Plan Review Details - Permit 01091152
Plan Review Stops For Permit 01091152
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-11-01 Cont ID  
Sent By jwitmer Date 2001-11-01 Time 16:24 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-10-31 Cont ID  
Sent By jwitmer Date 2001-10-31 Time 07:21 Rev Time 1.25
Received By jwitmer Date 2001-10-31 Time 07:21 Sent To  
Notes
2001-10-31 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01091152
 2312 SPANISH WELLS
 SIERRA CONST
 TEL: (305) 216-4477
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- SHOW ELEVATIONS FOR THE HANDICAPPED
 ACCESIBLE ENTRANCE INTO THE SALES OFFICE
 SLOPE AND HANDRAILS.
 A) A NOTE ON THE COMMENT SHEET INDI-
 CATES THE TRAILER IS IN A PIT, THIS
 LOCATION IS IN A FLOOD ZONE"AO".
 B) THE CITY WILL REQUIRE A CUT SECTION
 FROM THE DESIGNER OF RECORD INDICAT-
 ING HOW THE SOILS AROUND THE TRAILER
 WILL CONFORM WITH SBC 2304.3.4 18"
 CLEARENCE FROM THE BOTTOM OF FLOOR
 TO GRADE.
 C) INDICATE HOW THE SOILS ARE TO KEPT
 AWAY FROM THE SIDES OF THE TRAILER
 AND STILL COMPLY WITH THE FL ACCES
 CODE.
 D) THIS SISTE IS IN A "AO" FLOOD ZONE,
 AN ELEVATION CERTIFICATE WILL BE RE-
 QUIRED BEFORE C.O. THIS ALSO
 INCLUDES THE SLAB HEIGTH OF THE
 A/C COMPRESSOR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-10-17 Cont ID  
Sent By hpiskura Date 2001-10-17 Time 11:13 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-10-17 00:00:00SEE COPY OF NOTES FROM PERMIT #01070198
 ATTACHED TO THIS APPLICATION

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-10-30 Cont ID  
Sent By dpalmer Date 2001-10-30 Time 21:10 Rev Time 0.00
Received By dpalmer Date 2001-10-30 Time 21:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-10-01 Cont ID  
Sent By dpalmer Date 2001-10-01 Time 23:11 Rev Time 0.00
Received By dpalmer Date 2001-10-01 Time 23:11 Sent To  
Notes
2001-10-01 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT AN ELECTRICAL
 PLAN FOR TRAILER WAS SUBMITTED. THIS
 TRAILER IS EXEMPT FROM ELECTRICAL PLAN
 REVIEW.
 PLEASE NOTE THAT, WHAT IS NEEDED IS AN
 ELECTRIAL RISER DIAGRAM SHOWING SERVICE
 AND TRAILER HOOK-UP.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-11-01 Cont ID  
Sent By jwitmer Date 2001-11-01 Time 16:25 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-10-01 Cont ID  
Sent By mcarsill Date 2001-10-01 Time 15:33 Rev Time 0.00
Received By mcarsill Date 2001-10-01 Time 15:33 Sent To  
Notes
2001-10-01 00:00:001) PLEASE PROVIDE ADDRESS FOR SALES
 TRAILER IN THE EVENT OF AN EMERGENCY.
 2) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO,DURING AND AFTER CONSTRUCTION.
 3) SMOKE DETECTORS REQUIRED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-11-01 Cont ID  
Sent By jwitmer Date 2001-11-01 Time 16:25 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-10-12 Cont ID  
Sent By kstevens Date 2001-10-12 Time 17:43 Rev Time 0.33
Received By kstevens Date 2001-10-12 Time 17:43 Sent To  
Notes
2001-10-12 00:00:00PASSED/PROVISO
  
 RPZ BACKFLOW REQUIRED ON WATER SERVICE.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-09-26 Cont ID  
Sent By sgraham Date 2001-09-26 Time 12:35 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***