Plan Review Details - Permit 01091132
Plan Review Stops For Permit 01091132
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2002-01-07 Cont ID  
Sent By jgomez Date 2002-01-07 Time 14:13 Rev Time 0.25
Received By jgomez Date 2002-01-07 Time 14:12 Sent To  
Notes
2002-01-07 00:00:00PRODUCT APPROVAL CHECKLIST:
 1-FRENCH DOOR SITE SPECIFIC PRODUCT
 APPROVAL:
 A)MANUFACTURER'S ENGINEER TO PROVIDE
 ORIGINAL SIGNATURE AND OFFICE ADDRESS
 & PHONE NUMBER AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTES WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
 B)USE CITY SAMPLE (ATTACHED) WHEN
 SUBMITTING INFORMATION FOR SITE
 SPECIFIC PRODUCT APPROVAL.
 C)PROFESSIONAL ENGINEER OF RECORD NEED
 TO SIGN, SEAL & DATE THIS SPECIFIC
 PRODUCT APPROVAL FORM AS WELL.
 -INCLUDE ALL HIS INFORMATION AS REQ'D
 BY CHAPTER 471 FLORIDA STATUTES.
 -SPECIFY LOCATION. THIS IS A SITE
 SPECIFIC INSTALLATION.
 D)CLARIFY WHY THE 2X WOOD BUCK IS NOT
 CONSIDERED STRUCTURAL. SEE SECTION 4.2
 OF PRODUCT APPROVAL INFO. SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-12-05 Cont ID  
Sent By jgomez Date 2001-12-05 Time 17:21 Rev Time 1.00
Received By jgomez Date 2001-12-05 Time 17:21 Sent To  
Notes
2001-12-05 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE AO. NEED THE ELEVATION
 CERTIFICATE.
 2-NEED ADDITIONAL SOIL BORINGS FOR EACH
 STRUCTURE AS RECOMMENDED ON THE PRE-
 LIMINARY SOIL TEST REPORT.
 3-PROVIDE PRODUCT APPROVAL FOR FRENCH
 DOORS ASEMBLIES AS SHOWN ON PLANS IF
 OPTION SELECTED.
 4-PROVIDE MANUFACTURER'S CERTIFICATION
 FOR TWO HOUR FIRE RATED CONCRETE BLOCK
 ACCORDING TO THE BLOCK'S EQUIVALENT
 THICKNESS AND AGGREGATES USED. SEE
 SECTION 709.3 SBC 1997.
 5-PROVIE COMPLETE INFORMATION FOR STORM
 PANELS UNDER A SEPARATE PERMIT.
  
  
 NOTES:
 -DRAWINGS AND COMMENTS TO BE FILED UNDER
 PERMIT #01091132.
 -THESE COMMENTS APPLY TO PERMIT #S:
 01091132, 01091133, 01091134 AND
 01091138.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-10-24 Cont ID  
Sent By jgomez Date 2001-10-24 Time 18:16 Rev Time 1.00
Received By jgomez Date 2001-10-24 Time 17:28 Sent To  
Notes
2001-10-24 00:00:00CHECKLIST:
 1-SEE COMMENTS BY PLUMBING. CORRECT
 ORIGINAL DRAWINGS TO AVOID DELAYS.
 2-NEED NOTICE OF COMMENCEMENT.
 3-WILL NEED ADDITIONAL SOIL BORINGS FOR
 EACH STRUCTURE AS RECOMMENDED ON THE
 PRELIMINARY SOIL TEST REPORT.
 4-PROVIDE PRODUCT APPROVAL FOR:
 A)GARAGE DOORS PRODUCT APPROVAL WAS
 DELETED FROM SBCCI LISTING.
 B)WINDOW MULLIONS.
  
 5-CLEARLY INDICATE OPTIONS TO BE BUILT
 AND PROVIDE CORRESPONDING PRODUCT
 APPROVAL OR CROSS OUT OPTION'S SHEET.
 6-OWES ADDITIONAL FEES FOR UPDATED VALUE
 AND RADON FEES. PLEASE PAY ATTACHED
 RECEIPTS AND BRING PAID RECEIPTS.
 7-PROVIDE CERTIFICATION FOR TWO HR FIRE
 RATED CONCRETE BLOCK THAT COMPLIES
 WITH SECTION 709.3 SBC 1997 ACCORDING
 WITH THE EQUIVALENT THICKNESS.
 8-PROVIDE COMPLETE INFORMATION FOR STORM
 PANELS OR APPLY FOR SEPARATE PERMIT.
  
  
  
 NOTES:
 -DRAWINGS AND COMMENTS TO BE FILED UNDER
 PERMIT #01091132.
 -THESE COMMENTS APPLY TO PERMIT #S:
 01091132, 01091133, 01091134 AND
 01091138.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-02 Cont ID  
Sent By btrobaug Date 2002-05-02 Time 07:10 Rev Time 0.00
Received By btrobaug Date 2002-05-02 Time 06:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-10-10 Cont ID  
Sent By dpalmer Date 2001-10-10 Time 07:23 Rev Time 0.00
Received By dpalmer Date 2001-10-10 Time 07:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-10-17 Cont ID  
Sent By mcarsill Date 2001-10-17 Time 08:59 Rev Time 0.00
Received By mcarsill Date 2001-10-17 Time 08:59 Sent To  
Notes
2001-10-17 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO,DURING,AND AFTER CONSTRUCTION.
 2) BUILDING ADDRESSES REQUIRED.
 3) ELECTRIC POWERED SMOKE DETECTORS
 REQUIRED.
 4) PORTABLE FIRE EXTINGUISHERS REQUIRED.
 5) EGRESS WINDOWS TO COMPLY WITH
 BUILDING AND FIRE CODE REQUIREMENTS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-01-29 Cont ID  
Sent By pkrauss Date 2002-01-29 Time 14:06 Rev Time 0.35
Received By pkrauss Date 2002-01-29 Time 13:52 Sent To  
Notes
2002-01-29 00:00:00MECH REV PERMIT 01091163

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-10-04 Cont ID  
Sent By hmoser Date 2001-10-04 Time 17:30 Rev Time 0.33
Received By hmoser Date 2001-10-04 Time 17:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-12-01 Cont ID  
Sent By kstevens Date 2001-12-01 Time 06:14 Rev Time 0.33
Received By kstevens Date 2001-12-01 Time 06:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-02 Cont ID  
Sent By jleech Date 2001-10-02 Time 18:18 Rev Time 1.00
Received By jleech Date 2001-10-02 Time 18:18 Sent To  
Notes
2001-10-02 00:00:00PLUMBING DENIED;
 1.FHA DIMENSIONS FOR W/C ARE NOT CORRECT
 PLEASE MAKE CHANGES TO MASTER PLANS.
 2.PAGE 2 SANITARY RISER DIAGRAM. OPT.
 L.T. REQUIRES A VENT. PLEASE MAKE
 CHANGES TO MASTER PLAN.
 PLUMBING PLAN REVIEW BY;
 J LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 1 Status P Date 2001-10-02 Cont ID  
Sent By sgraham Date 2001-10-02 Time 14:36 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***