Plan Review Details - Permit 01091396
Plan Review Stops For Permit 01091396
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-10-17 Cont ID  
Sent By hpiskura Date 2001-10-17 Time 15:58 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-11-01 Cont ID  
Sent By dpalmer Date 2001-11-01 Time 11:35 Rev Time 0.00
Received By dpalmer Date 2001-11-01 Time 11:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-10-01 Cont ID  
Sent By dpalmer Date 2001-10-01 Time 23:56 Rev Time 0.00
Received By dpalmer Date 2001-10-01 Time 23:55 Sent To  
Notes
2001-10-01 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT GROUNDING FOR
 TRANSFORMER NEEDS TO BE SHOWN TO EXIST-
 -ING BLDG STEEL 250-30. PLEASE NOTE THAT
 IT IS NOT KNOWN IF THERE ARE ANY BREAKS
 OF PVC IN THE COLD WATER LINE.
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 AND ALL CONTINUOUS LOADS AT 125%.
 215-5,230-42,215-2-3.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASES NOTE THAT AIC RATINGS ARE
 SHOWN FOR PANELS BUT NOT MIAN DISCONNECT
 PLEASE SHOW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-10-30 Cont ID  
Sent By mcarsill Date 2001-10-30 Time 16:56 Rev Time 0.00
Received By mcarsill Date 2001-10-30 Time 16:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-10-02 Cont ID  
Sent By mcarsill Date 2001-10-02 Time 11:04 Rev Time 0.00
Received By mcarsill Date 2001-10-02 Time 11:04 Sent To  
Notes
2001-10-02 00:00:001) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
 2) FIRE-ALARM NOTES ON PAGE FAO.1
 INDICATES CLASS B, STYLE C CIRCUITS.
 ONLY CLASS A, STYLE D CIRCUITS ALLOWED.
 3) FIRE ALARM NOTES INDICATES DUCT
 SMOKE DETECTOR WHEN ACTIVATED WILL
 CAUSE A TROUBLE SIGNAL. WHEN ACTIVATED
 THIS DEVICE IS TO SOUND FIRE ALARM
 SYSTEM.
 4) ARE ANY STORAGE RACKS PLANNED FOR
 THE WAREHOUSE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-10-15 Cont ID  
Sent By ndenmark Date 2001-10-15 Time 08:51 Rev Time 0.33
Received By ndenmark Date 2001-10-15 Time 08:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-11-04 Cont ID  
Sent By pschmitz Date 2001-11-04 Time 12:24 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-12 Cont ID  
Sent By kstevens Date 2001-10-12 Time 18:03 Rev Time 0.50
Received By kstevens Date 2001-10-12 Time 18:03 Sent To  
Notes
2001-10-12 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PAGE PO.1 PLUMBING NOTES #13 & #18.
 AIR CHAMBERS DO NOT WORK AND SHOULD NOT
 BE USED. IF THEY ARE USED THEY SHALL
 COMPLY WITH SPC-94 SEC 607.8.3 AND BE
 ACCESSIBLE AND RECHARGABLE PER WH-PDI
 201. WATER HAMMER ARRESTORS SHALL BE
 SIZED AND LOCATED PER MANUFACTURE IN-
 STALLATION INSTRUCTIONS AND WH-PDI 201.
 THEY SHALL BE LOCATED CLOSE TO THE
 SOURCE AND NOT AT TOP OF DROP AS SHOWN.
  
 2) OCCUPANT CONTENT PER SHIFT REQUIRED
 FOR WAREHOUSE AREA, SUBSTANTIATED BY
 OWNER PER SPC-94 TABLE 407 TO CALCULATE
 MINIMUM FACILITIES.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377