Plan Review Details - Permit 01090745
Plan Review Stops For Permit 01090745 |
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2001-09-24 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2001-09-24 |
Time |
16:19 |
Rev Time |
0.00 |
Received By |
mamini |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FS |
|
Rev No |
3 |
Status |
P |
Date |
2002-02-27 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-02-27 |
Time |
09:12 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-02-27 |
Time |
09:11 |
Sent To |
|
|
Notes |
2002-02-27 00:00:00 | A) THE FIRE DEPARTMENT CONNECTION SHALL | | BE PLACED IN AN AREA THAT IS | | ACCESSIBLE TO FIRE APPARATUS. ALSO THIS | | CONNECTION IS TO BE LOCATED WITHIN | | 150 FEET OF A FIRE HYDRANT. PLEASE | | VERIFY A SUITABLE LOCATION FOR THE | | FDC WITH A FIRE RESCUE REPRESENTATIVE | | FOR BUILDING # 3. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FS |
|
Rev No |
2 |
Status |
P |
Date |
2001-10-01 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-10-01 |
Time |
10:28 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-10-01 |
Time |
10:28 |
Sent To |
|
|
Notes |
2001-10-01 00:00:00 | 1) THE FIRE DEPARTMENT CONNECTION SHOWN | | ON SHEET FP3 FOR THIS THREE STORY | | BUILDING IS NOT CORRECT. THE FDC MUST | | BE FACED DIFFERENTLY AS THERE IS NO | | ACCESS TO THE LOCATION IT IS SHOWN. | | ALSO THIS DEVICE MUST BE WITHIN 150 | | FEET OF A FIRE HYDRANT. PLEASE SUBMIT | | A REVISION. | | 2) PLEASE BE ADVISED THAT THE STANDPIPE | | SYSTEM IN BUILDING THREE MUST PROVIDE | | 750 GALLONS PER MINUTE AT THE ROOF | | AT 65 PSI. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FS |
|
Rev No |
1 |
Status |
F |
Date |
2001-09-24 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-09-24 |
Time |
10:10 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-09-24 |
Time |
10:10 |
Sent To |
|
|
Notes |
2001-09-24 00:00:00 | 1) NO FIRE DEPARTMENT CONNECTION SHOWN. | | 2) CLUBHOUSE FIRE PROTECTION SHOWN. | | CLUBHOUSE FIRE SPRINKLER SYSTEM NOT | | PART OF THIS PERMIT AND SHOULD BE | | REMOVED FROM DRAWINGS. | | 3) ONLY ONE FLOOR AND ROOF FIRE | | PROTECTION SHOWN. IF THE FLOOR PLAN IS | | THE SAME IT SHOULD BE NOTED AS TYPICAL | | ON THE DRAWINGS FOR ALL THREE FLOORS. | | 4) PLANS ARE MISSING THE FOLLOWING | | A) POINT OF COMPASS | | B) CEILING CONSTRUCTION | | C) FULL HEIGHT CROSS SECTION | | D) LOCATION OF FIRE WALLS | | E) LOCATION OF PARTITIONS | | F) OCCUPANCY OF EACH ROOM OR AREA | | G) HANGER LOCATIONS | | H) NUMBER OF SPRINKLERS PER RISER, EACH | | FLOOR | | I) LOCATION OF ANY CONCEALED SPACES, | | ATTICS, CLOSETS. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2001-10-01 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-10-01 |
Time |
10:27 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-10-01 |
Time |
10:27 |
Sent To |
|
|
Notes |
|
|
|