Plan Review Details - Permit 01101268
Plan Review Stops For Permit 01101268
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-12-11 Cont ID  
Sent By hpiskura Date 2001-12-11 Time 07:47 Rev Time 0.00
Received By hpiskura Date   Time   Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-11-13 Cont ID  
Sent By hpiskura Date 2001-11-13 Time 08:17 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-11-13 00:00:00THE $65000 DECLARED VALUATION APPEARS
 TOO LOW FOR THIS SCOPE OF WORK.PLEASE
 PROVIDE A DETAILED TAKEOFF INCLUDING
 EXTENSIONS TO JUSTIFY THE ESTIMATE.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-11-05 Cont ID  
Sent By dpalmer Date 2001-11-05 Time 20:02 Rev Time 0.00
Received By dpalmer Date 2001-11-05 Time 20:02 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-10-30 Cont ID  
Sent By mamini Date 2001-10-30 Time 09:32 Rev Time 1.00
Received By mamini Date 2001-10-30 Time 09:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-12-11 Cont ID  
Sent By hpiskura Date 2001-12-11 Time 07:50 Rev Time 0.00
Received By mcarsill Date 2001-12-11 Time 08:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-10-25 Cont ID  
Sent By mcarsill Date 2001-10-25 Time 15:36 Rev Time 0.00
Received By mcarsill Date 2001-10-25 Time 15:36 Sent To  
Notes
2001-10-25 00:00:001) NO INTERIOR FINISH INFORMATION
 PROVIDED ON PLANS. PLEASE PROVIDE
 INTERIOR FINISH CLASSIFICATION
 INFORMATION FOR WALLS AND CEILINGS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-11-07 Cont ID  
Sent By ndenmark Date 2001-11-07 Time 12:09 Rev Time 0.33
Received By ndenmark Date 2001-11-07 Time 12:09 Sent To  
Notes
2001-11-07 00:00:00PROVISO:
 FAN SHUT DOWN BY DUCT SMOKE DETECTOR TO
 BE TESTED FOR FINAL MECHANICAL. THIS
 TEST WAS NOT DONE AS PART OF THE PRIOR
 BUILDOUT APPROVAL.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-12-04 Cont ID  
Sent By kstevens Date 2001-12-04 Time 16:07 Rev Time 1.00
Received By kstevens Date 2001-12-04 Time 16:07 Sent To  
Notes
2001-12-04 00:00:00PASSED/PROVISO
  
 SEPARATE PERMITS REQUIRED FOR PLUMBING
 DEMO AND GAS DEMO.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-11-05 Cont ID  
Sent By kstevens Date 2001-11-05 Time 10:58 Rev Time 1.25
Received By kstevens Date 2001-11-05 Time 10:58 Sent To  
Notes
2001-11-05 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PAGE A-2 PRIVATE TOILET ROOM FOR THE
 OCCUPANT OF A PRIVATE OFFICE SHALL BE
 ADAPTABLE PER FACBC SEC 4.1.3(11).
 PLEASE SHOW DETAILS OF COMPLIANCE. SHOW
 HOW 20 PERCENT OVER CONTRACT IS SPENT
 FOR ADA PER SEC 4.6.1(2).
 2) PAGES A-1 & P-1. GREASE TRAP TO BE
 DRAINED, TOP REMOVED, HOLE CUT IN BOTTOM
 INSPECTED, THEN CLEAN FILL PUT IN BEFORE
 BURYING.
 3) SEPARATE DEMO PERMIT FOR DWV, WATER,
 GAS AND GREAS TRAP.
 4) PAGES A-2 & A-6. SINK IN BREAK ROOM
 SHALL COMPLY WITH FACBC SEC 4.24. PLEASE
 PROVIDE DETAILS.
 5) SPC TABLE 407 REQUIRES THAT A DRINK-
 ING FOUNTAIN BE INSTALLED. IF A SINGLE
 FOUNTAIN IS INSTALLED THEN PROVISIONS
 SHALL BE MADE FOR THOSE WHO HAVE DIFFIC-
 ULITY BENDING OR STOOPING PER FACBC SEC
 4.1.3(10). PLEASE SUBMIT DETAILS FOR
 DRINKING FOUNTAIN PER FABCB SEC 4.15
 ALSO.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-10-25 Cont ID  
Sent By sgraham Date 2001-10-25 Time 10:35 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***