Plan Review Stops For Permit 01100404 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2001-10-12 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-10-12 |
Time |
11:32 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-10-12 |
Time |
11:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-10-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-10-10 |
Time |
17:14 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-10-10 |
Time |
17:14 |
Sent To |
|
|
Notes |
2001-10-10 00:00:00 | **************** UNSAT **************** | | | | 1)NOTE: PLEASE CLARIFY GFI PROTECTION | | FOR SERVICE 230-95. | | | | 2)NOTE: PLEASE CLARIFY GROUNDING FOR | | TRANSFORMER. PER 250-30 | | | | 3)NOTE: PLEASE CLARIFY WHERE THE EXIST- | | -ING SERVICE IS IN SPACE? THIS WAS PART | | OF ALLOWING THE SECOND SERVICE BEING | | ADDED. IF NEW SERVICE FOR "TENANT" | | SPACE IS GOING TO BE STAND ALONE THEN | | 2HR FIREWALLS WILL BE REQ`D TO SEPARATE | | FROM SIDE TENANTS. 230-2 | | PLEASE ALSO SHOW WHAT CIRCUITS ARE BEING | | FED FROM EXISTING SERVICE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2001-10-16 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-10-16 |
Time |
09:48 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-10-16 |
Time |
09:48 |
Sent To |
|
|
Notes |
|
|
|