Plan Review Details - Permit 01091250
Plan Review Stops For Permit 01091250
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-10-30 Cont ID  
Sent By dpalmer Date 2001-10-30 Time 13:01 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-10-30 00:00:00OK PER BILL STAPLES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-10-02 Cont ID  
Sent By jwitmer Date 2001-10-02 Time 15:21 Rev Time 1.50
Received By jwitmer Date 2001-10-02 Time 15:21 Sent To  
Notes
2001-10-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: REQUIRED/
 CHANGE OF OCCUPANCY
 RESIDENTIAL TO
 BUSINESS
 OWNER: GAY CINQUE
 TEL: 835-1584
  
 1)- SBC AMENDMENTS 104.1.1 / 3401.2.2.
 CHANGE OF OCCUPANCY OF ANY EXISTING
 BUILDING OR STRUCTURE, THE BUILDING,
 ELECTRICAL, GAS, MECHANICAL & PLUMBING
 SYSTEMSSHALL BE MADE TO CONFORM TO THE
 INTENT OF THE TECHNICAL CODES AS
 REQUIRED BY THE BUILDING OFFICIAL.
  
 2)- SBC 3401.2.2.2.CHANGES IN OCCUPANCY
 OF A BUILDING NOW EXISTING OR HEREAFTER
 ERECTED SHALL NOT BE MADE UNTIL A RE-
 VISED CERTIFICATE OF OCCUPANCY HAS BEEN
 ISSUED. A DESIGN PROFESSIONAL WILL NEED
 TO CERTIFY THE EXISTING FLOOR SYSTEM
 FOR 50 LBS. LIVE LOAD DESIGNED FOR
 BUSINESS USE.
  
 3)- SBC 104.2.2. A PLOT PLAN SHALL BE
 NECESSARY TO INDICATE THE PARKING THAT
 WILL BE REQUIRED, HANDICAPPED PARKING,
 ACCESS ISLE AND A ACCESSIBLE ROUTE INTO
 THE STRUCTURE. THE BUILDING OFFICIAL
 SHALL DETERMINE THE EXTENT OF THE ACCESS
 IBILTY, IF THE 20 % DISPROPORTIONATE
 COST RULE IS IN EFFECT OR IF THE CHANGE
 OF OCCUPANCY WILL REQUIRE THE ENTIRE
 STRUCTURE TO BE CONSIDERED "NEW CONSTRUC
 TION".
 FL ACC CODE 4.1.6 THIS EDITION OF THE
 CODE DOES NOT APPLY TO BUILDINGS OR FA-
 CILITIES WHICH WERE IN EXISTANCE ON OCT.
 1, 1997 UNLESS: (I) THE BUIULDING, IS
 BEING CONVERTED FROM RESIDENTIAL TO
 NONRESIDENTIAL OR MIXED USE, AS DEFINED
 BY LOCAL LAW.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412
 THE BUILDING OFFICIAL SHALL BE OUT OF
 THE OFFICE UNTIL OCT.4/01. UPON ARRIVAL
 THIS MATTER WILL BE DISCUSSED & TO WHAT
 EXTENT THE TECHNICAL AS WELL AS THE
 ACCESSIBILITY CODE WILL NEED TO COMPLY.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-10-30 Cont ID  
Sent By dpalmer Date 2001-10-30 Time 13:02 Rev Time 0.00
Received By dpalmer Date 2001-10-30 Time 13:02 Sent To  
Notes
2001-10-30 00:00:00********** REVISION NEEDED ************
  
 1)NOTE: PLEASE NOTE THAT PLANS NEED TO
 SHOW ALL BRANCH CIRCUIT #`SAND
 CORRELATE WITH SUBMITTED PANEL SCHEDULES
 BEFORE FINAL.
  
 PLEASE SUBMIT FOR REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-10-23 Cont ID  
Sent By dpalmer Date 2001-10-23 Time 12:14 Rev Time 0.00
Received By dpalmer Date 2001-10-23 Time 12:14 Sent To  
Notes
2001-10-23 00:00:00******************UNSAT **************
  
 PLEASE NOTE THAT PLANS ARE BEING DENIED
 DUE TO THE REQ`MENTS FOR CHANGE OF USE
 TO COMMERCIAL 104.1.1. SEE COMMENTS
 FROMBLDG OFFICIAL.
  
 PLEASE NOTE THE FOLLOWING MINOR
 ELECTRICAL CHANGES NEEDED.
  
 1)NOTE: PLEASE NOTE ONE ROOM/OFFICE MISS
 ING OUTLETS?
  
 2)NOTE: PLEASE NOTE ALL CONTINOUS LOADS
 INCLUDING LIGHTING TO BE SHOWN AT 125%.
  
  
 PLEASE SUBMIT THESE MINOR CHANGES WHEN
 ALL OF THE OTHER ISSUES WITH ZONING,
 BLDG, PLUMB ETC ARE ADDRESSED.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-10-03 Cont ID  
Sent By dpalmer Date 2001-10-03 Time 19:02 Rev Time 0.00
Received By dpalmer Date 2001-10-03 Time 19:02 Sent To  
Notes
2001-10-03 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT PLANS WERE
 SUBMITTED CHANGING FROM RESIDENTIAL TO
 COMMERCIAL, PLEASE NOTE THAT LOAD
 CALCULATIONS NEED TO BE SHOWN FOR A
 OFFICE AND CONTINUOUS LOADS NEED TO BE
 SHOWN AT 125%. OUTLETS AT 180VA.EACH
  
 2)NOTE: PLEASE SHOW LOCATION OF PANEL
 ON FLOOR LAYOUT.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
  
 4)NOTE: PLEASE CLARIFY ANY COLD WATER
 AS PART OF GROUNDING ELECTRODE SYSTEM.
 250-50
  
 5)NOTE: PLEASE SHOW A/C LOCATIONS ON
 PLANS AND DISCONNECTS PER 440-11.
  
 6)NOTE: PLEASE SHOW WATER HEATER
 LOCATION.
  
 7)NOTE: PLEASE NOTE REQ`D EXITS LIGHTS
 AND EMERGENCY LIGHTS.
 ART 700
  
 PLEASE NOTE THAT IF HOUSE IS GOING TO
 REMAIN AS RESIDENTIAL THEN PLANS WOULD
 NEED TO REFLECT A SFR. W/ SD`S, KITCHEN
 LAUNDRY ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2001-10-30 Cont ID  
Sent By dpalmer Date 2001-10-30 Time 12:59 Rev Time 0.00
Received By dpalmer Date 2001-10-30 Time 12:59 Sent To  
Notes
2001-10-30 00:00:00OK TO PAASS FOR EXIT AND EM LTS.
 PER MIKE C.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-09-26 Cont ID  
Sent By mcarsill Date 2001-09-26 Time 13:23 Rev Time 0.00
Received By mcarsill Date 2001-09-26 Time 13:23 Sent To  
Notes
2001-09-26 00:00:001) SINCE THE BUILDING WAS RESIDENTIAL
 AND IS NOW PLANNED FOR BUSINESS
 OCCUPANCY, THE BUILDING SHALL COMPLY
 WITH ALL THE REQUIREMENTS FOR NEW
 BUSINESS "CHANGE OF USE".
 2) PLEASE INDICATE EXIT SIGNS AND
 EMERGENCY LIGHTING.
 3) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 4) PLEASE INDICATE LOCATIONS AND SIZES
 OF EXIT DOORS.
 5) IS THE BUILDING ONE OR TWO STORY.
 6) PLEASE INDICATE TYPES OF LOCKING
 DEVICES PLANNED FOR EXIT DOORS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop Z ZONING
Rev No 2 Status N Date 2001-10-30 Cont ID  
Sent By dpalmer Date 2001-10-30 Time 12:59 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2001-10-30 00:00:00OK TO ISSUE PER BILL STAPLES.

Review Stop Z ZONING
Rev No 1 Status F Date 2001-09-26 Cont ID  
Sent By sgraham Date 2001-09-26 Time 11:39 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-09-26 00:00:00FOR COMMERICAL USES, NEED 3-REG PARKING
 1-HC PARKING IN THE REAR OF BLDG