sent By kstevens Date 2002-07-15 Time 10:20 Rev Time 0.00
Received By kstevens Date 2002-07-08 Time 17:42 Sent To  
Notes
2002-07-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA AMEND-98 DESIGN MANUAL
  
 1) PER CLAIRFICATION FROM FAIR HOUSING,
 PROGRAMS BRANCH CHIEF, DIANE COOK LEE
 (305) 536-4479 X 2213, THE VANITY CABIN-
 ET FOR ALL "B" UNITS ON SHTS A3.04,
 A3.05 & A3.06 SHALL BE REMOVABLE. PLEASE
 SHOW ON DETAILS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-04-20 Cont ID  
Sent By kstevens Date 2002-04-20 Time 15:57 Rev Time 0.00
Received By kstevens Date 2002-04-20 Time 15:57 Sent To  
Notes
2002-04-20 00:00:00DENIED
 REFERENCE: SPC-94 - FHA-24 CODE OF REGU-
 LATION (CFR) 100.205
 (C)(IV) DESIGN MAN.
  
 1) FROM PREVIOUS REVIEW, SHOW CLEAR
 FLOOR SPACE FOR ALL BATHROOMS AND KIT.
 FIXTURES PER DESIGN MANUAL.
 2) FROM PREVIOUS REVIEW, SHT L3.02,04.
 COMMENT ASKED TO SHOW PREVENTER LOCATION
 FOR WATER FEATURE, REPLY SAID NOTE WAS
 ADDED. PLEASE SHOW WHERE BACKFLOW WILL
 BE LOCATED.
 3) FROM PREVIOUS REVIEW, SHT P1,6 SHOW
 LOCATION OF BACK FLOW PREVENTERS, UNABLE
 TO FIND LOCATION FOR WATER FEATURES AND
 COOLING TOWER.
 4) FROM PREVIOUS REVIEW SHT P-11 VERTI-
 CAL SANITARY RISERS #5,#13 SEC 911 WET
 VENTS, NO MORE THAN 4 FIXTURE UNITS ON A
 2" WET VENT. PLEASE RECHECK THESE RISERS
 5) SECONDARY ROOF DRAINS?????????

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-11-04 Cont ID  
Sent By pschmitz Date 2001-11-04 Time 07:29 Rev Time 0.00
Received By pschmitz Date 2001-11-04 Time 11:37 Sent To  
Notes
2001-11-04 00:00:00PLUMBING PLAN REVIEW,DENIED
 CODE REFERENCES,STD PLUMBING CODE-94.
 FAIR HOUSING ACT 24 CODE OF REGULATION,
 (CFR) 100.205 (C) (IV) DESIGN MANUAL.
 (1) SHT 8A.03 COMPLY WITH FHA CFR-24,AS
 LAID OUT IN THE DESIGN MANUAL, SPECIFY
 OPTION A OR B. REQUIRMENTS 1 THRU 7,SHOW
 MANEUVERING AND CLEAR FLOOR SPACE ALSO
 GRAB BAR REINFOFCEMENT/"DESIGN MANUAL".
 (2) SHT L3.02,04 DETAIL(11), WATER FEA-
 TURE, SHOW LOCATION OF REQUIRED BACK
 FLOW PREVENTER FOR WATER SUPPLY SEC 606
 (3) SHT IR6.02,03,04 IRRIGATION WATER
 SUPPLY,BACK FLOW PREVENTER LOCATION.
 (4) SHT P1,6 SHOW LOCATION OF BACK FLOW
 PREVENTERS,FOR FLUSHING RING, COOLING
 TOWERS, WATER FEATURES, SWIMMING POOL,
 AND FOUNTAIN WATER SUPPLY,SEC 606.
 (5A SHT P9 AIR CHAMBERS, COMPLY WITH
 SEC 607.8.3, ACCESSIBLE AND RECHARGEABLE
 (B) WATER HAMMER ARRESTORS SEC 607.8.2
 COMPLY WITH PDI-WH201,ASSE 1010, INSTALL
 PER MFG. FOR SIZE AND PLACEMENT.
 (6) SHT P9, NOTE(1) RP1-1 COMPLY WITH
 FL ENERGY CODE-97 SEC 412.1.ABCD.4 HOT
 WATER PIPING INSULATION TAB 4-11.
 (7) SHT P-10 RVD RISER DIAGRAM, COMPLY
 W/CITY OWPBMCW AMEND SPC-94,SEC507.6.1-2
 3/4"RVD DRAIN UP TO 150,000 BTU'S.
 PROVIDE CALCULATIONS FOR 3/4" RVD, SIZE.
 (8) SHT P-11 VERTIAL SANITARY RISERS,#1,
 #5,#13, SEC 911 WET VENTS, NO MORE THAN
 4 FIXTURE UNITS ON A 2" WET VENT.
 (9) SHT P-12 VERTICAL SANITARY RISERS,
 #18,#21, SEC 916 RELIEF VENTS- STACKS OF
 10 OR MORE BRANCH INTERVALS,REQUIRE
 RELIEF VENTS.
 (10) SHT P-13 DETAIL OF OIL INTERCEPTOR
 REFERENCE TO SFBC, CURRENT CODE SPC-94
 SEC 1004.5, NOTE #19.
 (14) SHT P-13,SEC 104.3 EXAMINATION OF
 DOUCMENTS, PROVIDE SHOP DRAWINGS OF ALL
 PLUMBING FIXTURES AND EQUIPMENT.
 (15)SHT P-10 SEC 504 MINIMUM CAPICITY OF
 WATER HEATERS, COMPLY WITH TAB 505.
 (16) SHT A2.12,A7.02,SEC 1109 SECONDARY
 (EMERGENCY) SCUPPER DRAINS,PROVIDE CALCU
 LATIONS,INCLUDE 1/2 THE VERTICAL WALLS,
 SHOW SIZE AND LOCATION.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659- 8096X8233

Review Stop Z ZONING
Rev No 6 Status N Date 2004-03-23 Cont ID  
Sent By mmclean Date 2004-03-23 Time 10:18 Rev Time 0.00
Received By mmclean Date 2004-03-23 Time 10:18 Sent To  
Notes
2004-03-23 00:00:00NO ZONING REQUIRED, PER ANA APONTE

Review Stop Z ZONING
Rev No 5 Status P Date 2004-02-25 Cont ID  
Sent By aaponte Date 2004-02-25 Time 16:36 Rev Time 0.50
Received By aaponte Date 2004-02-25 Time 16:36 Sent To  
Notes
2004-02-25 00:00:00PROVISO: WASHINGTONIA ROBUSTA PALMS
 SHOULD BE INSTALLED ON DATURA STREET
 TO MATCH EXISTING STREETSCAPE.

Review Stop Z ZONING
Rev No 4 Status P Date 2003-08-13 Cont ID  
Sent By lmartine Date 2003-08-13 Time 15:09 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2003-08-13 00:00:00REVISIONS APPROVED BY DANA LITTLE ON
 8/12/03

Review Stop Z ZONING
Rev No 3 Status P Date 2003-05-28 Cont ID  
Sent By sthyng Date 2003-05-28 Time 08:41 Rev Time 0.00
Received By sthyng Date 2003-05-28 Time 08:41 Sent To  
Notes
2003-05-28 00:00:00******PROVISO********
  
 PER ANTHEA GIANNIOTES
  
 OPENINGS FOR LOUVERS ON SHEET A4.01 AND
 A4.12 SHOULD BE SQUARE OR VERTICAL AND
 IN PROPORTION.

Review Stop Z ZONING
Rev No 2 Status P Date 2002-07-29 Cont ID  
Sent By dpalmer Date 2003-03-10 Time 12:53 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-07-30 00:00:00ARCHITECT WILL REVISIT GRILL SITUATION
 WITH URBAN DESIGN BEFORE THE C/O IS
 ISSUED AS PER J MINICOZZI
2002-07-29 00:00:00APPROVED BY JOE MINICOZZI WITH THE
 FOLLOWING CONDITIONS:
 1.THE LANDSCAPE ARCHITECT NEEDS TO SUB-
 MIT A PLAN FOR THE STREETSCAPES. IT THE
 UNDERSTANDING THAT IT WILL BE A
 SEPARATE APPLICATION.
 2.THE ZONING APPROVAL FOR THE VARIANCE
 FOR THE GARAGE STATED THAT THE SEALED
 WINDOWS AT THE GARAGE MUST BE DETAILED
 TO MINIMIZE THE EMPTY BUILDING EFFECT.
 DETAILING SHALL BE THAT OF A WINDOW
 EFFECT. IN AN AGREEMENT WITH THE ARCH-
 ITECT, THE WINDOWS WERE SUPPOSED TO BE
 PAINTED TO GIVE A DARK LOOK TO THE
 WINDOWS. IN THE LAST REVISION, VENTS
 WERE ADDED TO THE WINDOWS TO ALLOW FOR
 GARAGE AIR CIRCULATION. THIS IS FINE,
 BUT THE VENTS SHOULD BE DETAILED AS
 WINDOWS, NOT JUST VENTS. THE ARCHITECT
 WILL FAX A DRAWING OF THE VENTS
 CAMOUFLAGED WITH MESH SCREEN IN FRONT
 OF THE VENT SYSTEM TO BETTER OBSCURE THE
 LOUVERS OF THE VENTS.

Review Stop Z ZONING
Rev No 1 Status F Date 2001-11-19 Cont ID  
Sent By sgraham Date 2001-11-19 Time 12:49 Rev Time 0.50
Received By sgraham Date   Time   Sent To  
Notes
2001-11-19 00:00:001. STOREFRONT GLAZING SHALL BE CLEAR.
 ON THE WINDOW SCHEDULE IN NOTE #3 ON A8
 .04 IT DENOTES THE STOREFRONT GLAZING AS
 SOLARGREEN TINT. PLEASE VERIFY IT THIS
 IS CLEAR TO ALLOW VISIBILITY INTO THE
 STOREFRONT AND SUBMIT A SAMPLE OF THE
 GLAZING WITH TO THE CITY URBAN DESIGNER
 2.LANDSCAPE PLAN SHEET L2.02 NEEDS TO
 BE MODIFFIED TO MATCH THE SITE CONTEXT.
 A. NARCISSUS PAVEMENTS AND LANDSCAPING
 SHALLMATCH DESIGN OF NARCISSUS TO THE
 NORTHIN PAVER BLOCK DESIGN,
 WASHINGTONIA PLACEMENT, TREE GRATES,ETC.
 B. DATURA LAANDSCAPE PLAN SHALL MATCH
 DATURA WITH SIMILAAR PAVEMENTS, TREES &
 GRATING TO THAT IS CURRENTLY ON DATURA.