2001-11-14 00:00:00 | *************BUILDING UNSAT************* |
| |
| 1)A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) PROVIDE DOCUMENTATION THAT THERE IS |
| AN EGRESS EASEMENT THAT WILL PROVIDE AN |
| UNOBSTRUCTED PATH OF TRAVEL FROM THE |
| ACCESS DOOR THROUGH THE ADJOINING LOT TO |
| A PUBLIC AREA. PROVISIONS THAT WILL |
| PREVENT THE OWNER OF THE ADJACENT |
| PROPERTY FROM BLOCKING THE ACCESS DOOR |
| WITH FENCES, SHRUBBERY OR OTHER IS |
| REQUIRED. THE SITUATION OF THE ACCESS |
| DOOR PROVIDING DIRECT ACCESS TO A POOL |
| MUST BE ADDRESSED SHOULD THE OWNER OF |
| THE ADJACENT PROPERTY EVER WANT TO |
| INSTALL A PRIVATE POOL ON HIS PROPERTY |
| MUST ALSO BE ADDRESSED. |
| |
| 3) PROVIDE ACCESS TO ATTIC PER 97 SBC |
| SEC. 2309.6, IF THE CLEAR HEIGHT OF THE |
| ATTIC IS 24" OR MORE AT THE PEAK. |
| |
| 4) THE EXTERIOR WALL SECTION,C ON SHEET |
| A-3.0 INDICATES THE BOTTOM OF THE FOOTER |
| AT 12" BELOW FINAL GRADE. THE SOIL |
| REPORT REQUIRES THE FOUNDATION TO BEAR |
| 14" BELOW FINAL GRADE. PLEASE CORRECT. |
| |
| 5) THE MASONRY OPENING FOR THE GLASS |
| BLOCK AT THE KITCHEN IS INCORRECTLY |
| LISTED AS 85 SQ.FT. THE M.O. FOR THE |
| G.B. IN THE GREAT ROOM IS LISTED AS 42" |
| X 26", WHICH WOULD BE FOR THREE COURSES |
| OF FIVE BLOCKS, HOWEVER, THE PLANS |
| INDICATE THREE COURSES OF FOUR BLOCKS. |
| PLEASE CORRECT. |
| |
| 6) THE PRODUCT APPROVALS SUBMITTED FOR |
| STORM PANELS ARE INCOMPLETE. ONLY THE |
| APPROVED DRAWINGS WERE SUBMITTED WITH |
| THE KEY PLAN AND INSTALLATION SCHEDULE. |
| |
| 7) PROVIDE THE MANUFACTURER'S SPECS. FOR |
| THE 1 HOUR RATED GLASS BLOCK. |
| |
| |
| TRUSSES |
| UNSAT |
| |
| NOTE: SEMCO & HUGHES HAVE BEEN PURCHASED |
| BY USP. SOME OF THE CONNECTOR CAPACITIES |
| HAVE BEEN REDUCED AND OTHERS HAVE BEEN |
| CONTINUED. PLEASE REFER TO THE LATEST |
| USP CATALOG FOR TRUSS CONNECTOR |
| INFORMATION. |
| |
| 1) THE UPLIFT VALUES PROVIDED IN THE |
| TRUSS ANCHOR SCHEDULE DO NOT AGREE WITH |
| THE VALUES LISTED IN THE CATALOG. PLEASE |
| THE CRITERIA USED TO DETERMINE THE |
| UPLIFT VALUES FOR THE CONNECTORS WHEN |
| NUMBER OF FASTENERS DIFFERS FROM THOSE |
| SPECIFIED BY THE MANUFACTURER. |
| |
| 2) NO ANCHORS ARE SPECIFIED FOR JOINT 4 |
| OF TRUSSES T1. |
| |
| 3) THE TRUSS DESIGN CERTIFICATION COVER |
| SHEET DESIGNATES WINDLOADS IN COMPLIANCE |
| WITH ASCE 7-95 FOR 150 MPH. SOME OF THE |
| TRUSS DRAWINGS INDICATE 110 MPH WINDLOAD |
| AND OTHERS 150 MPH. THE STRUCTURE IS |
| DESIGNED TO ASCE 7-95 AND 145 MPH. PER |
| SHEET S1. PLEASE CORRECT. |
| |
| 4) THE TRUSS DRAWINGS INDICATE AN UPLIFT |
| OF 1637# AT JOINT 9 FOR TRUSS T2. THIS |
| EXCEEDS THE VALUE OF THE TA-15 CONNECTOR |
| SPECIFIED. THE UPLIFT AT JOINT 1 IS |
| 2924# WHICH EXCEEDS THE CAPACITY OF THE |
| TA-14 CONNECTOR SPECIFIED. |
| UPLIFT VALUES IN YOUR SCHEDULE EXCEED |
| THOSE LISTED IN CATALOG. |
| |
| 5) TRUSS GT3; UPLIFT AT JOINT 1 (2725#) |
| EXCEEDS THE TA-14 ANCHOR (1450#) AND AT |
| JOINT 9 ( 2271#) EXCEEDS THE TA-15 |
| (1450#). |
| |
| 6) TRUSS GT7; UPLIFT AT JOINT 24 (3699#) |
| AND JOINT 13 (3245#) ARE QUESTIONABLE |
| DUE TO THE CATALOG VALUES OF THE |
| SPECIFIED ANCHORS AND THE REDUCTIONS IN |
| CAPACITY DUE TO BEING LOCATED WITHIN |
| 8 INCHES OF EACH OTHER. THE SAME |
| COMMENTS ARE APPLICABLE TO TRUSS GT7A. |
| |
| 7) TRUSS GT11; UPLIFT AT JOINT 1 EXCEEDS |
| SPECIFIED ANCHOR. THERE IS NO REDUCTION |
| GIVEN FOR THE (3) ANCHORS LOCATED WITHIN |
| 8 INCHES OF EACH OTHER. SEE CATALOG. |
| |
| 8) THE TURRET FRAMING PLAN INDICATES A |
| TA-6 ANCHOR. THIS MARK IS NOT LISTED IN |
| YOUR TRUSS ANCHOR SCHEDULE. |
| |
| 9) PLEASE CLARIFY THE ANCHOR FOR TRUSS |
| TT1 AT TURRET. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |