Plan Review Details - Permit 01090741
Plan Review Stops For Permit 01090741
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-09-25 Cont ID  
Sent By mcarsill Date 2001-09-25 Time 11:02 Rev Time 0.00
Received By mcarsill Date 2001-09-25 Time 11:02 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 3 Status P Date 2002-02-27 Cont ID  
Sent By mcarsill Date 2002-02-27 Time 09:40 Rev Time 0.00
Received By mcarsill Date 2002-02-27 Time 09:40 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 2 Status P Date 2001-10-01 Cont ID  
Sent By mcarsill Date 2001-10-01 Time 13:22 Rev Time 0.00
Received By mcarsill Date 2001-10-01 Time 13:22 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 1 Status F Date 2001-09-25 Cont ID  
Sent By mcarsill Date 2001-09-25 Time 11:02 Rev Time 0.00
Received By mcarsill Date 2001-09-25 Time 11:02 Sent To  
Notes
2001-09-25 00:00:001) A NOTICE OF COMMENCEMENT IS REQUIRED
 PRIOR TO RECEIVING A PERMIT.
 2) NO FIRE DEPARTMENT CONNECTION SHOWN.
 3) ONLY ONE FLOOR AND ROOF FIRE
 PROTECTION SHOWN. IF THE FLOOR PLAN IS
 THE SAME IT SHOULD BE NOTED AS TYPICAL
 ON THE DRAWINGS.
 4) PLANS ARE MISSING THE FOLLOWING
 A) POINT OF COMPASS
 B) CEILING CONSTRUCTION
 C) FULL HEIGHT CROSS SECTION
 D) LOCATION OF FIRE WALLS
 E) LOCATION OF PARTITIONS
 F) OCCUPANCY OF EACH ROOM OR AREA
 G) HANGAR LOCATIONS
 H) NUMBER OF SPRINKLERS PER RISER, EACH
 FLOOR
 I) LOCATION OF ANY CONCEALED SPACES,
 ATTICS, CLOSETS.
 PLEASE HAVE ENGINEER PROVIDE A TITLE
 BLOCK.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-10-01 Cont ID  
Sent By mcarsill Date 2001-10-01 Time 13:21 Rev Time 0.00
Received By mcarsill Date 2001-10-01 Time 13:21 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved