Plan Review Details - Permit 01101096
Plan Review Stops For Permit 01101096
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-11-06 Cont ID  
Sent By jwitmer Date 2001-11-06 Time 06:57 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-10-31 Cont ID  
Sent By jwitmer Date 2001-10-31 Time 12:38 Rev Time 1.50
Received By jwitmer Date 2001-10-31 Time 12:38 Sent To  
Notes
2001-10-31 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01101096
 2000 PALM BEACH LAKES # 302
 CONT: LEIGHTON & MC GINN
 TEL: 662-6609
  
 SBC= 1997 STANDARD BUILDING CODE
  
 1)- FL ACC CODE 4.13.6 MANEUVERING CLEAR
 ENCES AT DOORS REQUIRES 18" ON THE PULL
 SIDE OF DOORS, 12" PUSH.
  
 2)- SBC 704.2.1.4 EXIT ACCESS CORRIDORS,
 FIRE RATED WALLS RREQUIRED TO HAVE PRO-
 TECTED OPENINGS SHALL BE EFFECTIVELY AND
 PERMANENTLY IDENTIFIED WWITH SIGNAGE OR
 STENCILING, SUGESTED WORDS" FIRE/ SMOKE
 BARRIER PROTECT ALL OPENINGS".
  
 3)- SBC TABLE 803.3 MINIMUM INTERIOR
 FINISH CLASSIFICATION SCHEDULE
  
 4)- SBC 1016.2-1016.3 MISSING EMERGENCY
 LIGHTING & EXIT INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096X8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-10-30 Cont ID  
Sent By dpalmer Date 2001-10-30 Time 20:18 Rev Time 0.00
Received By dpalmer Date 2001-10-30 Time 20:18 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-10-26 Cont ID  
Sent By mamini Date 2001-10-26 Time 10:49 Rev Time 1.00
Received By mamini Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-11-14 Cont ID  
Sent By mcarsill Date 2001-11-14 Time 09:48 Rev Time 0.00
Received By mcarsill Date 2001-11-14 Time 09:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-10-17 Cont ID  
Sent By mcarsill Date 2001-10-17 Time 09:59 Rev Time 0.00
Received By mcarsill Date 2001-10-17 Time 09:59 Sent To  
Notes
2001-10-17 00:00:001) PLANS FAILED TO INDICATE EXIT
 SIGNS AND EMERGENCY LIGHT FIXTURES.
 PLEASE INDICATE THESE REQUIRED ITEMS
 ON NEXT SUBMITTAL.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-10-29 Cont ID  
Sent By pkrauss Date 2001-10-29 Time 13:25 Rev Time 0.40
Received By pkrauss Date 2001-10-29 Time 13:11 Sent To  
Notes
2001-10-29 00:00:00 
  
 PROVISO ON PLAN -
  
 PRIOR TO CONNECTING TO ANY EXISTING
 DUCTWORK, CALL FOR AN INSPECTION.

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-11-13 Cont ID  
Sent By lsmith Date 2001-11-13 Time 14:37 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2001-11-13 Cont ID  
Sent By lsmith Date 2001-11-13 Time 14:37 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***