Plan Review Stops For Permit 01091140 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2002-01-07 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2002-01-07 |
Time |
13:45 |
Rev Time |
0.25 |
Received By |
jgomez |
Date |
2002-01-07 |
Time |
13:45 |
Sent To |
|
|
Notes |
2002-01-07 00:00:00 | PRODUCT APPROVAL CHECKLIST: | | 1-FRENCH DOOR SITE SPECIFIC PRODUCT | | APPROVAL: | | A)MANUFACTURER'S ENGINEER TO PROVIDE | | ORIGINAL SIGNATURE AND OFFICE ADDRESS | | & PHONE NUMBER AS REQUIRED BY CHAPTER | | 471 FLORIDA STATUTES WHEN SUBMITTING | | DOCUMENTS FOR PUBLIC RECORDS. | | B)USE CITY SAMPLE (ATTACHED) WHEN | | SUBMITTING INFORMATION FOR SITE | | SPECIFIC PRODUCT APPROVAL. | | C)PROFESSIONAL ENGINEER OF RECORD NEED | | TO SIGN, SEAL & DATE THIS SPECIFIC | | PRODUCT APPROVAL FORM AS WELL. | | -INCLUDE ALL HIS INFORMATION AS REQ'D | | BY CHAPTER 471 FLORIDA STATUTES. | | -SPECIFY LOCATION. THIS IS A SITE | | SPECIFIC INSTALLATION. | | D)CLARIFY WHY THE 2X WOOD BUCK IS NOT | | CONSIDERED STRUCTURAL. SEE SECTION 4.2 | | OF PRODUCT APPROVAL INFO. SUBMITTED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2001-12-04 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2001-12-04 |
Time |
17:42 |
Rev Time |
1.00 |
Received By |
jgomez |
Date |
2001-12-04 |
Time |
17:42 |
Sent To |
|
|
Notes |
2001-12-04 00:00:00 | APPROVED WITH PROVISO: | | 1-FLOOD ZONE AO: NEED THE ELEVATION | | CERTIFICATE. | | 2-NEED ADDITIONAL SOIL BORINGS FOR EACH | | STRUCTURE AS RECOMMENDED ON THE PRE- | | LIMINARY SOIL TEST REPORT. | | 3-PROVIDE PRODUCT APPROVAL FOR FRENCH | | DOORS AS SHOWN ON PLANS IF OPTION | | IS SELECTED. | | 4-PROVIDE MANUFACTURER'S CERTIFICATION | | FOR TWO HR FIRE RATED CONCRETE BLOCK | | ACCORDING TO THE BLOCK'S EQUIVALENT | | THICKNESS AND AGGREGATES USED. SEE | | SECTION 709.3 SBC 1997. | | 5-PROVIDE COMPLETE INFORMATION FOR STORM | | PANELS UNDER A SEPARATE PERMIT. | | | | | | | | NOTES: | | -DRAWINGS TO BE FILED UNDER PERMIT # | | 01091140. | | -THESE COMMENTS APPLY TO PERMIT #S: | | 01091140, 01091144, 01091147, 01091148, | | 01091146 AND 01091143. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2001-10-17 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2001-10-17 |
Time |
18:43 |
Rev Time |
1.00 |
Received By |
jgomez |
Date |
2001-10-17 |
Time |
18:43 |
Sent To |
|
|
Notes |
2001-10-17 00:00:00 | CHECKLIST: | | 1-SEE COMMENTS BY PLUMBING. SAME COMMENT | | WAS ADDRESSED SEVERAL TIMES BEFORE. | | 2-NEED NOTICE OF COMMENCEMENT. | | 3-WILL NEED ADDITIONAL SOIL BORINGS FOR | | EACH STRUCTURE AS RECOMMENDED ON THE | | PRELIMINARY SOIL TEST REPORT. | | 4-PROVIDE PRODUCT APPROVAL FOR: | | A)GARAGE DOORS PRODUCT APPROVAL WAS | | DELETED FROM SBCCI. | | B)WINDOW MULLIONS. | | | | 5-CLEARLY INDICATE OPTIONS TO BE BUILT | | AND PROVIDE CORRESPONDING PRODUCT | | APPROVAL OR CROSS OUT SHEET. | | 6-OWES ADDITIONAL FEES FOR UPDATED | | VALUATION AND RADON FEES. PLEASE, PAY | | ATTACHED RECEIPTS. | | 7-PROVIDE CERTIFICATION FOR 2 HR FIRE | | RATED CONCRETE BLOCK USED TO SEPARATE | | TOWNHOUSES. SEE SEC. 709.3 SBC 1997. | | 8-PROVIDE COMPLETE INFORMATION FOR STORM | | PANELS OR APPLY FOR SEPARATE PERMIT. | | | | NOTES: | | -THESE COMMENTS APPLY TO PERMIT #S: | | 01091140, 01091144, 01091147, 01091148, | | 01091146 AND 01091143. | | -DRAWINGS TO BE FILED UNDER PERMIT # | | 01091140. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2002-03-25 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-03-25 |
Time |
15:21 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-03-25 |
Time |
14:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2001-10-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-10-10 |
Time |
07:15 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-10-10 |
Time |
07:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2001-10-16 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-10-16 |
Time |
15:42 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-10-16 |
Time |
15:41 |
Sent To |
|
|
Notes |
2001-10-16 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | TO,DURING AND AFTER CONSTRUCTION. | | 2) BUILDING ADDRESSES REQUIRED. | | 3) ELECTRIC POWERED SMOKE DETECTORS | | REQUIRED. | | 4) PORTABLE FIRE EXTINGUISHERS REQUIRED. | | 5) EGRESS WINDOWS TO COMPLY WITH | | BUILDING AND FIRE CODE REGULATIONS. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2002-03-08 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-03-08 |
Time |
15:29 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2002-03-08 |
Time |
15:20 |
Sent To |
|
|
Notes |
2002-03-08 00:00:00 | THIS SUBMITTAL WAS NOT A REVISION. | | APPROVED BY H. MOSER 10-3-01 PLANS WHERE | | NOT STAMPED.OKAY PER H. MOSER. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2001-10-03 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2001-10-03 |
Time |
20:05 |
Rev Time |
0.33 |
Received By |
hmoser |
Date |
2001-10-03 |
Time |
20:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2001-12-01 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-12-01 |
Time |
07:28 |
Rev Time |
0.33 |
Received By |
kstevens |
Date |
2001-12-01 |
Time |
07:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2001-11-05 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-11-05 |
Time |
17:15 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2001-11-05 |
Time |
17:15 |
Sent To |
|
|
Notes |
2001-11-05 00:00:00 | DENIED | | REFERENCE: SPC-94 - FHA AMEND 98 DESIGN | | MANUAL | | 1) PAGES 1, 1A, 1B MODEL 1527 (L)(R). | | M/BATH SHOWS 1'7" TO C/L OF W/C AND IT | | SHOULD BE 1'6". ALSO SHOW CLEAR FLOOR | | SPACE FOR LAV. | | 2) PAGES 1, 1A, 1B MODEL 1527 (L)(R). | | 2ND BATH SHOW CLEAR FLOOR SPACE FOR W/C | | AND LAV. | | 3) PAGES 1, 1A, 1B MODEL 1409 (L)(R). | | M/BATH SHOWS 1'7" TO C/L OF W/C AND IT | | SHOULD BE 1'6". ALSO SHOW CLEAR FLOOR | | SPACE FOR LAV. | | 4) PAGES 1, 1A, 1B MODEL 1409 (L)(R). | | 2ND BATH SHOWS 2'8" OPENING FOR W/C, AND | | MINIMUM OPENING REQUIRED IS 2'9". ALSO | | SHOW CLEAR FLOOR SPACE FOR W/C AND LAV. | | 5) PAGES 1, 1A, 1B MODEL 1357 (L)(R). | | M/BATH SHOWS 1'7" TO C/L OF W/C AND IT | | SHOULD BE 1'6". ALSO SHOW CLEAR FLOOR | | SPACE FOR LAV. | | 2ND BATH SHOW CLEAR FLOOR SPACE FOR W/C | | AND LAV. | | 6) PAGES 1, 1A, 1B GENERAL NOTES #11 - | | CHANGE TO READ FHA AMENDED 98 DESIGN | | MANUAL. | | 7) PAGE 2 MODELS 1409 (L)(R) AND 1527 | | (L)(R) PLUMBING RISERS. OPT LAUNDRY TRAY | | IS NOT VENTED PROPERLY. SHOW VENT FOR | | THESE FIXTURES. | | 8) CORRRECTIONS FOR SIGNED AND SEALED | | PLANS SHALL BE SIGNED AND SEALED ALSO. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-10-02 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-10-02 |
Time |
18:01 |
Rev Time |
1.00 |
Received By |
jleech |
Date |
2001-10-02 |
Time |
18:01 |
Sent To |
|
|
Notes |
2001-10-02 00:00:00 | PLUMBING DENIED; | | 1.FHA DIMENSIONS FOR W/C ARE NOT CORRECT | | 18" FROM TUB NOT 19". PLEASE MAKE | | CHANGES TO MASTER PLANS. | | 2.PAGE 2 SANITARY RISER DIAGRAM. OPT. | | L.T. REQUIRES A VENT. PLEASE MAKE | | CHANGES TO MASTER PLANS. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2001-10-02 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2001-10-02 |
Time |
14:41 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|