Plan Review Stops For Permit 01091304 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2002-02-14 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2002-02-14 |
Time |
18:06 |
Rev Time |
0.33 |
Received By |
jgomez |
Date |
2002-02-14 |
Time |
18:06 |
Sent To |
|
|
Notes |
2002-02-14 00:00:00 | TRUSS DRAWINGS REVIEW. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2001-12-06 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2001-12-06 |
Time |
18:45 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2001-12-06 |
Time |
18:45 |
Sent To |
|
|
Notes |
2001-12-06 00:00:00 | APPROVED WITH PROVISO: | | 1-FLOOD ZONE AO: NEED THE ELEVATION | | CERTIFICATE. | | 2-NEED ADDITIONAL SOIL BORINGS FOR EACH | | STRUCTURE AS RECOMMENDED ON THE PRE- | | LIMINARY SOIL TEST REPORT. | | 3-PROVIDE PRODUCT APPROVAL FOR FRENCH | | DOORS ASSEMBLIES AS SHOWN ON PLANS IF | | OPTION SELECTED. | | 4-PROVIDE MANUFACTURER'S CERTIFICATION | | FOR TWO HOUR FIRE RATED CONCRETE BLOCK | | ACCORDING TO THE BLOCK'S EQUIVALENT | | THICKNESS AND AGGREGATES USED. SEE | | SECTION 709.3 SBC 1997. | | 5-PROVIDE COMPLETE INFORMATION FOR STORM | | PANELS UNDER A SEPARATE PERMIT. | | 6-TRUSS DRAWINGS: | | -UPDATE ALL GENERAL TRUSS DETAILS. USE | | ASCE 7-95 FOR 140 MPH, NOT ASCE 7-93. | | SEE COMMENTS ON DRAWINGS. | | | | | | | | NOTES: | | -DRAWINGS AND COMMENTS TO BE FILED UNDER | | PERMIT #01091304. | | -THESE COMMENTS APPLY TO PERMIT #S: | | 01091304, 01091306, 01091308, 01091312, | | 01091314 AND 01091316. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2001-10-27 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2001-10-27 |
Time |
15:45 |
Rev Time |
1.00 |
Received By |
jgomez |
Date |
2001-10-27 |
Time |
15:45 |
Sent To |
|
|
Notes |
2001-10-27 00:00:00 | CHECKLIST: | | 1-SEE COMMENTS BY PLUMBING. REVISE | | ORIGINAL DRAWINGS TO AVOID DELAYS. | | 2-NEED TO RECORD NOTICE OF COMMENCEMENT. | | 3-NEED ADDITIONAL SOIL BORINGS FOR EACH | | STRUCTURE AS RECOMMENDED ON THE PRE- | | LIMINARY SOIL TEST REPORT. | | 4-PROVIDE PRODUCT APPROVAL FOR: | | A)GARAGE DOORS PRODUCT APPROVAL WAS | | DELETED FROM SBCCI LISTING. | | B)WINDOW MULLIONS. | | | | 5-CLEARLY INDICATE ON PLANS OPTIONS TO | | BE BUILT AND PROVIDE PRODUCT APPROVALS | | OR CROSS OUT OPTIONS. | | 6-OWES ADDITIONAL FEES FOR UPDATED VALUE | | AND RADON FEES. PLEASE PAY ATTACHED | | RECEIPTS AND BRING PAID RECEIPTS. | | 7-PROVIDE CERTIFICATION FOR TWO HR FIRE | | RATED CONCRETE BLOCK THAT COMPLIES W/ | | SECTION 709.3 SBC 1997 ACCORDING TO | | THE EQUIVALENT THICKNESS. | | 8-PROVIDE COMPLETE INFORMATION FOR STORM | | PANELS OR APPLY FOR A SEPARATE PERMIT. | | | | | | | | | | NOTES: | | -DRAWINGS AND COMMENTS TO BE FILED UNDER | | PERMIT #01091304. | | -THESE COMMENTS APPLY TO PERMIT #S: | | 01091304, 01091306, 01091308, 01091312, | | 01091314 AND 01091316. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2002-07-23 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-07-23 |
Time |
10:05 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-07-23 |
Time |
10:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-06-07 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-06-07 |
Time |
15:36 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-06-07 |
Time |
14:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2001-10-23 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-10-23 |
Time |
07:26 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-10-23 |
Time |
07:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2001-12-06 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-12-06 |
Time |
17:11 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-12-06 |
Time |
17:11 |
Sent To |
|
|
Notes |
2001-12-06 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | TO,DURING AND AFTER CONSTRUCTION. | | 2) BUILDING ADDRESSES REQUIRED. | | 3) PORTABLE FIRE EXTINGUISHERS REQUIRED. | | 4) ELECTRIC POWERED SMOKE DETECTORS | | REQUIRED. | | 5) EGRESS WINDOWS TO COMPLY WITH | | BUILDING AND FIRE CODE REQUIREMENTS. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2002-01-29 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-01-29 |
Time |
13:12 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2002-01-29 |
Time |
12:39 |
Sent To |
|
|
Notes |
2002-01-29 00:00:00 | MECH REV PERMIT 01100037 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2001-10-20 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2001-10-20 |
Time |
08:40 |
Rev Time |
0.33 |
Received By |
hmoser |
Date |
2001-10-20 |
Time |
08:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2001-11-30 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-11-30 |
Time |
18:15 |
Rev Time |
0.33 |
Received By |
kstevens |
Date |
2001-11-30 |
Time |
18:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-10-17 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-10-17 |
Time |
16:51 |
Rev Time |
0.25 |
Received By |
jleech |
Date |
2001-10-17 |
Time |
16:51 |
Sent To |
|
|
Notes |
2001-10-17 00:00:00 | DENIED; | | 1.PAGE 1A & 2 GENERAL NOTES. CHANGE TO | | READ FHA 98 DESIGN MANUAL. | | 2.MODEL 1527 L & R.M/B SHOWS 1'7" TO | | CENTER OF W/C AND IT SHOULD BE 1' 6" | | ALSO SHOW CLEAR FLOOR SPACE FOR LAV. | | PAGE 1A &1B. | | 3.IN BATH 2 SHOW CLEAR FLOOR SPACE FOR | | W/C AND LAV. PAGE 1A &1B. | | 4.MODEL 1409 M/B SHOWS 1'7" TO CENTER | | OF W/C AND IT SHOULD BE 1'6" ALSO | | SHOW CLEAR FLOOR SPACE FOR W/C AND | | LAV. PAGE 1A &1B. | | 5.BATH 2 SHOWS 2'8" OPENING FOR W/C | | 2'9" MIN. SPACE REQUIRED FOR W/C ALSO | | SHOW CLEAR FLOOR SPACE FOR W/C AND LAV | | PAGE 1A &1B. | | 6.PAGE 2 RISER DIAGRAMS. MODEL 1527 & | | 1409. SHOW VENT FOR OPT. L.T. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2001-10-09 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2001-10-09 |
Time |
14:12 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|