Plan Review Details - Permit 01091304
Plan Review Stops For Permit 01091304
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-02-14 Cont ID  
Sent By jgomez Date 2002-02-14 Time 18:06 Rev Time 0.33
Received By jgomez Date 2002-02-14 Time 18:06 Sent To  
Notes
2002-02-14 00:00:00TRUSS DRAWINGS REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-12-06 Cont ID  
Sent By jgomez Date 2001-12-06 Time 18:45 Rev Time 0.50
Received By jgomez Date 2001-12-06 Time 18:45 Sent To  
Notes
2001-12-06 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE AO: NEED THE ELEVATION
 CERTIFICATE.
 2-NEED ADDITIONAL SOIL BORINGS FOR EACH
 STRUCTURE AS RECOMMENDED ON THE PRE-
 LIMINARY SOIL TEST REPORT.
 3-PROVIDE PRODUCT APPROVAL FOR FRENCH
 DOORS ASSEMBLIES AS SHOWN ON PLANS IF
 OPTION SELECTED.
 4-PROVIDE MANUFACTURER'S CERTIFICATION
 FOR TWO HOUR FIRE RATED CONCRETE BLOCK
 ACCORDING TO THE BLOCK'S EQUIVALENT
 THICKNESS AND AGGREGATES USED. SEE
 SECTION 709.3 SBC 1997.
 5-PROVIDE COMPLETE INFORMATION FOR STORM
 PANELS UNDER A SEPARATE PERMIT.
 6-TRUSS DRAWINGS:
 -UPDATE ALL GENERAL TRUSS DETAILS. USE
 ASCE 7-95 FOR 140 MPH, NOT ASCE 7-93.
 SEE COMMENTS ON DRAWINGS.
  
  
  
 NOTES:
 -DRAWINGS AND COMMENTS TO BE FILED UNDER
 PERMIT #01091304.
 -THESE COMMENTS APPLY TO PERMIT #S:
 01091304, 01091306, 01091308, 01091312,
 01091314 AND 01091316.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-10-27 Cont ID  
Sent By jgomez Date 2001-10-27 Time 15:45 Rev Time 1.00
Received By jgomez Date 2001-10-27 Time 15:45 Sent To  
Notes
2001-10-27 00:00:00CHECKLIST:
 1-SEE COMMENTS BY PLUMBING. REVISE
 ORIGINAL DRAWINGS TO AVOID DELAYS.
 2-NEED TO RECORD NOTICE OF COMMENCEMENT.
 3-NEED ADDITIONAL SOIL BORINGS FOR EACH
 STRUCTURE AS RECOMMENDED ON THE PRE-
 LIMINARY SOIL TEST REPORT.
 4-PROVIDE PRODUCT APPROVAL FOR:
 A)GARAGE DOORS PRODUCT APPROVAL WAS
 DELETED FROM SBCCI LISTING.
 B)WINDOW MULLIONS.
  
 5-CLEARLY INDICATE ON PLANS OPTIONS TO
 BE BUILT AND PROVIDE PRODUCT APPROVALS
 OR CROSS OUT OPTIONS.
 6-OWES ADDITIONAL FEES FOR UPDATED VALUE
 AND RADON FEES. PLEASE PAY ATTACHED
 RECEIPTS AND BRING PAID RECEIPTS.
 7-PROVIDE CERTIFICATION FOR TWO HR FIRE
 RATED CONCRETE BLOCK THAT COMPLIES W/
 SECTION 709.3 SBC 1997 ACCORDING TO
 THE EQUIVALENT THICKNESS.
 8-PROVIDE COMPLETE INFORMATION FOR STORM
 PANELS OR APPLY FOR A SEPARATE PERMIT.
  
  
  
  
 NOTES:
 -DRAWINGS AND COMMENTS TO BE FILED UNDER
 PERMIT #01091304.
 -THESE COMMENTS APPLY TO PERMIT #S:
 01091304, 01091306, 01091308, 01091312,
 01091314 AND 01091316.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-07-23 Cont ID  
Sent By btrobaug Date 2002-07-23 Time 10:05 Rev Time 0.00
Received By btrobaug Date 2002-07-23 Time 10:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-07 Cont ID  
Sent By btrobaug Date 2002-06-07 Time 15:36 Rev Time 0.00
Received By btrobaug Date 2002-06-07 Time 14:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-10-23 Cont ID  
Sent By dpalmer Date 2001-10-23 Time 07:26 Rev Time 0.00
Received By dpalmer Date 2001-10-23 Time 07:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-12-06 Cont ID  
Sent By mcarsill Date 2001-12-06 Time 17:11 Rev Time 0.00
Received By mcarsill Date 2001-12-06 Time 17:11 Sent To  
Notes
2001-12-06 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO,DURING AND AFTER CONSTRUCTION.
 2) BUILDING ADDRESSES REQUIRED.
 3) PORTABLE FIRE EXTINGUISHERS REQUIRED.
 4) ELECTRIC POWERED SMOKE DETECTORS
 REQUIRED.
 5) EGRESS WINDOWS TO COMPLY WITH
 BUILDING AND FIRE CODE REQUIREMENTS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-01-29 Cont ID  
Sent By pkrauss Date 2002-01-29 Time 13:12 Rev Time 0.35
Received By pkrauss Date 2002-01-29 Time 12:39 Sent To  
Notes
2002-01-29 00:00:00MECH REV PERMIT 01100037

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-10-20 Cont ID  
Sent By hmoser Date 2001-10-20 Time 08:40 Rev Time 0.33
Received By hmoser Date 2001-10-20 Time 08:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-11-30 Cont ID  
Sent By kstevens Date 2001-11-30 Time 18:15 Rev Time 0.33
Received By kstevens Date 2001-11-30 Time 18:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-17 Cont ID  
Sent By jleech Date 2001-10-17 Time 16:51 Rev Time 0.25
Received By jleech Date 2001-10-17 Time 16:51 Sent To  
Notes
2001-10-17 00:00:00DENIED;
 1.PAGE 1A & 2 GENERAL NOTES. CHANGE TO
 READ FHA 98 DESIGN MANUAL.
 2.MODEL 1527 L & R.M/B SHOWS 1'7" TO
 CENTER OF W/C AND IT SHOULD BE 1' 6"
 ALSO SHOW CLEAR FLOOR SPACE FOR LAV.
 PAGE 1A &1B.
 3.IN BATH 2 SHOW CLEAR FLOOR SPACE FOR
 W/C AND LAV. PAGE 1A &1B.
 4.MODEL 1409 M/B SHOWS 1'7" TO CENTER
 OF W/C AND IT SHOULD BE 1'6" ALSO
 SHOW CLEAR FLOOR SPACE FOR W/C AND
 LAV. PAGE 1A &1B.
 5.BATH 2 SHOWS 2'8" OPENING FOR W/C
 2'9" MIN. SPACE REQUIRED FOR W/C ALSO
 SHOW CLEAR FLOOR SPACE FOR W/C AND LAV
 PAGE 1A &1B.
 6.PAGE 2 RISER DIAGRAMS. MODEL 1527 &
 1409. SHOW VENT FOR OPT. L.T.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-10-09 Cont ID  
Sent By sgraham Date 2001-10-09 Time 14:12 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***