Plan Review Details - Permit 01100130
Plan Review Stops For Permit 01100130
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-02-05 Cont ID  
Sent By jwitmer Date 2002-02-05 Time 12:34 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2002-02-05 00:00:00BUILDING PROVISO:
 PERMIT 01100130
  
 1):PROVIDE (2) COPIES OF CURRENT SINGLE
 HUNG WINDOWS.DADE COUNTY OR SBCCI
 REPORT.
 2): PROVIDE PRODUCT TESTING REPORT FOR
 FRENCH DOORS, (2 COPIES).
 3): SUBMIT A KEY DRAWING FOR STORM SHUT-
 TER PLACEMENT AND ASSOCIATED FASTENING
 SCHEDULE.
 4) ADDITIONAL FEES: COUNTY IMPACT FEES &
 STATE RADON FEES.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-11-14 Cont ID  
Sent By jwitmer Date 2001-11-14 Time 13:50 Rev Time 4.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-11-14 00:00:00BUILDING PLAN REVIEW
 PERMIT# 01100130
 2320 TECUMSEH DR
 CONT: BILL FREE & ASSOC
 TEL: 624-0149
 CEL: 662-3652
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- SHEET A-7:TYPICAL WALL SECTION
 A) FOUNDATION NOTES 18"X18" CONC. MONO.
 FTG. A SECOND NOTE INDICATES 12"
 FROM FINISH FLOOR TO GRADE ALLOWING
 6" OF THE FOUNDATION TO BENEATH
 GRADE. SBC1804.1.3 A MINIMUM OF 12"
 OF THE FOUNDATION MUST BE BELOW
 GRADE.
 B) MISSING SBC 1814.3.3 MOISTURE BAR-
 RIER FOR MONOSLAB.
 C) TERMITE TREATMENT: SBC 1804.2/ 2304.
 1.2
  
 2)- MISSING INFORMATION, ON THE INTERIOR
 BEARING WALLS, MONOLITHIC FOOTERS, SUNK-
 ENED FLOOR AREAS. FOUNDATION SIZE, STEEL
 AND ANCHOR BOLTS.
  
 3)- MISSING INFORMATION ON CONCRETE
 COLUMNS ASWELL AS MASONRY REINFORCEMENT.
 COLUMN SIZE,STEEL HOOPS.
  
 4)- MISSING INFORMATION FOR TIE BEAM OR
 BOND BEAM CONSTRUCTION, SIZE,DEPTH,
 STIRRUPS STEEL?
  
 5)- MISSING TRUSS PLAN WITH THE MAGNI-
 TUDE OF LOADS TO BE RESISTED, TYPE OF
 HURRICANE STRAPS &TIES ANSD ALLOWABLE
 LOADS.
  
 6)- SHEET A-4, ADDITIONAL INFORMATION
 ON THE FRAMING & ATTACHMENT OF CHIMNEY,
 DETAIL OF 2 FLUES, PLANS INDICATE 1
 FLUE? 2 FIREPLACES?
  
 7)- ENERGY SHEETS DO NOT INDICATE THE
 USE OF A FIREPLACE?
  
 8)-FACTORY PREBUILT FIREPLACES/ CHIMNEYS
 SHALL COMPLY WITH UL 127, SUBMIT SPECIFI
 CATIONS.
  
 9)- SBC 2810 FRESH AIR INTAKES ARE RE-
 QUIRED ON THE FIREPLACE.
  
 10)- SBC 2809 GAS LOGS SHALL BE INSTALL-
 ED IN ACCORDANCE WITH REGULATIONS OF THE
 STANDARD GAS CODE.
  
 11)- SHEET A-4 FRONT ELEVATION, ADDTION-
 AL INFORMATION REQUIREDON THE CONSTRUCTI
 ON OF THE FRONT ENTRY.
  
 12)- A-7 METAL LATH SOFFIT: HIRIB ATTACH
 MENT ASPER 2504.2.2 SEE ASTM C 1063.
 7.10.2.3 HORIZONTAL FRAMING MEMBERS
 SHALL HAVE NAILS OR STAPLES TO PROVIDE
 AT LEAST 1 3/4" PENETRATION INTO HORIZON
 TAL FRAMING MEMBERS.
  
 13)- SHEET A-8 JAMB/ HEAD DOOR DETAIL,
 MISPRINT, 1/2" X 3" CONCRETE SCREWS.
  
 14)- INDICATE THE POSITIVE/ NEGATIVE
 PRESSURES ASSOCIATED WITH WINDOW & DOOR
 OPENINGS, INDICATE ON ELEVATIONS, END
 ZONES & INTERIOR ZONES.
  
 15)- SBC 1606.2.6.2COMPONENTS & CLADDING
 MISSING OR EXPIRED PRODUCT REPORTS (2)
 COPIES REQUIRED.
 A) WINDOWS- 4000 ALUM SERIES SINGLE
 HUNG - EXPIRED
 B) DOORS- FRENCH DOORS NO REPORT
 C) STORM SHUTTERS- MISSING, KEY PLAN
 INDICATING LOCATION OF SHUTTERS &
 FASTENING SCHEDULE, SAMPLE ATTACHED
  
 PLANS ARE OF A CONCEPTUAL DESIGN IN NA-
 TURE, A THOROUGH REVIEW CAN'T BE COM-
 PLETED AT THIS TIME.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096X8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-01-28 Cont ID  
Sent By btrobaug Date 2002-01-28 Time 11:33 Rev Time 1.00
Received By btrobaug Date 2002-01-25 Time 07:24 Sent To  
Notes
2002-01-28 00:00:00 
 ****************PROVISO*****************
 1) PLEASE PROVIDE AN A.I.C. RATING TO
 THE FIRST MEANS OF DISCONNECT FOR
 INSPECTORS APPROVAL BEFORE FINAL, PER
 110-9 & 110-10.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 (561) 659-8096 EXT.8392

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-10-24 Cont ID  
Sent By dpalmer Date 2001-10-24 Time 15:11 Rev Time 0.00
Received By btrobaug Date 2001-10-24 Time 15:11 Sent To  
Notes
2001-10-24 00:00:00****************** UNSAT ***************
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 MAIN DISCONNECTS AND PANELS.
  
 2) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 3)NOTE: PLEASE NOTE SMOKE DETECTOR INTO
 BEDROOM. NFPA-72 2-2.1.1.1
  
 4)NOTE: PLEASE NOTE OUTLET IN BATH TO
 BE AJACENT TO SINK. 210-52 D
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-01-30 Cont ID  
Sent By hmoser Date 2002-01-30 Time 18:09 Rev Time 0.50
Received By hmoser Date 2002-01-30 Time 18:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-10-09 Cont ID  
Sent By hmoser Date 2001-10-09 Time 17:56 Rev Time 0.75
Received By hmoser Date 2001-10-09 Time 17:55 Sent To  
Notes
2001-10-09 00:00:00NO MECHANICAL PERMIT NUMBER ON
 APPLICATION

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-01-30 Cont ID  
Sent By kstevens Date 2002-01-30 Time 17:38 Rev Time 0.33
Received By kstevens Date 2002-01-30 Time 17:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-10-22 Cont ID  
Sent By kstevens Date 2001-10-22 Time 18:37 Rev Time 0.33
Received By kstevens Date 2001-10-22 Time 18:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-10-09 Cont ID  
Sent By sgraham Date 2001-10-09 Time 14:48 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***