Plan Review Details - Permit 01091471
Plan Review Stops For Permit 01091471
Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status P Date 2003-09-04 Cont ID  
Sent By shernand Date 2003-09-24 Time 09:22 Rev Time 0.30
Received By bstaples Date   Time   Sent To  
Notes
2003-09-04 00:00:00USE OF APPROVED FOAM ON EXTERIOR OF
 BUILDING APPROVED BY BUILDING OFFICIAL
 UNDER ALTERNATE MATERIALS, SECTION
 103.7 OF THE CITY OF WEST PALM BEACH
 AMENDMENBTS TO THE FLORIDA BUILDING
 CODE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status F Date 2003-08-20 Cont ID  
Sent By csiegber Date 2003-08-27 Time 14:55 Rev Time 0.00
Received By hpiskura Date 2003-08-20 Time 09:58 Sent To  
Notes
2003-08-20 00:00:00SHEET A29 REVISONS DATED 7/28/03
  
 THE USE OF COMBUSTIBLE ARCHITECTURAL IS
 PROHIBITTED BY SBC F102.2.7, SBC 1404.1.
 1 OF THE 1997 STANDARD BUILDING CODE
 WHICH THE BUILDING WAS PERMITTED UNDER.
  
 THE CURRENT 2001 FLORIDA BUILDING CODE
 IN EFFECT HAS SIMILAR LANGUAGE.
  
 PLEASE REVISE AS NECESSARY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status F Date 2003-07-31 Cont ID  
Sent By csiegber Date 2003-08-19 Time 15:37 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-07-31 00:00:00AMELUNG HANDRAIL INFORMATION
  
 ENGINEERING SUBMITTED FOR PUBLIC RECORD
 REQUIRES AN ORIGINAL SIGNATURE AND
 EMBOSSED SEAL.
  
 DELEGATED ENGINEERING IS REQUIRED TO BE
 REVIEWED BY THE DESIGNER OF RECORD FOR
 CONFORMANCE WITH DESIGN INTENT.
  
 CC: DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2003-07-22 Cont ID  
Sent By alange Date 2003-07-31 Time 09:25 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-07-22 00:00:00SHEET AO2, REVISION #5

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status F Date 2003-07-10 Cont ID  
Sent By hpiskura Date 2003-07-10 Time 09:51 Rev Time 0.00
Received By hpiskura Date 2003-07-10 Time 09:51 Sent To  
Notes
2003-07-10 00:00:00VARIOUS INFORMATION SUBMITTED 7/2/03
 NOTED AS REVISED STOREFRONT SUBMITTALS
 AND STOREFRONT SIDELIGHTS.
  
 AS NOTED IN MY COMMENTS DATED 5/20/03, A
 SEPARATE PERMIT IS REQUIRED FOR DOORS,
 WINDOWS, ETC. WHEN THAT SPECIFIC
 INFORMATION HAS NOT BEEN INCLUDED WITH
 THE ORIGINAL PERMIT APPLICATION AS IS
 THE APPARENT CASE HERE.
  
 APPLY FOR A PERMIT AND INCLUDE THREE
 SETS OF INFORMATION.PROVIDE AN
 INSTALLATION SCHEDULE SHOWING THE
 LOCATION AND SIZES OF THE ELEMENTS TO
 BE INSTALLED, INCLUDING THE ATTENDANT
 DESIGN PRESSURES FROM THE EOR.
  
 SELECT, NOTE, MARK OR SHOW WHICH
 COMPONENTS WILL BE USED IN THE
 RESPECTIVE NOA'S WHERE APPLICABLE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status F Date 2003-05-20 Cont ID  
Sent By shernand Date 2003-07-02 Time 12:23 Rev Time 0.00
Received By hpiskura Date 2003-05-20 Time 17:44 Sent To  
Notes
2003-05-20 00:00:00NOA 01-0228.09 SUBMITTED 5/15/03.
  
 IF NOA'S AND/OR TEST REPORTS ARE NOT
 INCLUDED WITH THE ORIGINAL PERMIT
 APPLICATION, A SEPARATE PERMIT AND FEES
 ARE REQUIRED.
  
 THE BUEROSSE, PE SHOP DWG 1 OF 2 SAYS
 "DOORS BY OTHERS".WHERE IS THAT
 INFORMATION?
  
 SECTION 6.1.2 OF THE 01-0228.09 NOA
 CALLS FOR THE COMPONENTS TO BE USED TO
 BE CLEARLY MARKED ON THOSE DRAWINGS.
  
 WHERE IS THE ATTACHMENT METHOD FOR THE
 STOREFRONT SYSTEM?
  
 CC: MIKE SIZEMORE

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status F Date 2003-05-12 Cont ID  
Sent By shernand Date 2003-05-19 Time 09:44 Rev Time 0.00
Received By hpiskura Date 2003-05-12 Time 15:36 Sent To  
Notes
2003-05-12 00:00:00THE COPIES OF THE ARCHITECTURAL PAGES
 ARE NOT SHOP DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2003-04-15 Cont ID  
Sent By shernand Date 2003-05-07 Time 13:24 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-04-15 00:00:00REVISION DATED 4/4/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2003-01-16 Cont ID  
Sent By sthyng Date 2003-03-11 Time 16:23 Rev Time 0.00
Received By hpiskura Date 2003-01-16 Time 08:53 Sent To  
Notes
2003-01-16 00:00:00REVISION 4 A-02, REV 2 A-30, REV 2 A31

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status C Date 2002-12-11 Cont ID  
Sent By dpalmer Date 2003-01-06 Time 16:51 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-12-11 00:00:00RE: ROOF TILE NOA 99-1012.01.
  
 THE NOA HAS HIGH LIGHTED ON IT TABEL 4A
 FOR A SINGLE PATTY ADHESIVE SYSTEM.
  
 SECTION 3 LIMITATIONS, REQUIRES A
 STATIC FIELD UPLIFT TEST IN ACCORDANCE
 WITH MIAMI DADE RAS 106.THE RESULTS
 OF THIS TESTING MUST BE PROVIDED TO THE
 CITY.
  
 DOCUMENTATION OF THE QUARTERLY TESTING
 AS SET OUT IN THE REPORT MUST ALSO BE
 PROVIDED TO THE CITY.
  
 PRIOR TO ANY INSTALLATION, AN ANALYSIS
 IN ACCORDANCE WITH MIAMI-DADE RAS 127
 FOR A MOMENT BASED SYSTEM USING THE
 PRESSURE FOR THE CORNER ZONE MUST BE
 BE PROVIDED BY G.V. PIREZ, PE.THE
 SHEET DATED 9/15/01 HAS PRESSURES OF
 -112 FOR ZONE 1 AND -182 FOR ZONE 2.
 THE CORNERS OR ZONE THREE ARE ABSENT
 FROM THAT SHEET AND THE MR APPEARS
 MARGINAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2002-11-13 Cont ID  
Sent By hpiskura Date 2002-11-13 Time 12:19 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-11-13 00:00:00THE "OPERABLE WINDOW" SUBMITTAL DATED
 11/12/02 FOR WINDOWS HAVING SITE
 SPECIFIC ENGINEERING PREPARED BY AL
 FAROOQ CORP. ARE REQUIRED TO HAVE A
 SEPARATE PERMIT AND TO BE DESIGNED IN
 ACCORDANCE WITH THE 2001 FBC.
  
 SEE THE ATTACHED IMPLEMENTATION
 STANDARD FOR HURRICANE MISSILE IMPACT
 PROTECTION
  
 THIS WAS NOTED ON PREVIOUS SUBMITTALS
 FOR WINDOWS AND ROOF COVERINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2002-10-29 Cont ID  
Sent By btrobaug Date 2002-11-12 Time 17:58 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-10-29 00:00:00THE KRAFT FACED INSULATION CALLED OUT
 IN THE CERTAINTEED FIBERGLASS INSUALTION
 INFORMATION SUBMITTED 10/28/02 DOES NOT
 COMPLY WITH SBC 708.2.1 FOR THE FLAME
 SPREAD RATING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2002-10-11 Cont ID  
Sent By dpalmer Date 2002-10-29 Time 07:03 Rev Time 0.00
Received By hpiskura Date 2002-10-11 Time 09:42 Sent To  
Notes
2002-10-11 00:00:00RE: SHOP DWGS AND NOA'S SUBMITTED
 10/3/02
  
 PRODUCT APPROVAL INFORMATION FOR THE
 ROOF TILE WAS NOT INCLUDED AND/OR
 REVIEWED WITH THE BUILDING PERMIT SO A
 SEPARATE PERMIT AND INFORMATION IS
 REQUIRED.NOTE TOO, THAT THE MONIER
 SYSTEM CHOSEN IS FOR A WOOD DECK
 APPLICATION.THESTRUCTURAL PLANS DO
 NOT HAVE WOOD DECKS. (TYPE I
 CONSTRUCTION)
  
 INCLUDED HERE IS A COPY OF THE PROVISO
 THAT WAS INCLUDED AT TIME OF PERMIT
 ISSUE
 THE ENGINEER'S PRESSURE ZONES FOR THE
 ROOF HAVE NOT BEEN PROVIDED YET.
  
 WHERE WILL THE AEICOR METAL ROOFING BE
 USED?

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2002-09-16 Cont ID  
Sent By hpiskura Date 2002-09-16 Time 10:51 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-09-16 00:00:00RE: DOOR TYPE 8 NOA, DATED 9/11/02
  
 THE REVISED WIND LOAD PAGE A-02 AND THE
 WIND LOAD FAX FROM G.V. PIREZ ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 RESPECTIVE DESIGN PROFESSIONALS WHEN
 SUBMITTED FOR PUBLIC RECORD.SEE FBC
 104.2.2.
  
  
  
 ALSO, PAY THE REVISION FEES AS PROVIDED
 FOR IN THE CITY'S PERMIT FEE SCHEDULE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2002-08-26 Cont ID  
Sent By hpiskura Date 2002-08-26 Time 13:25 Rev Time 0.00
Received By hpiskura Date 2002-08-26 Time 13:26 Sent To  
Notes
2002-08-26 00:00:00REV #3 A26

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status C Date 2002-07-11 Cont ID  
Sent By hpiskura Date 2002-07-11 Time 15:06 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-07-11 00:00:00THE SEVERAL AND VARIOUS METRO DADE
 NOTICE OF ACCEPTANCES FOR THE DOORS AND
 WINDOWS SUBMITTED AS SHOPDRAWINGS ON
 6/25/02 ARE REQUIRED TO HAVE A SEPARATE
 PERMIT APPLICATION, SINCE THEY WERE NOT
 INCLUDED WITH THE ORIGIANL PERMIT PLANS.
  
  
 PLEASE INCLUDE A SKETCH INDICATING THE
 LOCATION OF THE WINDOW OR DOOR TO BE
 INSTALLED.SHOW THE DESIGN PRESSURES
 FOR THE OPENINGS ON THE SKETCH.ENSURE
 THAT THE PRESSURES ON THE NOA'S AGREE
 WITH THE BUILDING DESIGN AND IN CASES
 WHERE THERE IS MORE THAN ONE METHOD OR
 UNIT ON THENOA THAT THE INTENDED METHOD
 OR UNIT IS CLEARLY SELECTED AND MARKED
 ON THE NOA.
  
 SOME OF THE NOA'S INDICATED THE
 REQUIREMENT FOR "HURRICANE PROTECTION"
 IE SHUTTERS.THE BUILDING OFFICIAL'S
 INTERPRETATION OF THE CODE IS THAT
 SHUTTERS ARE NOT TO BE SUBSTITUTED FOR
 IMPACT RESISTANT GLAZING IN LARGE
 BUILDINGS AND/OR LARGE NUMBERS OF
 OPENINGS.SEE THE ATTACHED
 IMPLEMENTATION STANDARD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-04-10 Cont ID  
Sent By hpiskura Date 2002-04-10 Time 11:32 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-04-10 00:00:00PROVISO:
  
 THE REVISED SUSPENDED CEILING DETAIL ON
 SHEET A-11.1 LACKS SPECIFIC CONSTRUCTION
 INFORMATION.PROVIDE A SKETCH
 DETAILING SPACING OF FRAMING CHANNELS,
 TYPE AND NUMBER OF FASTENERS AND THE
 GAUGE OF THE FRAMING MEMBERS.
 STATEMENTS SUCH AS "ANCHOR TO STRUCTURE
 ABOVE" ARE NOT ADEQUATE.PLEASE SUBMIT
 THIS INFORMATION BEFORE CONSTRUCTION.
  
 THE USE OF HURRICANE PANELS IS SUBJECT
 TO THE BUILDING OFFICIAL'S
 INTERPRETATION PAPER.SEE ATTACHED.
  
 THE DRAWINGS NOTED IN THE METRO DADE
 REPORTS NUMBERED 00-0628.11, 01-0629.08
 AND99-0218.01 ARE MISSING.ALSO,
 PROVIDE ABLDG SKETCH OR TABLE DEPICTING
 THE PRESSURES FOR THE COMPONENTS AND
 CLADDING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-02-25 Cont ID  
Sent By hpiskura Date 2002-02-25 Time 11:04 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-02-25 00:00:00THE UL 505 CONSTRUCTION DECLARED ON
 SHEET A.28 SECTION 5 DOES NOT APPEAR TO
 BE PRACTICAL FOR SHAFT CONSTRUCTION IN
 THE CONFIGURATION DEPICTED ON THE
 PLANS.HOW WILL THE JOINTS BE TAPED ON
 THE INTERIOR OF THE SHAFTS AND THE
 ANGLES ATTACHED?
  
 DETAILS 4/A.27 AND S2.3, WHAT IS THE
 MATERIAL SHOWN AS "SM WRC 2X6"?
  
 PROVIDE SPECIFIC CONSTRUCTION DETAILS
 INCLUDING CONNECTIONS FOR THE SUSPENDED
 STUD CEILING SYSTEM SHOWN IN SECTION 3,
 SHEET A.09.
  
 SHEET A35, NOTE 1.04 B, CALLS OUT ASCE
 7-93, THE DESIGN PRESSURES IN NOTE
 2.02ADO NOT AGREE WITH THOSE ON SHEETS
 A12 - A14, ROOFING NOTES 1D ARE
 ASCE7-93.SHEET M8 DECLARES THE SOUTH
 FLORIDA BUILDING CODE AND THE
 SPECIFICATIONS STILL REFERENCE A 110
 MPH WIND DESIGN.PLEASE REVISE AS
 NECESSARY AND ENSURE COMPLIANCE WITH
 ASCE 7-95 IN ACCORDANCE WITH SBC 1606.1.
 1
  
 THE INFORMATION PROVIDED ON 2/6/02 DOES
 NOT QUALIFY THE "DYPLAST" MATERIAL AS
 NON-COMBUSTIBLE AS PROVIDED FOR IN SBC
 202. THE "ACROCRETE" PRODUCTS MAY ONLY
 BE USED IN ACCORDANCE WITH ITS LISTING
 AND LIMITATIONS CONTAINED IN THAT
 REPORT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-11-07 Cont ID  
Sent By hpiskura Date 2001-11-07 Time 16:32 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-11-08 00:00:00PLEASE PROVIDE A RECENT PROPERTY SURVEY.
  
 THE SOIL REPORT IS REQUIRED TO HAVE THE
 EMBOSSED SEAL OF THE ENGINEER TOGETHER
 WITH THE ORIGINAL SIGNATURE AND DATE.
 THIS IS REQUIRED FOR ALL DOCUMENTS
 PREPARED BY AN ENGINEER OR ARCHITECT
 AND SUBMITTED FOR PUBLIC RECORD.SEE
 FS 471 AND 481
  
 PLEASE PROVIDE THE FIRE DESIGN NUMBERS
 FOR THE MASONRY WALLS SERVING AS SHAFT
 ENCLOSURES AND EXTERIOR WALLS.SEE SBC
 701.5.
  
 WHAT IS THE MEANING OF THE NOTE ON
 SHEETA0-1 "ADJACENT BUILDING WALL
 CONSTRUCTED AS FIRE WALL AS DEFINED BY
 CODE." ?
  
 THE DOORS TO THE CLUBHOUSE AND FITNESS
 ROOMS SHOWN AS #26 ARE REQUIRED TO BE
 FIRE RATED.SEE SBC 705.1.2 AND
 704.1.1.
  
  
 SBC 1008 REQUIRES ONE OF THE EXIT STAIRS
 TO BE CONTINUOUS TO THE ROOF.
  
 SBC 3104.3 REQUIRES "PROTECTION AT THE
 INTERFACE" WHERE THE COVERED WALKWAY
 JOINS THE BUILDING.
  
 NEITHER THE PLANS NOR THE SPECIFICATIONS
 INDICATE THE USE OF FIRE RETARDANT
 TREATED, (FRT) BLOCKING AS PROVIDED FOR
 IN SBC 609 AND SBC 707.1.
  
 SBC 104.2.1 DOES NOT ALLOW CITING THE
 CODE IN LIEU OF SPECIFIC DESIGN
 INFORMATION SUCH AS THAT FOUND ON SHEET
 A-29 "ADHERE DYPLAST W/ STANDARD
 BUILDING CODE 1403.6.8 ..."WHICH IS
 NOT A VALID CODE SECTION ANYWAY, PLEASE
 REVISE AS NECESSARY.
  
 DETAIL 1/A12 ON SHEET A29. SHOW A
 SPECIFIC CONNECTION DETAIL FOR THE
 STONE CORBEL OR IF DESIGN IS
 DESIGNATED, THE LOCATION, NATURE,
 DIRECTION AND MAGNITUDE OF THE FORCES
 TO BE RESISTED.
  
 MOST OF THE PAGES IN THE STRUCTURAL
 CALCULATIONS DO NOT PERTAIN TO THIS
 BUILDING.PLEASE PROVIDE COMPLETE
 CALCULATIONS DEMONSTRATING COMPLIANCE
 WITH SBC 1601 AND NOT JUST A WIND
 RESISTANCE INVESTIGATION.
  
 SHEET S-1.1 NOTE #8, WHAT IS THE TOP OF
 FOOTING ELEVATIONS?
  
 SEE SBC 1608.2.2 FOR THE GUARDRAIL
 DESIGN LOADS SHOWN ON SHEET A27 IN
 DETAIL 5/A25.
  
 SHEET S 1-1 DEPICTS COLUMNS NUMBERED 1
 THROUGH 48 AND THE COLUMN SCHEDULE ON
 SHEET S 4-1 LISTS ONLY 42.THERE IS NO
 DETAIL FOR COLUMN #46.
  
 A THRESHOLD INSPECTION PLAN IS REQUIRED
 FOR THIS BUILDING AS PROVIDED FOR IN FS
 553.71.
  
 SEVERAL AREAS OF THE SPECIFICATIONS
 ERRONEOUSLY CITE A 110 MPH WIND SPEED.
 PLEASE REVISE AS NECESSARY AND INCLUDE
 A SKETCH OF THE BUILDING DEFINING THE
 PRESSURE ZONES AND THEIR ATTENDANT
 PRESSURES.
  
 SMOKE DETECTORS ARE NOT SHOWN INSIDE OF
 THE SLEEPING ROOMS AS PROVIDE FOR IN
 NFPA 72 WHICH IS INVOKED BY SBC 905.2.
  
 THE STAIR SECTIONS SHOWN WITH RISER
 HEIGHTS OF 6.5" OR LESS WHEN TAKEN
 TOGETHER WITH THE DECLARED 11" TREAD DO
 NOT MEET THE 24"- 25" OF SBC 1007.3.1.
 SEE ALSO NFPA 101 FOR THE 7/11
 REQUIREMENT.
  
 PLEASE PROVIDE CALCULATIONS AND A
 WRITTEN NARRATIVE TO BETTER DESCRIBE
 THE SEQUENCE OF OPERATIONS FOR SMOKE
 CONTROL DECLARED ON SHEET M-8.
 DEMONSTRATE THAT THE BAROMETRIC RELIEF
 DAMPER WILL PROVIDE FOR AT LEAST 2500
 CFM FLOWINGAND ANTICPATED STACK
 PRESSURES IN THE BUILDING.SEE SBC
 412.11 (5).
  
 DESCRIBE HOW SMOKE REMOVAL FROM THE
 CORRIDORS WILL BE ACCOMPLISHED AT A
 RATE OF AT LEAST 6 AIR CHANGES PER
 HOUR. SEE SBC 412.5 (3) IF THIS IS THE
 INTENDED METHOD.
  
 SHEET E3-5 DOES NOT SHOW THE FIRE
 DEPARTMENT COMMUNICATION SYSTEM
 REQUIRED BY SBC 412.3.3.ARE THE MARKS
 SHOWN ON THE PLANS AS [T] THE INTENDED
 LOCATIONS?
  
 E 3-5, OR THE SPECIFICATIONS, DO NOT
 SHOW THE BACKUP POWER SUPPLY FOR THE
 ALARM SYSTEM. ELEVATOR RECALL BY
 ELEVATOR LOBBY SMOKE DETECTOR IS NOT
 NOTED IN THE SEQUENCE OF OPERATION. SEE
 SBC 412.6.3.
  
 THERE IS NO SPECIFICATION FOR THE
 GENERATOR FUEL SUPPLY.SEE SBC
 412.7.1.2.ALSO THE E SHEETS DO NOT
 CLEARLY INDICATE THE MANDATORY STAND BY
 POWER LOADS TO BE CARRIED BY THE
 GENERATOR.SEE SBC 412.7.2.
  
 SEVERAL OF THE DOORS WITHIN THE UNITS DO
 NOT MEET THE NOMINAL 32" WIDTH REQUIRED
 BY THE FAIR HOUSING ACT. TOILET AND
 POWDER ROOMS, BEDROOMS, WALKIN CLOSETS,
 PATIOS, AND SIMILAR LIVING AREAS AS
 CITED IN THAT LAW.PLEASE REVISE AS
 NECESSARY.
  
 THE METRO DADE NOTICE OF ACCEPTANCE
 REPORT #990212.09 IS ILLEGIBLE.
  
 NOA #97-1204.02 IS EXPIRED.
  
 00-0721.05 FOR THE SHUTTERS DOES NOT
 HAVE THE COMPONENTS SELECTED OR THE
 LOCATION OF THEIR PROPOSED APPLICATION
 ON THE BUILDING.SHUTTERS ON
 MULTI-STORY BUILDINGS IN LIEU OF IMPACT
 RESISTANT GLAZING, ARE SUBJECT TO
 APPROVAL BY THE BUILDING OFFICIAL ON A
 CASE BY CASE BASIS.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO THE
 COUNTY FOR THE CITY, THE PERMIT PLANS
 STAMPED BY THAT OFFICE,AND A COPY OF
 THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 CONTACT DON NEELY REGARDING THE ONSITE
 THRESHOLD INSPECTOR FOR SPECIFIC CITY
 REQUIREMENTS.561-659-8096 X 8333.

Review Stop E ELECTRICAL
Rev No 22 Status P Date 2003-10-14 Cont ID  
Sent By dpalmer Date 2003-10-14 Time 11:30 Rev Time 0.50
Received By dpalmer Date 2003-10-14 Time 11:30 Sent To P
Notes
2003-10-14 00:00:00TWO ROLLS PF PLANS NEEDED TO BE STAMPED
 BY ALL TRADES EXCEPT MECH.
 RTEMOVED 3.3 DUE TO REV BEING CORRECTED
 UNDER SEPARATE REV SUBMITTAL.

Review Stop E ELECTRICAL
Rev No 21 Status P Date 2003-10-06 Cont ID  
Sent By dpalmer Date 2003-10-06 Time 16:09 Rev Time 0.33
Received By dpalmer Date 2003-10-06 Time 16:09 Sent To  
Notes
2003-10-06 00:00:00MAIN SERVICE LOAD ADJUSTDMENT

Review Stop E ELECTRICAL
Rev No 20 Status F Date 2003-09-19 Cont ID  
Sent By dpalmer Date 2003-09-19 Time 09:19 Rev Time 0.50
Received By dpalmer Date 2003-09-19 Time 09:19 Sent To  
Notes
2003-09-19 00:00:00********** UNSAT **********************
  
 1)NOTE: PLEASE SEE SHEET E-3-3, SHOWS
 37900AMPS ON 4000A BUS DUCT AND SAME FOR
 4000A SW BRD.
  
 PLEASE SUBMIT THE ABVOE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 19 Status P Date 2003-08-27 Cont ID  
Sent By dpalmer Date 2003-08-27 Time 10:51 Rev Time 0.50
Received By dpalmer Date 2003-08-27 Time 10:51 Sent To  
Notes
2003-08-27 00:00:00REV FOR UNITS/ UNIT LOAD CALCULATIONS.

Review Stop E ELECTRICAL
Rev No 18 Status F Date 2003-08-22 Cont ID  
Sent By csiegber Date 2003-08-22 Time 16:01 Rev Time 1.00
Received By dpalmer Date 2003-08-22 Time 06:30 Sent To  
Notes
2003-08-22 00:00:00*********** UNSAT *****************
  
 PLEASE PROVIDE A CURRENT 2-1,3-2,3-3
 PLEASE PROVIDE LATEST LOAD STUDY EVEN
 IF LOADS HAVE DECREASED FOR RECORD.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 DPALMER @WPB.ORG

Review Stop E ELECTRICAL
Rev No 17 Status P Date 2003-08-22 Cont ID  
Sent By dpalmer Date 2003-08-22 Time 06:21 Rev Time 3.00
Received By dpalmer Date 2003-08-22 Time 06:03 Sent To  
Notes
2003-08-22 00:00:00*************** NOTE **************
  
 REV OK FOR 3-1 AND 3-4 ONLY
 WAITING FOR NEW 3-3,2-1 SEE OTHER
 COMMENTS.

Review Stop E ELECTRICAL
Rev No 16 Status P Date 2003-08-15 Cont ID  
Sent By csiegber Date 2003-08-19 Time 15:39 Rev Time 0.50
Received By btrobaug Date 2003-08-15 Time 15:43 Sent To  
Notes
2003-08-15 00:00:00REVISED PANEL SCHEDULES,UNITS A,A1,B.B1
 & C./WRT.

Review Stop E ELECTRICAL
Rev No 15 Status F Date 2003-08-07 Cont ID  
Sent By dbaxter Date 2003-08-12 Time 14:01 Rev Time 0.33
Received By dpalmer Date 2003-08-07 Time 13:20 Sent To  
Notes
2003-08-07 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE SEE THAT RISER DIAGRAM
 DOES NOT HAVE TITLE BLOCK FOR ENGINEER
 OF RECORD AND IS NOT SIGNED DATED AND
 SEALED BY ENGINEER OF RECORD.?
 PLEASE HAVE ALL REVISED DRAWINGS DONE
 BY ENGINEER. FS/ FAC 471.025, 61G15-23.
 002.
 REVIEW WILL BE DONE AT THAT TIME.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 14 Status P Date 2003-08-05 Cont ID  
Sent By alange Date 2003-08-05 Time 15:01 Rev Time 0.33
Received By dpalmer Date 2003-08-05 Time 13:35 Sent To  
Notes
2003-08-05 00:00:00POOL REVISION/ PLAN ONLY.

Review Stop E ELECTRICAL
Rev No 13 Status F Date 2003-07-16 Cont ID  
Sent By alange Date 2003-08-04 Time 15:50 Rev Time 2.00
Received By dpalmer Date 2003-07-16 Time 12:48 Sent To  
Notes
2003-07-16 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANELS.
 THERE ARE NUMEROUS LOCATIONS THAT
 FEEDERS SIZES DO NOT SEEM TO CORRELATE
 AND SOME DO NOT MEET 310-16 FOR SIZING
 AND OCP UNDER 240.
  
 PLEASE PROVIDE A CURRENT AND UP TO DATE
 COMPLETE RISER DIAGRAM AND ALL PANEL
 SCHEDULES.
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 12 Status P Date 2003-04-28 Cont ID  
Sent By dpalmer Date 2003-04-28 Time 14:01 Rev Time 1.25
Received By dpalmer Date 2003-04-28 Time 14:01 Sent To FIRE
Notes
2003-04-28 00:00:00REV OK, 1-1,1-2,3-1,3-4

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2003-01-07 Cont ID  
Sent By shernand Date 2003-04-21 Time 16:42 Rev Time 0.25
Received By dpalmer Date 2003-01-07 Time 07:03 Sent To  
Notes
2003-01-07 00:00:00REV FOR TELEPHONE CONDUITS.

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2002-11-13 Cont ID  
Sent By dpalmer Date 2002-11-13 Time 12:41 Rev Time 0.50
Received By dpalmer Date 2002-11-13 Time 12:41 Sent To P
Notes
2002-11-13 00:00:00********** UNSAT *********
  
 1)NOTE: PLEASECLARIFY "CHANGE" IN
 SWITCH GEAR. IF CHANGED FROM PLANS,
 PLEASE REVISE RISER DIAGRAM AND SUBMIT
 WITH PLANS. PLEASE NOTE, ATLEAST ONE
 COPY OF SUBMITTALS NEEDS TO BE ORIG
 SIGNATURE AND SEAL BY ENGINEER OF RECORD
 471 FS
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2002-10-09 Cont ID  
Sent By btrobaug Date 2002-10-28 Time 14:18 Rev Time 1.25
Received By btrobaug Date 2002-10-09 Time 14:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2002-10-03 Cont ID  
Sent By dpalmer Date 2002-10-03 Time 16:10 Rev Time 3.00
Received By dpalmer Date 2002-10-03 Time 16:10 Sent To  
Notes
2002-10-03 00:00:00********* NOTE **************
  
 PLEASE NOTE THIS STOP IS FOR ELECTRICAL
 SPEC BOOKS ONLY.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2002-09-20 Cont ID  
Sent By dpalmer Date 2002-09-20 Time 05:56 Rev Time 0.50
Received By dpalmer Date 2002-09-20 Time 05:56 Sent To  
Notes
2002-09-20 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE PLANS NEED TO HAVE
 CORRECTED DATES W/ REVISIONS SHOWN
 WITH CLOUDS/TRIANLGES.
 PLEASE NOTE PAGES THAT ARE SUBMITTED
 WITH THE SAME DATES FROM DEC OF 2001?
 PLEASE NOTE SOME PAGES SHOWN WITH A
 REV #2 AND PLANS ONLY SHOW REV #1?
  
 PLEASE CORRELATE PLANS, LABEL, DATE, ETC
 SUBMIT THE ABOVE INFORMATION FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2002-07-25 Cont ID  
Sent By dpalmer Date 2002-07-25 Time 10:34 Rev Time 0.00
Received By dpalmer Date 2002-07-25 Time 10:34 Sent To  
Notes
2002-07-25 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT ALL SHEETS FOR
 SPECS ON LIGHTING NEED TO SHOW SOME
 KING OF RECOGNIZED TESTING,UL,ETL,MET,,
 ETC.
  
 PLEASE SUBMIT FOR REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2002-07-25 Cont ID  
Sent By dpalmer Date 2002-07-25 Time 10:33 Rev Time 0.00
Received By dpalmer Date 2002-07-25 Time 10:33 Sent To FIRE
Notes
2002-07-25 00:00:00******** NOTE ****
  
 SPEC BOOKS FOR MATERIALS ONLY. GENERATOR
 SPECS ALSO.
 SENT TO FIRE FOR GEN AND TANK REVIEW.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2002-07-25 Cont ID  
Sent By dpalmer Date 2002-07-25 Time 06:50 Rev Time 0.00
Received By dpalmer Date 2002-07-25 Time 06:50 Sent To  
Notes
2002-07-25 00:00:00************* UNSAT ******************
 ***** GENERATORS SPEC NAD CALCULATIONS**
  
 1)NOTE: PLEASE NOTE THAT GENERATOR SPECS
 AND CALCS THAT ARE SUBMITTED FOR RECORD
 MUST BE SIGNED,DATED AND SEALED BY THE
 ENGINEER OF RECORD. 471.025
 MUST BE ORIGINAL.
  
 2)NOTE: PLEASE NOTE THAT SHEETS DO NOT
 CORRELATE? ONE SHOWS CALCS AT 120/208
 AND GENERATOR AT 277/480V??
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-03-28 Cont ID  
Sent By dpalmer Date 2002-03-28 Time 09:06 Rev Time 0.00
Received By dpalmer Date 2002-03-28 Time 09:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-03-07 Cont ID  
Sent By dpalmer Date 2002-03-07 Time 07:02 Rev Time 0.00
Received By dpalmer Date 2002-03-06 Time 14:18 Sent To  
Notes
2002-03-07 00:00:00****************** UNSAT *************
  
 PLEASE NOTE THERE WERE ONLY TWO NOTES,
 THAT STILL NEED TO BE ADDRESSED.
 PLEASE SEE FIRE REVIEW COMMENTS, THERE
 MAY BE SOME CHANGES THEY MAY AFFECT
 ELECTRICAL DRAWINGS.
 PLEASE NOTE THAT THE FIRE DEPT AND
 ELECTRICAL NEED TO HAVE LAYOUT CHANGED
 FOR "FIRE DEPT RM`S". PLEASE NOTE THAT
 ROOMS SEEM TO BE TOO SMALL FOR OPERATION
 OF EQUIPMENT/PANELS DURING A FIREOR
 TESTING OF EQUIPMENT. PLEASE NOTE HOW
 DOOR(S) OPEN DIRECTLY INFRONT OF ONE OF
 THE PANELS. THIS WOULD MAKE IT DIFFICULT
 FOR CLEARENCES. PLEASE NOTE CLEARENCES
 PER 110-26.
  
 1)NOTE: PLEASE NOTE FROM NOTE#16 FROM
 FIRST REVIEW. PLEASE NOTE THAT THE
 CONDUCTORS SIZES ARE NOW SHOWN FOR
 PANEL "DH". IT IS NOTED THAT OCP AT
 PANEL IS AT 500A`S. PLEASE CLARIFY LOAD
 BEING SHOWN AT 514AMPS? PLEASE NOTE
 310-16 75 DEGREE COLUMN FOR SIZING.
 LOAD EXCEEDS RATING FOR TWO SETS OF
 250MCM. (510A`S).
  
 2)NOTE: PLEASE NOTE THAT LOAD SHOWN FOR
 FIRE PUMP IS SHOWN AT 73.0 KVA.? THIS
 PUTS LOAD AT 202A. 430-150 PUTS MOTOR
 AT 211AMPS.
  
 PLEASE ALSO CLARIFY HOW LOAD SHOWN FOR
 PANEL"DE" IS SHOWN AT 124.6 KVA AND THEN
 ON LOAD STUDY FOR GEN., IT IS SHOWN AT
 106.2? IT IS NOTED THAT NOTE MENTIONS
 ONLY "ONE ELEVATOR". PLEASE CLARIFY
 HOW LOAD DECREASES WHEN "ATS" IS FEEDING
 ENTIRE PANEL?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-10-24 Cont ID  
Sent By dpalmer Date 2001-10-24 Time 22:04 Rev Time 0.00
Received By dpalmer Date 2001-10-24 Time 22:04 Sent To  
Notes
2001-10-24 00:00:00**************** UNSAT *****************
  
  
 1)NOTE: PLEASE NOTE THAT IN ORDER TO DO
 A COMPLETE PLAN REVIEW. PLANS NEED TO
 BE COMPLETE. GAZEBO IS MISSING,GENERATOR
 LOACTION, MISSING ELECTRICAL ROOM DETAIL
 -S FOR FLOOR WITH HOUSE PANELS?
  
 2)NOTE: PLEASE NOTE TWO FLOORS SHOWING
 HOUSE PANELS 4E AND 4H?
  
 3)NOTE: PLEASE NOTE THAT CIRCUIT LAYOUT
 ON LOWER CORNER OF E1-2 DOES NOT
 CORRELATE WITH E3-1?
  
 4)NOTE: PLEASE NOTE MEANS OF BEING ABLE
 TO SHUT DOWN GENERATOR TO BE GROUPED
 WITH MAINS? 230-72, 230-76,230-79
  
 5)NOTE: PLEASE NOTE THAT FIRE PUMP ROOM
 IS SHOWN ON SECOND FLOOR, WHERE IS MAIN
 ELECTRICAL ROOM?
  
 6)NOTE: PLEASE NOTE COMPLETE CONCRETE
 ENCASEMENT OF SERVICE ENTRANCE CONDUCTOR
 S, NO MORETHAN 8' OF UNPROTECTED CONDUCT
 -ORS INSIDE THE BLDG. PER LOCAL AMEND.
 230-70A
  
 7)NOTE: PLEASE NOTE PANEL "A" NOT
 COMPLETED.
  
 8)NOTE: PLEASE NOTE NO OCP SHOWN FOR
 ALL MAINS FOR APT PANELS???
  
 9)NOTE: PLEASE NOTE, ON E3-2 RISER SHOWS
 12H AND 12E AND YET E3-1 DOES NOT SHOW
 WHERE THESE ARE FED FROM? PANEL "DE"
 DOES NOT SHOW?
  
 10)NOTE: PLEASE NOTE GROUNDING ELECTRODE
 CONDUCTOR SIZE PER 250-66 NEEDS TO BE
 SHOWN ON E3-3
  
 PLEASE NOTE THAT THERE ARE MANY ITEMS
 ON E3-1 THAT NEED TO BE ADDRESSED.
  
 11)NOTE: PLEASE NOTE NO OCP SHOWN FOR
 FIRE PUMP, FROM FIRE PUMP CONTROL PANEL,
 AND FIRE PUMP ATS.
  
 12)NOTE: PLEASE NOTE CONDUCTOR TO FIRE
 PUMP ARE SHOWN AT 250MCM??, PLEASE SEE
 SIZING PER LOAD OF PUMP 430-150 AND
 CONDCUTOR SIZES PER 310-16.
  
 13)NOTE: PLEASE NOTE OCP PER 695-4-B-1
  
 14)NOTE: PLEASE NOTE THAT OCP ON GENER-
 -ATOR IS SHOWN AT 500AMPS WITH 250MCM??
 310-16.
  
 15)NOTE: PLEASE NOTE THAT CONDCUTOR SIZE
 FOR 400A ATS MAIN IS SHOWN AT 4/0?
 310-16 FOR 400AMPS, ALSO 350MCM FROM
 ATS TO PANEL "DE" ON 400A OCP??
  
 16)NOTE: PLEASE NOTE THAT NO CONDCUTOR
 SIZE IS SHOWN COMING FROM FPL TO 600A
 PANEL"DH"???
  
 17)NOTE: PLEASE NOTE THAT THERE ARE NO
 VOLTAGES SHOWN FOR PANEL"DH" ON PANEL
 SCHEDULE.
  
 18)NOTE:PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PANEL"DH" "DE" ETC
  
 19)NOTE: PLEASE NOTE THAT THERE ARE NO
 PANEL SCHEDULES SUBMITTED FOR ALL HOUSE
 PANELS, NOT TO INCLUDE CIRCUIT SCHEDULE
 ON E1-2.
  
 21)NOTE:PLEASE NOTE THAT THE GENERATOR
 IS TO BE SIZED PER 695-B-1. PLEASE
 NOTE THAT LOAD EXCEEDS RATING OF GEN.
 PLEASE CLARIFY HOW AUTOMATIC SHEDDING
 OF LOADS WILL TAKE PLACE???
  
 22)NOTE: PLEASE PLACE NOTE ON PLANS FOR
 COLOR CODING OF FEDDERS PER LOCAL
 AMENDMENTS 215-8 277/480V BR/PURP/YELLOW
 GRAY, 120/208 BLK/RED/BLUE.
  
 23)NOTE: PLEASE CLARIFY GROUNDING SIZE
 OF CONDCUCTOR FOR GENERATOR AS #4,???
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL. PLEASE CALL TO SET UP A
 MEETING IN PERSON TO CLARIFY ITEMS THAT
 MAY BE MORE CLEAR IN PERSON.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2003-10-10 Cont ID  
Sent By csiegber Date 2003-10-09 Time 16:09 Rev Time 0.00
Received By mamini Date 2001-10-18 Time 10:55 Sent To  
Notes
2001-10-18 00:00:00N/A
 1. SEE PERMIT # 01091474 FOR CIVIL/ SITE
 WORK. MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-10-05 Cont ID  
Sent By mamini Date 2001-10-05 Time 10:45 Rev Time 3.00
Received By mamini Date 2001-10-05 Time 10:24 Sent To  
Notes
2001-10-05 00:00:00FAILED:
 1. INSUFFICENT INFORMATIONS FOR CIVIL
 ENGINEERING REVIEW, PLEASE SUBMIT CIVIL
 PLANS FOR OUR REVIEW AND APPROVAL WHEN
 PLANS ARE COMPLETELY DEVELOPED.
 2. CIVIL PLANS SUBMITTAL SHOULD INCLUDE
 STORM WATER CALCULATIONS, PERVIOUS &
 IMPERVIOUS CALCULATIONS FOR ENTIRE SITE
 AND POLLUTION PREVENTION PLAN.
 3. WE RECOMMEND A SEPARATE PERMIT
 APPLICATION FOR UNDERGROUND UTILITIES
 AND SITE WORKS.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status P Date 2003-10-03 Cont ID  
Sent By mcarsill Date 2003-10-03 Time 15:33 Rev Time 0.00
Received By mcarsill Date 2003-10-03 Time 15:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status P Date 2003-08-29 Cont ID  
Sent By mcarsill Date 2003-08-29 Time 15:06 Rev Time 0.00
Received By mcarsill Date 2003-08-29 Time 15:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2003-07-16 Cont ID  
Sent By mcarsill Date 2003-07-16 Time 17:07 Rev Time 0.00
Received By mcarsill Date 2003-07-16 Time 17:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2003-04-29 Cont ID  
Sent By dpalmer Date 2003-04-28 Time 14:01 Rev Time 0.00
Received By nmccray Date 2003-04-29 Time 11:34 Sent To  
Notes
2003-04-29 00:00:00REVISION OK E1-1, E1-12, E3-1, & E3-4

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2003-01-16 Cont ID  
Sent By nmccray Date 2003-01-16 Time 10:59 Rev Time 0.00
Received By nmccray Date 2003-01-16 Time 10:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2002-09-26 Cont ID  
Sent By mcarsill Date 2002-09-26 Time 17:08 Rev Time 0.00
Received By mcarsill Date 2002-09-26 Time 17:08 Sent To  
Notes
2002-09-26 00:00:00THE REQUIRED FIRE PUMP WILL BE REQUIRED
 TO PROVIDE AT LEAST 750 GPM AT THE
 ROOF AT 65 PSI RESIDUAL PRESSURE AT THE
 SAME LOCATION. THE FIRE PUMP AND
 APPURTENANT EQUIPMENT ARE TO BE
 INSTALLED IN ACCORDANCE WITH NFPA 20.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-09-13 Cont ID  
Sent By mcarsill Date 2002-09-13 Time 17:30 Rev Time 0.00
Received By mcarsill Date 2002-09-13 Time 17:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-04-19 Cont ID  
Sent By dpalmer Date 2002-07-25 Time 10:34 Rev Time 0.00
Received By mcarsill Date 2002-04-19 Time 16:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-02-26 Cont ID  
Sent By mcarsill Date 2002-02-26 Time 09:19 Rev Time 0.00
Received By hpiskura Date 2002-02-26 Time 09:19 Sent To  
Notes
2002-02-26 00:00:00A) PLEASE INDICATE ON THE DRAWINGS
 THAT THE TRASH CHUTE CAP WILL BE AT
 LEAST THREE FEET ABOVE THE ROOF OF
 THE BUILDING. RE: NFPA 82, SECTION
 3-2.2.4.
 B) THE TRASH ROOM MUST BE AT LEAST
 TWO HOUR RATED WITH OPENING PROTECTIVES
 OF AT LEAST 1 1/2 RATINGS. RE: NFPA
 82, SECTION 3-2.4.3.
 C) IT APPEARS THAT A PORTION OF THE
 UNDERGROUND FIRE LINE RUNS UNDERNEATH
 THE BUILDING'S FOUNDATION. THIS IS
 NOT PERMITTED. RE: NFPA 24, SECTION
 8-3.1.
 D) ADDRESS REQUIRED ON BUILDING.
 E) CANVAS CANOPIES ARE TO BE FIRE
 RETARDANT.
 F) ROOF MANIFOLDS ARE REQUIRED ON THE
 ROOF. THE PLANS MAKE AT LEAST ONE
 REFERENCE TO FIRE DEPARTMENT CONNECTIONS
 BEING LOCATED ON THE ROOF.
 G) THE FIREFIGHTERS SMOKE CONTROL OR
 REMOVAL PANEL SHOULD BE LABELED WITH
 STAIRWELL LOCATIONS AND ANY OTHER
 LABELS THAT HELP PUT THE BUILDING INTO
 SOME ORIENTATION WITH REGARDS TO LAYOUT.
 H) CORRIDOR ARCH SECTION DISPLAYS
 6'- 8" HEIGHT. PLEASE VERIFY WITH
 BUILDING OFFICIALS IF THIS IS
 ACCEPTABLE.
 I) DOES UNIT A-2, UNIT C HAVE PIPE
 CHASES.
 J) THE PLAN REVIEW RESPONSE ITEM 20
 SHOULD BE AN ALERT TONE, FOLLOWED BY
 "AN EMERGENCY HAS BEEN REPORTED IN THE
 BUILDING, PLEASE LEAVE THE BUILDING,
 VIA THE EXITS, DO NOT USE THE ELEVATORS
 FOLLOWED AGAIN BY THE ALERT TONE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-10-09 Cont ID  
Sent By mcarsill Date 2001-10-09 Time 14:23 Rev Time 0.00
Received By mcarsill Date 2001-10-09 Time 14:23 Sent To  
Notes
2001-10-09 00:00:001) SITE PLAN DOES NOT INDICATE FIRE
 HYDRANT LOCATIONS.
 2) A DETERMINATION WILL BE REQUIRED BY
 THE BUILDING OFFICIAL OR HIS DESIGNEE
 WITH REGARDS TO THE COVERED WALKWAY.
 FS 553.895 (2) EXEMPTS AN OPEN PARKING
 GARAGE WITH A 20 FOOT SEPARATION FROM
 BEING FIRE SPRINKLER PROTECTED. THE
 COVERED PEDESTRIAN WALKWAY APPEARS TO
 CONNECT BOTH THE PARKING GARAGE AND THE
 HIGH-RISE BUILDING.
 3) A KNOX-BOX WILL BE REQUIRED FOR FIRE
 ACCESS.
 4) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 5) PLEASE CLARIFY WELL COMPACTED FIELD
 FOR FIRE TRUCK ACCESS.
 6) A TEMPORARY STANDPIPE SYSTEM WILL
 BE REQUIRED WHEN CONSTRUCTION REACHES
 THREE STORIES AND FIFTY FEET.
 7) STAIRS ARE TO BE CONTINIOUS WITH
 CONSTRUCTION.
 8) PLEASE DEMONSTRATE COMPLIANCE WITH
 THE STETCHER REQUIREMENTS OF 1997
 STANDARD BUILDING CODE.
 9) PLEASE EXPLAIN HOW ALL OF THE
 REQUIRED DEVICES FOR THE FIRE COMMAND
 CENTER ARE GOING TO FIT INTO THE
 CLOSET PROVIDED. PLEASE SEE 1997
 STANDARD BUILDING CODE.
 10) PLEASE DEMONSTRATE COMPLIANCE FOR
 SMOKE CONTROL REQUIREMENTS OF 1997
 STANDARD BUILDING CODE.
 11) SIGNS ARE REQUIRED FOR STAIRWAYS
 INDICATING FLOOR LEVEL, TERMINUS TOP
 AND BOTTOMS AND THE IDENTITY OF THE
 STAIRS.
 12) PLEASE INDICATE WHAT PROVISIONS
 HAVE BEEN MADE FOR FIRE RESCUE ACCESS
 FOR THE NORTH AND SOUTH GATES. WILL
 THESE GATES BE ELECTRIC OR MANUALLY
 OPERATED. IF ELECTRIC IS BATTERY
 BACK-UP AVAILABLE. SEPARATE PLANS
 AND PERMITS REQUIRED FOR SECURITY GATES.
 13) SITE PLAN DOES NOT INDICATE THE
 LOCATION OF THE ABOVEGROUND FUEL TANK
 SHOWN ON PAGE P-12.
 14) NO FIRE DEPARTMENT CONNECTIONS
 SHOWN ON FP-1. SINCE THE BUILDING IS
 CONSIDERED HIGH-RISE, TWO FIRE
 DEPARTMENT CONNECTIONS WILL BE REQUIRED.
 15) AREA DIRECTLY NEXT TO ELECTRICAL
 ROOM DISPLAYS NO FIRE SPRINKLER
 PROTECTION. WHAT IS THIS AREA USED FOR.
 16) INTERIOR FINISH INFORMATION
 REQUIRED FOR WALLS AND CEILINGS OF
 BUILDINGS.
 17) PLEASE INDICATE THAT ATTIC SPACES
 WILL NOT BE USED FOR STORAGE.
 18) HOW IS COMBUSTIBLE LINT REMOVED
 FROM THE DRYER EXHAUST RISERS.
 19) NO SMOKE DETECTORS SHOWN IN
 SLEEPING ROOMS.
 20) PLEASE INDICATE WHAT THE VOICE
 EVACUATION MESSAGE OF THE FIRE ALARM
 SYSTEM WILL SAY.
 21) ELECTRICAL DRAWINGS APPEAR TO BE
 INCOMPLETE.
 22) PLEASE PROVIDE MORE DETAILS ON
 SMOKE EVACUATION SYSTEM FOR THE STAIR
 TOWERS AND IDENTIFY THAT THESE SYSTEMS
 WILL BE ON EMERGENCY POWER.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 39 Status N Date 2003-10-09 Cont ID  
Sent By csiegber Date 2003-10-09 Time 16:08 Rev Time 0.00
Received By csiegber Date 2003-10-09 Time 16:08 Sent To ENG
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 38 Status N Date 2003-09-26 Cont ID  
Sent By csiegber Date 2003-09-26 Time 08:27 Rev Time 0.00
Received By csiegber Date 2003-09-26 Time 08:27 Sent To  
Notes
2003-09-26 00:00:00TO COMM BD#27

Review Stop I INCOMING/PROCESSING
Rev No 37 Status N Date 2003-09-24 Cont ID  
Sent By shernand Date 2003-09-24 Time 09:22 Rev Time 0.00
Received By shernand Date 2003-09-24 Time 09:22 Sent To B
Notes
2003-09-24 00:00:00DON NEELY'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 36 Status N Date 2003-09-22 Cont ID  
Sent By csiegber Date 2003-09-22 Time 14:15 Rev Time 0.00
Received By csiegber Date 2003-09-22 Time 14:15 Sent To B
Notes
2003-09-22 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 35 Status N Date 2003-08-27 Cont ID  
Sent By csiegber Date 2003-08-27 Time 14:54 Rev Time 0.00
Received By csiegber Date 2003-08-27 Time 14:53 Sent To B
Notes
2003-08-27 00:00:00TO HP DESK (HANDRAIL SPACING)

Review Stop I INCOMING/PROCESSING
Rev No 34 Status N Date 2003-08-22 Cont ID  
Sent By csiegber Date 2003-08-22 Time 16:03 Rev Time 0.00
Received By csiegber Date 2003-08-22 Time 16:03 Sent To B
Notes
2003-08-22 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 33 Status N Date 2003-08-22 Cont ID  
Sent By csiegber Date 2003-08-22 Time 16:01 Rev Time 0.00
Received By csiegber Date 2003-08-22 Time 16:01 Sent To E
Notes
2003-08-22 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 32 Status N Date 2003-08-19 Cont ID  
Sent By csiegber Date 2003-08-19 Time 15:39 Rev Time 0.00
Received By csiegber Date 2003-08-19 Time 15:39 Sent To E
Notes
2003-08-19 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2003-08-19 Cont ID  
Sent By csiegber Date 2003-08-19 Time 15:37 Rev Time 0.00
Received By csiegber Date 2003-08-19 Time 15:36 Sent To B
Notes
2003-08-19 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2003-08-12 Cont ID  
Sent By dbaxter Date 2003-08-12 Time 14:01 Rev Time 0.00
Received By dbaxter Date 2003-08-12 Time 14:01 Sent To E
Notes
2003-08-12 00:00:00TO ELEC. BOX.

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2003-08-08 Cont ID  
Sent By alange Date 2003-08-08 Time 16:03 Rev Time 0.00
Received By alange Date 2003-08-08 Time 16:03 Sent To E
Notes
2003-08-08 00:00:00TO D PALMER DESK

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2003-08-06 Cont ID  
Sent By alange Date 2003-08-06 Time 16:29 Rev Time 0.00
Received By alange Date 2003-08-06 Time 16:29 Sent To  
Notes
2003-08-06 00:00:00TO COMM BD #60

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2003-08-05 Cont ID  
Sent By alange Date 2003-08-05 Time 14:58 Rev Time 0.00
Received By alange Date 2003-08-05 Time 14:58 Sent To E
Notes
2003-08-05 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2003-08-04 Cont ID  
Sent By alange Date 2003-08-04 Time 16:05 Rev Time 0.00
Received By alange Date 2003-08-04 Time 16:05 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2003-08-04 Cont ID  
Sent By alange Date 2003-08-04 Time 15:50 Rev Time 0.00
Received By alange Date 2003-08-04 Time 15:50 Sent To E
Notes
2003-08-04 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2003-07-31 Cont ID  
Sent By alange Date 2003-07-31 Time 09:25 Rev Time 0.00
Received By alange Date 2003-07-31 Time 09:25 Sent To B
Notes
2003-07-31 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2003-07-02 Cont ID  
Sent By shernand Date 2003-07-02 Time 12:23 Rev Time 0.00
Received By shernand Date 2003-07-02 Time 12:23 Sent To B
Notes
2003-07-02 00:00:00HP DESK, REVISED STOREFRONT SUBMITTALS.

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2003-07-02 Cont ID  
Sent By shernand Date 2003-07-02 Time 12:18 Rev Time 0.00
Received By shernand Date 2003-07-02 Time 12:17 Sent To  
Notes
2003-07-02 00:00:00COMM BOARD #52TWO REVISIONS. ONE
 PACKET TO HP DESK.IN BOX IS REVISIONS
 TO P,E,B.

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2003-06-30 Cont ID  
Sent By shernand Date 2003-06-30 Time 16:51 Rev Time 0.00
Received By shernand Date 2003-06-30 Time 16:51 Sent To B
Notes
2003-06-30 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2003-06-27 Cont ID  
Sent By shernand Date 2003-06-27 Time 16:07 Rev Time 0.00
Received By shernand Date 2003-06-27 Time 16:07 Sent To  
Notes
2003-06-27 00:00:00COMM BOARD #44

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2003-05-19 Cont ID  
Sent By shernand Date 2003-05-19 Time 09:44 Rev Time 0.00
Received By shernand Date 2003-05-19 Time 09:44 Sent To B
Notes
2003-05-19 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2003-05-07 Cont ID  
Sent By shernand Date 2003-05-07 Time 13:22 Rev Time 0.00
Received By shernand Date 2003-05-07 Time 13:22 Sent To B
Notes
2003-05-07 00:00:00HP DESK. TWO SUBMITTALS.

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2003-04-21 Cont ID  
Sent By shernand Date 2003-04-21 Time 16:41 Rev Time 0.00
Received By shernand Date 2003-04-21 Time 16:41 Sent To E
Notes
2003-04-21 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2003-04-21 Cont ID  
Sent By shernand Date 2003-04-21 Time 16:34 Rev Time 0.00
Received By shernand Date 2003-04-21 Time 16:34 Sent To B
Notes
2003-04-21 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2003-04-11 Cont ID  
Sent By shernand Date 2003-04-11 Time 09:08 Rev Time 0.00
Received By shernand Date 2003-04-11 Time 09:08 Sent To  
Notes
2003-04-11 00:00:00COMM BOARD #51

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2003-03-11 Cont ID  
Sent By sthyng Date 2003-03-11 Time 16:23 Rev Time 0.00
Received By sthyng Date 2003-03-11 Time 16:23 Sent To B
Notes
2003-03-11 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2003-03-06 Cont ID  
Sent By dpalmer Date 2003-03-06 Time 14:32 Rev Time 0.00
Received By dpalmer Date 2003-03-06 Time 14:32 Sent To B
Notes
2003-03-06 00:00:00TO HP'S DESK, TRUSS SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2003-02-04 Cont ID  
Sent By dpalmer Date 2003-02-04 Time 08:55 Rev Time 0.00
Received By dpalmer Date 2003-02-04 Time 08:55 Sent To B
Notes
2003-02-04 00:00:00SUBMITTALS TO HHP`S DESK. DOORS.

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2003-02-04 Cont ID  
Sent By dpalmer Date 2003-02-04 Time 08:55 Rev Time 0.00
Received By dpalmer Date 2003-02-04 Time 08:55 Sent To B
Notes
2003-02-04 00:00:00SUBMITTALS TO HHP`S DESK. HANDRAILS.

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2003-02-04 Cont ID  
Sent By dpalmer Date 2003-02-04 Time 08:54 Rev Time 0.00
Received By dpalmer Date 2003-02-04 Time 08:54 Sent To B
Notes
2003-02-04 00:00:00SUBMITTALS TO HHP`S DESK. TRUSS.

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2003-01-24 Cont ID  
Sent By dpalmer Date 2003-01-24 Time 11:36 Rev Time 0.00
Received By dpalmer Date 2003-01-24 Time 11:36 Sent To B
Notes
2003-01-24 00:00:00SUBMITTALS TO HAROLD P'S DESK FIXED
 WINDOWS.

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2003-01-24 Cont ID  
Sent By dpalmer Date 2003-01-24 Time 11:35 Rev Time 0.00
Received By dpalmer Date 2003-01-24 Time 11:35 Sent To B
Notes
2003-01-24 00:00:00SUBMIT ROOF BEAM ETC TO HAROLD P'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-01-06 Cont ID  
Sent By dpalmer Date 2003-01-06 Time 16:51 Rev Time 0.00
Received By dpalmer Date 2003-01-06 Time 16:51 Sent To B
Notes
2003-01-06 00:00:00TO DON NEELY'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2002-12-23 Cont ID  
Sent By dpalmer Date 2002-12-23 Time 18:09 Rev Time 0.00
Received By dpalmer Date 2002-12-23 Time 18:09 Sent To B
Notes
2002-12-23 00:00:00TO HHP DESK.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2002-12-23 Cont ID  
Sent By dpalmer Date 2002-12-23 Time 12:26 Rev Time 0.00
Received By dpalmer Date 2002-12-23 Time 12:26 Sent To  
Notes
2002-12-23 00:00:00TO COMM BOARD #50

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2002-11-12 Cont ID  
Sent By btrobaug Date 2002-11-12 Time 17:58 Rev Time 0.00
Received By btrobaug Date 2002-11-12 Time 17:58 Sent To B
Notes
2002-11-12 00:00:00TO HAROLD P./WRT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2002-11-07 Cont ID  
Sent By btrobaug Date 2002-11-07 Time 11:16 Rev Time 0.00
Received By btrobaug Date 2002-11-07 Time 11:15 Sent To B
Notes
2002-11-07 00:00:00TO HAROLD P./WRT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-10-29 Cont ID  
Sent By dpalmer Date 2002-10-29 Time 07:03 Rev Time 0.00
Received By dpalmer Date 2002-10-28 Time 07:03 Sent To B
Notes
2002-10-29 00:00:00SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-28 Cont ID  
Sent By btrobaug Date 2002-10-28 Time 14:18 Rev Time 0.00
Received By btrobaug Date   Time   Sent To E
Notes
2002-10-28 00:00:00TO "E" IN BOX./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2003-09-02 Cont ID  
Sent By pkrauss Date 2003-09-02 Time 07:41 Rev Time 1.25
Received By pkrauss Date 2003-09-02 Time 07:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2003-04-15 Cont ID  
Sent By pkrauss Date 2003-04-15 Time 15:19 Rev Time 0.40
Received By pkrauss Date 2003-04-15 Time 15:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 8 Status F Date 2003-03-06 Cont ID  
Sent By pkrauss Date 2003-03-06 Time 09:22 Rev Time 0.55
Received By pkrauss Date 2003-03-06 Time 09:09 Sent To  
Notes
2003-03-06 00:00:00DENIED:MECHANICAL PERMIT 02041735
  
 1.DUCT PENETRATING "FIRE ROOM" HAS
 CHANGED TO FLEX.THIS IS A ONE HOUR
 PARTITION WALL, AS PER 1997 SMC 610.1.3
 EXCEPTIONS FOR LOCATION OF FIRE DAMPERS
 SHALL COMPLY WITH #3 ITEMS 1 THRU 4.
  
 1. DUCT SHALL NOT EXCEED 100 SQ IN
 2. DUCT SHALL BE OF .0217" MIN STEEL.
 3. DUCT SHALL CONTINUE W/NO OPENINGS
 FOR NOT LESS THAN 5' FROM RATED
 WALL.
 4. DUCT SHALL BE INSTALLED ABOVE A
 CEILING.
 PLEASE NOTE DUCT COMPLIES WITH ITEMS 1
 AND 4.
  
 2.CLARIFY DUCT PENETRATION THROUGH
 BATHROOM1 HR PATITION WALL.NO FIRE
 INDICATED ON PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2003-01-07 Cont ID  
Sent By pkrauss Date 2003-01-07 Time 13:46 Rev Time 0.50
Received By pkrauss Date 2003-01-07 Time 13:04 Sent To  
Notes
2003-01-07 00:00:00MECHANICAL PERMIT 02041735
  
 PROVISO:
 PLAN SHEET M-7 SEF-1, PLEASE NOTE
 LOCATION OF SEF-1 IN REFERENCE TO SPF-2,
 SHOULD BOTH SYSTEMS BE ACTIVATED WILL
 SPF-2 PULL SMOKE INTO THE STAIRWELL?
 PLEASE ADVISE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2002-09-27 Cont ID  
Sent By pkrauss Date 2002-09-27 Time 09:16 Rev Time 0.45
Received By pkrauss Date 2002-09-27 Time 08:06 Sent To  
Notes
2002-09-27 00:00:00REVISION FIRE DAMPERS FOR CORRIDOR
 PLAN SHEET M-2 ONLY
  
 ALSO SUBMITTALS FOR CONTROLS

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2002-08-07 Cont ID  
Sent By pkrauss Date 2002-08-07 Time 14:47 Rev Time 1.00
Received By pkrauss Date 2002-08-07 Time 14:47 Sent To  
Notes
2002-08-07 00:00:00THIS IS NOT A REVISION - SUBMITTAL DATA
 FOR VALVES, PIPE, INSULATION, ETC.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-04-19 Cont ID  
Sent By ndenmark Date 2002-04-19 Time 13:50 Rev Time 2.00
Received By ndenmark Date 2002-04-19 Time 13:50 Sent To  
Notes
2002-04-19 00:00:00PROVISO:
 ORIGINAL LETTER FROM BUILDING OWNER (2
 COPIES) REQUIRED TO BE SUBMITTED PRIOR
 TO FIRST INSPECTION
  
 THIRD RAISED SEAL ENGINEERS CALCULATION
 ON WINDOW OPEN AREA TO BE SUBMITTED AND
 STAMPED AND ADDED TO PLAN
  
 LETTER DETAILING ACCEPTANCE TEST FOR
 SMOKE CONTROL AND STAIR PRESSURIZATION
 TEST TO BE SUBMITTED FOR APPROVAL PRIOR
 TO BUILDING FINAL

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2002-04-11 Cont ID  
Sent By pkrauss Date 2002-04-01 Time 13:52 Rev Time 1.30
Received By pkrauss Date 2002-04-01 Time 12:14 Sent To  
Notes
2002-04-01 00:00:00 
 PLEASE CLARIFY THE SEQUENCE OF OPERATION
 FOR THE CORRIDOR (PLAN SHEET M-16).AS
 PER NFPA 92A 1.5.2, THE PRIMARY MEANS
 OF CONTROLLING SMOKE MOVEMENT IS BY
 CREATING AIR PRESSURE DIFFERENCES
 ACROSS PARTIONS, FLOORS AND OTHER
 BUILDING COMPONENTS.THE BASIC CONCEPT
 OF BUILDING PRESSURIZATION IS TO
 ESTABLISH A HIGHER PRESSURE IN ADJACENT
 SPACES THAN IN THE SMOKE ZONE.THE
 SEQUENCE OF OPERATION AS DESCRIBED ON
 PLAN SHEET M-15, INDICATES THE OPPOSITE
 OF WHAT IS REQUIRED BY NFPA 92A.SMOKE
 ZONE IS POSITIVE AND OTHER FLOORS ARE
 NEGATIVE.
  
 CONTACT CHIEF MECHANICAL INSPECTOR
 (NANCY DENMARK), FOR MEETING ON THE
 TEST CRITERIA FOR SMOKE CONTROL SYSTEM.
  
 PLEASE NOTE DRYERS TO BE INSTALLED AT
 FINAL INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.
  
 SPOKE WITH RALPH PENA (ENG) - SHOW
 COMPLIANCE WITH 1997 SBC 412.5.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-02-26 Cont ID  
Sent By pkrauss Date 2002-02-26 Time 13:04 Rev Time 2.00
Received By pkrauss Date 2002-02-26 Time 13:04 Sent To  
Notes
2002-02-26 00:00:00 
 PLAN SHEET M-8 GENERAL NOTES #1. A.,
 ALL WORK SHALL BE IN ACCORDANCE WITH
 SOUTH FLORIDA BUILDING CODE.PLANS ARE
 REVIEWED UNDER THE 1997 STANDARD
 MECHANICAL CODE NOT THE SOUTH FLORIDA
 BUILDING CODE.
  
 PLAN SHEET M-5 DETAILS FOR DRYER
 EXHAUST, AS PER 1997 SMC 509.3
 RESIDENTIAL DRYER EXHAUST SHALL BE A
 MAXIMUM OF 25 FT WITH A 5 FT REDUCTION
 FOR EACH 90 DEGREE BEND AND 2 1/2 FT
 REDUCTION FOR EACH 45 DEGREE BEND.
 DRYER EXHAUST IS GREATER THAN THE 25 FT
 ALLOWANCE.INDICATE HOW COMBUSTIBLE
 LINT IS TO BE REMOVED FROM THE DRYER
 EXHAUST.
  
 PLEASE NOTE ON THE TOILET EXHAUST RISER
 AS PER COUNTYWIDE AMENDMENTS 1997 SMC
 610.1.3 #2, SUBDUCT MUST BE A MINIMUM
 OF 26 GA. GALVANIZED OR EQUIVALENT.
 RISERS WHICH ARE SUBJECT TO MOISTURE
 SHALL BE LINED WITH SUITABLE MATERIAL
 TO PREVENT DETERIORATION OF DRYWALL
 ENCLOSURE. WHERE BRANCH DUCTS CONNECT TO
 RETURN RISERS, SUBDUCT SHALL BE CARRIED
 UPWARD 22" INSIDE THE RISER DUCT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-10-17 Cont ID  
Sent By pkrauss Date 2001-10-17 Time 11:07 Rev Time 8.00
Received By pkrauss Date 2001-10-16 Time 09:02 Sent To  
Notes
2001-10-17 00:00:00********************DENIED**************
  
 1.PROVIDE CLARIFICATION OF THE SMOKE
 EVAC FOR THE CORRIDORS ON FLOORS 2
 THRU 15.NOTE ON PLAN SHEET M-8
 INDICATE RTU 1 & 2 FAN MOTOR WILL
 CONTINUE TO RUN. PROVIDE SEQUENCE OF
 OPERATION FOR THE MOTORZIED DAMPERS
 INDICATED ON PLAN SHEET M-4.
  
 2.PROVIDE INFORMATION FOR SEQUENCE OF
 OPERATION FOR GROUND FLOOR SMOKE
 EVAC.
  
 3.PROVIDE CALCULATIONS AS PER 1997
 SBC 412.5.
  
 4.PROVIDE INFORMATION AS TO THE GROUND
 FLOOR RETURN AIR PLENUM.PLAN SHEET
 M-7 INDICATES RETURN AIR GRILLS IN
 THE VARIOUS OFFICES AND FITNESS
 CENTER.THERE IS NO INDICATION HOW
 THE AIR IS BEING RETURNED BACK TO
 THE AIR HANDLER BE MEANS OF DUCTWORK
 OR TRANSFER DUCTS.
  
 5.CLARIFY ALSO IF THESE AREAS WERE
 TAKEN INTO CONSIDERATION IN THE
 DESIGN OF THE SMOKE EVAC TO THIS
 FLOOR.
  
 6.SUBMIT TEST CRITERIA FOR THE SMOKE
 EVAC SYSTEM.
  
 7.ONLY ONE FIRE DAMPER IS DESIGNATED
 ON THE GROUND FLOOR.THE CORRIDOR
 LOOKS TO HAVE A FIRE RATING OF 1 HR.
 EXPLAIN WHY THE OTHER PENETRATIONS
 ARE NOT PROTECTED.
  
 8.PROVIDE CALCULATIONS FOR STAIRWELL
 PRESSURIZATION.
  
 PLEASE NOTE, STAIRWELL PRESSURIZATION
 SHALL BE TESTED WITH ALL DOORS CLOSED
 AND ALSO WITH ONE EXTERIOR DOOR PROPPED
 OPEN APPROXIMATELY 5" SIMULATING PEOPLE
 EXITING IN AN EMERGENCY SITUATION.AN
 INDEPENDANT TEST AND BALANCE COMPANY AND
 THE ENGINEER OF RECORD SHOULD ATTEND THE
 FINAL TESTING.
  
 9.PROVIDE RISER DIAGRAM FOR SPRINKLER
 SYSTEM FOR INDICATING LOCATION OF
 SPRINKLER HEADS AND ACCESS DOORS
 FOR MAINTENANCE FOR THE TRASH CHUTE
 AS WELL AS THE DRYER VENT SHAFT.
 1997 SBC 705.4.2.6.
  
 10. PLEASE CLARIFY SEPARATION OF DRYER
 EXHAUST AND TOILET EXHAUST SHARING
 THE 2 HOUR RATED SHAFT.PROVIDE A
 DETAIL SHOWING HOW THE SUB-DUCT IS
 SUPPORTED IN THE SHAFT.
  
 11. PLEASE NOTE THE ACCESS DOOR ON PLAN
 SHEET M-10 FOR THE DRYER EXHAUST IS
 NOT ACCESSIBLE.
  
 12. PROVIDE INFORMATION ON HOW THE
 COMBUSTIBLE LINT IS TO BE REMOVED
 FROM THE SHAFT.
  
 13. PLAN SHEET M-3, CLARIFY THE EXHAUST
 DUCT RUNNING THRU OR TERMINATING IN
 THE STAIRWELL.
  
 14. M-3, ON THE SOUTHEAST ROOF THE
 DRYER VENT CLOSE PROXIMTY TO THE
 CONDENSER UNITS.
  
 15. PLAN SHEET M-12 FAN COIL UNIT
 MOUNTING DETAIL, AUXILIARY DRAIN PAN
 WITH OVERFLOW PROTECTION BY MEANS OF
 A FLOAT SWITCH A SEPARATE DRAIN
 TERMINATING AT A CONSPICUOUS POINT
 TO SERVE AS AN ALARM THAT REGULAR
 LINE IS RESTRICTED. 1997 SMC
 304.8.6.1.
  
 16. PLAN SHEET M-13 DETAIL OF CONDENSING
 UNIT SUPPORTS.MINIMUM OF 18"
 BETWEEN THE ROOF SURFACE AND THE
 BOTTOM OF THE SUPPORT RAIL AS PER
 COUNTYWIDE AMENDMENTS 1997 SMC
 304.2.5.
  
 17. CONDENSER UNIT LOCATION SHALL COMPLY
 WITH 1997 SMC 304.7.2, A MINIMUM OF
 30" OF CLEAR SPACE ON THE SERVICE
 SIDE FOR INSPECTION AND SERVICING OF
 CONDENSING UNITS OR COMPRESSOR UNITS
 SHALL BE PROVIDED.
  
 18. PROVIDE LOCATION OF FUEL TANK.
  
 19. ADDITIONAL PERMIT REQUIRED FOR FUEL.
 PLEASE PROVIDE PLANS WITH PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 9 Status P Date 2003-09-04 Cont ID  
Sent By kstevens Date 2003-09-04 Time 10:28 Rev Time 1.25
Received By kstevens Date 2003-09-04 Time 10:28 Sent To  
Notes
2003-09-04 00:00:00REVISION OK - SHEET P1-A

Review Stop P PLUMBING
Rev No 8 Status P Date 2003-08-22 Cont ID  
Sent By kstevens Date 2003-08-22 Time 15:22 Rev Time 0.50
Received By kstevens Date 2003-08-22 Time 15:22 Sent To  
Notes
2003-08-22 00:00:00REVISION OK - SCUPPER DETAIL -

Review Stop P PLUMBING
Rev No 7 Status P Date 2003-07-14 Cont ID  
Sent By kstevens Date 2003-07-14 Time 12:02 Rev Time 1.00
Received By kstevens Date 2003-07-14 Time 12:01 Sent To  
Notes
2003-07-14 00:00:00REVISION OK - SANT. RISER DIAGRAM -
 WATER RISER DIAGRAM - DELETED W/C MEN'S
 ROOM AND MOVED W/H LOCATION

Review Stop P PLUMBING
Rev No 6 Status P Date 2003-01-11 Cont ID  
Sent By kstevens Date 2003-01-11 Time 17:26 Rev Time 0.75
Received By kstevens Date 2003-01-11 Time 17:26 Sent To  
Notes
2003-01-11 00:00:00REVISION OK - REMOVE W/C - URNAL, ADD
 SUNAS, MOVE SHOWERS, MOVE BAR SINK IN
 CLUBHOUSE, ADD OUTDOOR SHOWER AT CABANA

Review Stop P PLUMBING
Rev No 5 Status P Date 2002-11-18 Cont ID  
Sent By kstevens Date 2002-11-18 Time 18:55 Rev Time 0.50
Received By kstevens Date 2002-11-18 Time 18:55 Sent To  
Notes
2002-11-18 00:00:00WATER HEATER PAN SUBMITTALS - PROVISO
 PAN TO BE LARGE ENOUGH TO DRAIN PROPERLY
 AND HEATER DRAIN VALVE SHALL BE WITHIN
 THE PAN AREA.

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-10-10 Cont ID  
Sent By dpalmer Date 2002-11-13 Time 13:01 Rev Time 0.00
Received By kstevens Date 2002-10-10 Time 16:46 Sent To  
Notes
2002-10-10 00:00:00SUBMITTALS OK - D.F - SINK - FAUCET -
 W/H - SHR VALVE - OUT DOOR SHR

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-08-16 Cont ID  
Sent By kstevens Date 2002-08-16 Time 07:56 Rev Time 0.00
Received By kstevens Date 2002-08-16 Time 07:56 Sent To  
Notes
2002-08-16 00:00:00SUBMITTALS OK - FIXTURES & TRIM, PIPING,
 DRAINS, BOOSTER PUMP

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-02-25 Cont ID  
Sent By kstevens Date 2002-02-25 Time 16:12 Rev Time 1.50
Received By kstevens Date 2002-02-25 Time 16:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-20 Cont ID  
Sent By pschmitz Date 2001-10-20 Time 13:23 Rev Time 4.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-10-20 00:00:00PLUMBING PLAN REVIEW,DENIED
 CODE REFERENCE,STD PLUMBING CODE 94
 (1)SHT A20,NOTE 7,FACBC-97 NOT APPROVED
 COMPLY WITH FAIR HOUSING ACT 24 CODE OF
 REGULATION (CFR) 100.205 (C)(IV),
 REVISED APRIL 1998, DESIGN MANUAL.
 REQUIRMENTS 1 THRU 7,SPECIFY OPTION "A"
 OR "B". SHOW MANEUVERING AND CLEAR FLOOR
 SPACE, REQUIRMENT 7 AND REINFORCED WALL
 AREAS, AS OUT LINED IN DESIGN MANUAL.
 (2) SHT A28 DETAIL 4,PROVIDE A ISOMETRIC
 DRAWING OF ROOF DRAINAGE WITH PIPE SIZES
 , SQUARE FOOTAGE; ALSO INCLUDE 1/2 THE
 VERTIAL WALLS AND UPPER ROOFS.
 PROVIDE CALCULATIONS FOR THE SECONDARY
 DRAINAGE, INCLUDE 1/2 THE VERTIAL WALLS
 AND UPPER ROOFS. SEC 1108,1108.3,1109.
 (3A)SHT P1 PROVIDE A COMPLETE PLAN VIEW
 OF THE UNDER GROUND STORM AND SANITARY
 BUILDING DRAINAGE SYSTEM,SHOW PIPE SIZES
 AND THE LOAD ON EACH SYSTEM, SEC 104.3
 (B) TRASH ROOM DRAIN NOT APPROVED TO
 STORM DRAINAGE. SEC 701.5
 (C) SANITARY BUILDING DRAINS, 4" THRU 6"
 CLEANOUTS NOT MORE THAN 80 FT INTERVALS.
 SEC 710.2.4 (2)
 (4) SHT P6 SPECIFY TYPE OF SHOCK
 ARRESTOR AND TABLE FOR SIZING, SEC 104.3
 (5) SHT P 12 NOTE #10 RELIEF VENT, SHOW
 VENTS ON RISER,SHTS P8,P9. SEC 104.3 AND
 SEC 916.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS 561-659-8096X 8233

Review Stop Z ZONING
Rev No 1 Status P Date 2001-10-04 Cont ID  
Sent By sgraham Date 2001-10-04 Time 12:31 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***