Plan Review Details - Permit 01100285
Plan Review Stops For Permit 01100285
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-10-25 Cont ID  
Sent By jwitmer Date 2001-10-25 Time 13:02 Rev Time 1.50
Received By jwitmer Date 2001-10-25 Time 13:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-11-07 Cont ID  
Sent By dpalmer Date 2001-11-07 Time 21:48 Rev Time 0.00
Received By dpalmer Date 2001-11-07 Time 21:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-10-24 Cont ID  
Sent By dpalmer Date 2001-10-24 Time 19:54 Rev Time 0.00
Received By dpalmer Date 2001-10-24 Time 19:54 Sent To  
Notes
2001-10-24 00:00:00******************* UNSAT ***********
  
 1)NOTE: PLEASE CLARIFY OCP FOR "EXISTING
 "DS-2 FEEDING NEW '2M'. PLEASE NOTE
 PLANS DO NOT SHOW SIZE.
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW ALL CONTINUOUS LOADS AT
 125%. PLEASE NOTE THAT LOADS ARE SHOWN
 AT CONNECTED/AMPS/DEMAND? NEED TO SHOW
 WATTS/SQ FT/OUTLETS LOADS. ?= 180VA.
 PLEASE NOTE THAT LOAD SHOWN FOR OUTELTS
 IS AT 13.1KW, PLEASE NOTE BY ROUGH
 COUNT IT APPEARS TO BE HIGHER?
 PLEASE CLARIFY BY SHOWING.
 LARGEST MOTOR AT 125% ALSO.
 215-5. 215-2,230-42,,,,,
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW, IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-10-17 Cont ID  
Sent By mcarsill Date 2001-10-17 Time 12:14 Rev Time 0.00
Received By mcarsill Date 2001-10-17 Time 12:14 Sent To  
Notes
2001-10-17 00:00:00IF OCCUPANT LOAD IS GREATER THAN 50
 PERSONS THEN THE DOUBLE DOORS FROM
 VESTIBULE 200 MUST SWING IN THE
 DIRECTION OF EXIT TRAVEL.
  
 APPROVED PROVISO:
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-11-21 Cont ID  
Sent By pkrauss Date 2001-11-21 Time 16:19 Rev Time 0.35
Received By pkrauss Date 2001-11-21 Time 16:17 Sent To  
Notes
2001-11-21 00:00:00REVISION ON PLAN SHEET M-4

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-10-18 Cont ID  
Sent By ndenmark Date 2001-10-18 Time 10:34 Rev Time 0.33
Received By ndenmark Date 2001-10-18 Time 10:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-12-15 Cont ID  
Sent By pschmitz Date 2001-12-15 Time 15:48 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-12-15 00:00:00A/C CONDENSATE DRY WELLS,

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-11-16 Cont ID  
Sent By kstevens Date 2001-11-16 Time 10:58 Rev Time 0.50
Received By kstevens Date 2001-11-16 Time 10:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-21 Cont ID  
Sent By pschmitz Date 2001-10-21 Time 14:51 Rev Time 25.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-10-21 00:00:00PLUMBING PLAN REVIEW,DENIED
 (1) SHT A1,MINIMUM FACILITIES, TAB 407
 REQUIRES 3 W/C'S AND 3 LAVS, IN RM 210
 WOMENS REST RM.
 (2)SHT A-1-5, BREAK SINK, RM 219, COMPLY
 WITH FACBC-97 SEC 4.24, HGTH 34" AFF.
 (3)SHT P1 SPECIFICATIONS, LIST MATERIALS
 FOR DWV AND WATER PIPING, SEC 104.2
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233