Plan Review Details - Permit 01100593
Plan Review Stops For Permit 01100593
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-11-21 Cont ID  
Sent By jwitmer Date 2001-11-21 Time 10:51 Rev Time 0.00
Received By jwitmer Date 2001-11-21 Time 10:53 Sent To  
Notes
2001-11-21 00:00:00BUILDING PROVISO:
 650 S ROSEMARY AV
 KIOSK
 SHELL PERMIT ONLY:
 ADMENISTRATIVE CODE 104.4.3:

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-11-21 Cont ID  
Sent By jwitmer Date 2001-11-21 Time 09:16 Rev Time 1.50
Received By jwitmer Date 2001-11-21 Time 09:16 Sent To  
Notes
2001-11-21 00:00:00BUILDING PROVISO:
 AMENDMENTS / 1997 STANDARD BUILDING CODE
 SHELL PERMIT: WHEN APPLICATION TO ERECT
 A BUILDING HAS BEEN FILED AND PENDING
 ISSUANCE OF SUCH PERMIT, THE BUILDING
 OFFICIAL MAY, AT HIS/ HER DISCRETION
 ISSUE A SPECIAL PERMIT FOR THE SHELL
 ONLY. THE HOLDER OF SUCH PERMIT IS PRO-
 CEEDING AT THEIR OWN RISK AND WITHOUT
 ASSURANCE THAT A PERMIT FOR THE REMAIN-
 DER OF THE WORK WILL BE GRANTED NOR THAT
 CORRECTIONS WILL NOT BE REQUIRED IN
 ORDER TO MEET PROVISIONS OF THE TECHNI-
 CAL CODES. NO ELECTRICAL, PLUMBING,
 MECHANICAL NOR ROOFING IS COVERED UNDER
 THE SHELL PERMIT!
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-11-02 Cont ID  
Sent By jwitmer Date 2001-11-02 Time 15:09 Rev Time 2.00
Received By jwitmer Date 2001-11-02 Time 15:09 Sent To  
Notes
2001-11-02 00:00:00BUILDING PLAN REVIEW
 PLAN REVIEW # 01100593
 700 S ROSEMARY AV
 KIOSK- RESTRAUNT
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- KIOSK PLANS ARE OF A CONCEPTUAL
 NATURE ONLY. THERE IS NO INTERIOR
 DETAIL INFORMATION, WILL THE PUBLIC SIT
 INSIDE?
 2) DISCREPANCIES: SHEET A-2 INDICATES A
 STRUCTURE WITH EXTERIOR GLAZING, VS A-3
 WHICH INDICATES A MORE OPEN AIR STRUC-
 TURE?
 INDICATE THE TYPE OF STRUCTURE, ENCLOSED
 PARTIALLY OR OPEN. USE SBC TABLE
 1606.2B TO FIND THE COEFICIENTS TO BE
 USED TO FIND WIND PRESURE ZONES. PROVIDE
 CALCS.
 3)- MISSING IS THE PRODUCT TESTING FOR
 WINDOWS, DOORS, ROOFING & STORM SHUTTERS
 PLANS DEPICT A TRIFOLD STORM SHUTTER,
 PROVIDE PRODUCT TESTING FOR THIS TYPE OF
 APPLICATION.
 4)- COLUMN DETAIL DOESN'T GIVE DETAIL AS
 TO FASTENING OF THE WOOD BEAMS?
 5)- PLANS ARE TO GO TO COUNTY FOR IMPACT
 FEES.
 6)- PLANS ARE INADEQUATE TO DO A
 THOROUGH PLAN REVIEW.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2001-12-06 Cont ID  
Sent By dpalmer Date 2001-12-06 Time 07:20 Rev Time 0.00
Received By dpalmer Date 2001-12-06 Time 07:19 Sent To  
Notes
2001-12-06 00:00:00****************** UNSAT **************
  
  
 1)NOTE: PLEASE NOTE THAT AS PER REQUEST
 BY CONTRACTOR AND CITY PLACE. ALL THE
 M,E,P`S REVIEW WERE PULLED FROM MAIN
 IN ORDER TO ISSUE BLDG PERMIT.
 CONTRACTOR AND CITY PLACE WERE TOLD
 AT THAT TIME, SEPARATE PLANS, PERMIT
 APPLICATIONS AND FEES WOULD NEED TO BE
 BROUGHT IN AT A LATER DATE.
  
 PLEASE SUBMIT SEPARATE ELECTRICAL PLANS
 AND PERMIT APPLICATIONS.
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRIAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2001-11-21 Cont ID  
Sent By jwitmer Date 2001-11-21 Time 10:33 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-11-21 00:00:00SHELL PERMIT ONLY SBC/AMENDMENT 104.4.3

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2001-11-02 Cont ID  
Sent By dpalmer Date 2001-11-02 Time 06:20 Rev Time 0.00
Received By dpalmer Date 2001-11-02 Time 06:20 Sent To  
Notes
2001-11-02 00:00:00********** NOTE **********
  
 1)NOTE: PLEASE NOTE THAT AS PER REQUEST
 OF CARLOS BERNAL AT CITY PLACE, THE
 ELECTRICAL REVIEW IS TO BE PULLED FROM
 MAIN #. THERE WILL BE NO ELECTRICAL
 WORK DONE AT THIS TIME. SEPARATE PERMITS
 AND PLANS WILL BE SUBMITTED AT A LATER
 DATE.
  
  
 IF THERE ARE ANY QUESTIONS,PLEASE CALL/
 SEE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-10-30 Cont ID  
Sent By dpalmer Date 2001-10-30 Time 20:44 Rev Time 0.00
Received By dpalmer Date 2001-10-30 Time 20:43 Sent To  
Notes
2001-10-30 00:00:00***************** UNSAT ************
  
 1)NOTE: PLEASE NOTE THAT THERE WAS NO
 ELECTRICAL DETAIL FOR REVIEW.
 PLEASE SUBMIT DETAIL FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-11-07 Cont ID  
Sent By lsmith Date 2001-11-07 Time 13:57 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-11-21 Cont ID  
Sent By mcarsill Date 2001-11-21 Time 09:11 Rev Time 0.00
Received By mcarsill Date 2001-11-21 Time 09:11 Sent To  
Notes
2001-11-21 00:00:00SHELL ARRANGEMENT ONLY!!!

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-10-16 Cont ID  
Sent By mcarsill Date 2001-10-16 Time 13:56 Rev Time 0.00
Received By mcarsill Date 2001-10-16 Time 13:56 Sent To  
Notes
2001-10-16 00:00:001) PLEASE PROVIDE MORE DETAILS FOR
 FUTURE FOOD SERVICE AREA. ANY COOKING
 THAT PRODUCES SMOKE OR GREASE LADEN
 VAPORS IS TO BE PROTECTED BY AN
 APPROVED HOOD,DUCT,AND EXTINGUISHING
 SYSTEM. SEPARATE PLANS AND PERMITS
 REQUIRED PRIOR TO ANY INSTALLATION.
 PLEASE SUBMIT A PROPOSED MENU. PLEASE
 PROVIDE A TYPICAL LAYOUT FOR COOKING
 EQUIPMENT.
 2) ANY AWNINGS PLANNED FOR USE ARE TO
 BE FIRE RETARDENT.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2001-11-21 Cont ID  
Sent By jwitmer Date 2001-11-21 Time 10:37 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-11-21 00:00:00MECH ADMIN. ADMEND 104.4.3

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-11-01 Cont ID  
Sent By pkrauss Date 2001-11-01 Time 16:36 Rev Time 0.40
Received By pkrauss Date 2001-11-01 Time 16:36 Sent To  
Notes
2001-11-01 00:00:00*******************DENIED***************
  
  
 INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.PLEASE PROVIDE THE FOLLOWING
 INFORMATION FOR REVIEW.
  
  
 1.SIZE, MATERIAL AND R-VALUE FOR
 DUCTWORK AND GRILLS.
  
 2.ACCESS TO AHUSHOW COMPLIANCE WITH
 1997 SMC 304.2.1.PLEASE NOTE ALL
 MECHANICAL EQUIPMENT INSTALLED
 INDOORS AT HEIGHT GREATER THAN 20'
 ABOVE THE APPLICABLE FINISHED FLOOR
 SHALL BE ACCESSIBLE AS PER '97 SMC
 304.2.4.
  
 3.PLEASE PROVIDE EQUIPMENT INFORMATION
 (MAKE, MODEL, BTU, SEER).
  
 4.INDICATE WHAT TYPE OF FOOD SERVICE
 WILL BE TAKING PLACE.
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION, AND WALK-IN COOLERS.
 PLEASE PROVIDE PLANS AND MANUFACTURER
 SUBMITTAL DATA WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-12-16 Cont ID  
Sent By pschmitz Date 2001-12-16 Time 08:06 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-12-16 00:00:00 
 PLUMBING PLAN REVIEW, DENIED
 (1) ATTACHED ARE PREVIOUS NOTES 10-30-01
 NOT ADDRESSED.
 (2) PROVIDE INFORMATION ON LOCATION MIN-
 IMUM FACILITIES FOR EMPLOYEES.
 (3) CONTACT WPB ENVIROMENTAL COMPLIANCE
 FOR GREASE TRAP WEAVER, W/ SAMPLE POINT.
 561-837-4074 RODNY COMPO.
 END OF COMMENTS PAUL SCHMITZ
 561-659-8096X8233

Review Stop P PLUMBING
Rev No 2 Status N Date 2001-11-21 Cont ID  
Sent By jwitmer Date 2001-11-21 Time 10:38 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-11-21 00:00:00SHELL PERMIT ADMIN AMEND 104.4.3

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-30 Cont ID  
Sent By kstevens Date 2001-10-30 Time 11:37 Rev Time 1.00
Received By kstevens Date 2001-10-30 Time 11:37 Sent To  
Notes
2001-10-30 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) MINIMUM FACILITIES ARE REQUIRED. SPC-
 94 TABLE 407. PLEASE INDICATE HOW THIS
 IS COMPLIED WITH.
 2) PLEASE INDICATE USAGE OF THIS KIOSK.
 IF FOOD IS PREPARED, PLANS TO BE ROUTED
 TO HOTEL BUSINESS REGULATION BEFORE PLAN
 REVIEW. IF PREPACKAGED FOOD PLEASE CON-
 TACT DEPT. OF AGRICULTURE AND CONSUMER
 SERVICES.
 3) PLEASE SUBMIT A SANITARY AND WATER
 RISER DIAGRAM.
 4) PAGE A2 FLOOR DRAINS NOT VENTED PRO-
 PERLY. PLEASE VENT SYSTEM PER SPC SEC
 921.4.
 5) BACKFLOW TO BE LOCATED BY UTILITY
 DEPT. PLEASE CONTACT (561) 659-8000 EXT
 2008 FOR LOCATION AND TYPE OF BACKFLOW.
 5) TWO WAY CLEAN OUT REQUIRED NEAR JUN-
 CTION OF BLDG DRAIN AND BLDG SEWER PER
 SPC SEC 710.2.2
 6) PLEASE SHOW WHERE ROOF LEADERS TERMIN
 ATE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-10-15 Cont ID  
Sent By sgraham Date 2001-10-15 Time 09:10 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***