Plan Review Details - Permit 01091396
Plan Review Stops For Permit 01091396 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2001-10-17 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2001-10-17 |
Time |
15:58 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2001-11-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-11-01 |
Time |
11:35 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-11-01 |
Time |
11:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-10-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-10-01 |
Time |
23:56 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-10-01 |
Time |
23:55 |
Sent To |
|
|
Notes |
2001-10-01 00:00:00 | ***************** UNSAT *************** | | | | 1)NOTE: PLEASE NOTE THAT GROUNDING FOR | | TRANSFORMER NEEDS TO BE SHOWN TO EXIST- | | -ING BLDG STEEL 250-30. PLEASE NOTE THAT | | IT IS NOT KNOWN IF THERE ARE ANY BREAKS | | OF PVC IN THE COLD WATER LINE. | | | | 2)NOTE: PLEASE SHOW LOAD CALCULATIONS, | | AND ALL CONTINUOUS LOADS AT 125%. | | 215-5,230-42,215-2-3. | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | PLEASES NOTE THAT AIC RATINGS ARE | | SHOWN FOR PANELS BUT NOT MIAN DISCONNECT | | PLEASE SHOW. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2001-10-30 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-10-30 |
Time |
16:56 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-10-30 |
Time |
16:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2001-10-02 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-10-02 |
Time |
11:04 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-10-02 |
Time |
11:04 |
Sent To |
|
|
Notes |
2001-10-02 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS PROVIDED | | WITH PLANS. | | 2) FIRE-ALARM NOTES ON PAGE FAO.1 | | INDICATES CLASS B, STYLE C CIRCUITS. | | ONLY CLASS A, STYLE D CIRCUITS ALLOWED. | | 3) FIRE ALARM NOTES INDICATES DUCT | | SMOKE DETECTOR WHEN ACTIVATED WILL | | CAUSE A TROUBLE SIGNAL. WHEN ACTIVATED | | THIS DEVICE IS TO SOUND FIRE ALARM | | SYSTEM. | | 4) ARE ANY STORAGE RACKS PLANNED FOR | | THE WAREHOUSE. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2001-10-15 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2001-10-15 |
Time |
08:51 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
2001-10-15 |
Time |
08:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2001-11-04 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2001-11-04 |
Time |
12:24 |
Rev Time |
1.50 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-10-12 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-10-12 |
Time |
18:03 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2001-10-12 |
Time |
18:03 |
Sent To |
|
|
Notes |
2001-10-12 00:00:00 | DENIED | | REFERENCE: SPC-94 - FACBC-97 | | | | 1) PAGE PO.1 PLUMBING NOTES #13 & #18. | | AIR CHAMBERS DO NOT WORK AND SHOULD NOT | | BE USED. IF THEY ARE USED THEY SHALL | | COMPLY WITH SPC-94 SEC 607.8.3 AND BE | | ACCESSIBLE AND RECHARGABLE PER WH-PDI | | 201. WATER HAMMER ARRESTORS SHALL BE | | SIZED AND LOCATED PER MANUFACTURE IN- | | STALLATION INSTRUCTIONS AND WH-PDI 201. | | THEY SHALL BE LOCATED CLOSE TO THE | | SOURCE AND NOT AT TOP OF DROP AS SHOWN. | | | | 2) OCCUPANT CONTENT PER SHIFT REQUIRED | | FOR WAREHOUSE AREA, SUBSTANTIATED BY | | OWNER PER SPC-94 TABLE 407 TO CALCULATE | | MINIMUM FACILITIES. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT. 8377 |
|
|
|