Plan Review Stops For Permit 01090984 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2001-09-24 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-09-24 |
Time |
08:43 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-09-24 |
Time |
08:43 |
Sent To |
|
|
Notes |
2001-09-24 00:00:00 | 1) AN APPROVED FIXED TEMPERATURE | | HEAT DETECTOR IS REQUIRED IN THE | | ELEVATOR EQUIPMENT ROOM. THIS DEVICE | | SHALL DISCONNECT THE POWER TO THE | | ELEVATOR PRIOR TO THE APPLICATION OF | | WATER. HEAT DETECTOR DOES NOT HAVE TO | | BE CONNECTED TO THE BUILDINGS FIRE ALARM | | SYSTEM. SYSTEM SHALL NOT AUTOMATICALLY | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
|