Plan Review Details - Permit 01090574
Plan Review Stops For Permit 01090574
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-02-19 Cont ID  
Sent By hpiskura Date 2002-02-19 Time 16:04 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-01-03 Cont ID  
Sent By jwitmer Date 2002-01-03 Time 17:28 Rev Time 0.75
Received By hpiskura Date 2002-01-03 Time 17:28 Sent To  
Notes
2002-01-03 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01090574
 2957 AUSTRALIAN AV
 CITY OF WEST PALM BEACH
 CONT ALMAZON BROTHERS
 TEL 793-1712
  
 SBC = 1997 STANDARD BUILDING CODE
  
 1)- THE DOCK PLANS DO NOT DEPICT THE
 REQUIRED GUARDRAIL AS REQUIRED SBC SEC-
 TION 1015. THE EXCEPTION FOR RESIDENTIAL
 BOAT DOCKS DOES NOT APPLY FOR PUBLIC USE
  
 2)- SBC 104.2.2 ADDITIONAL INFORMATION
 REQUIRED, THE PLANS DO NOT INDICATE WHAT
 % OF THE 16"X16" CEMENT LOUVERS ARE
 SOLID, NOT KNOWING THE PER CENTAGE OF
 OPEN AREA PER VENT ENABLES THE DETERMINA
 TION OF COMPLIANCE WITH THE 3 SQ FT OR
 GREATER REQUIREMENT FOR VENTILATION REQU
 IRED FOR RESTROOMS PER SBC 1203.4.2.
  
 3)- THE PRODUCT APPROVAL FOR THE STAND-
 ING SEAM METAL ROOF IS MISSING SBC 1503.
 3.2 (110 MPH). SBCCI OR DADE COUNTY
 REPORTS REQUIRED, 2 COPIES.
  
 FLORIDA STATE STATUTE 489.113 (B) WILL
 REQUIRE A ROOFING CONTRACTOR TO PULL
 THE ROOFING PERMIT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-10-10 Cont ID  
Sent By hpiskura Date 2001-10-10 Time 12:51 Rev Time 0.00
Received By hpiskura Date   Time   Sent To Z
Notes
2001-10-10 00:00:00THE DOCK REQUIRES A GUARD RAIL IN
 ACCORDANCE WITH SBC 1015.
  
 ON SHEET C-3 OF 4 THE TWO ASSYMETRICAL
 PILINGS NEAR THE END OF THE DOCK DO NOT
 HAVE LOCATION DIMENSIONS.
  
 SHEET A3.0 PAGE 6 OF 8. SPECIFY THE
 SPACING OF THE #5 DOWEL/VERTICAL STEEL.
  
 ENSURE THAT THE TOILET ROOM LOUVERS
 PROVIDE THE 3 SQUARE FEET OR GREATER OF
 FREE AREA FOR VENTILATION REQUIRED BY
 SBC 1203.4.2.
  
  
  
 PLANS SUBMITTED FOR PUBLIC RECORD ARE
 REQUIRED TO HAVE THE EMBOSSED SEAL,
 DATE AND ORIGINAL SIGNATURE OF THE
 DESIGN PROFESSIONAL.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-02-19 Cont ID  
Sent By dpalmer Date 2002-02-19 Time 06:35 Rev Time 0.00
Received By dpalmer Date 2002-02-19 Time 06:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-01-03 Cont ID  
Sent By dpalmer Date 2002-01-03 Time 11:44 Rev Time 0.00
Received By dpalmer Date 2002-01-03 Time 11:44 Sent To  
Notes
2002-01-03 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT TWO DIFFERENT
 SETS OF PLANS WERE SUBMITTED FOR REVIEW,
 PLEASE NOTE IN ANY CASE, A MEANS OF
 DISCONNECT AT DETACHED STRUCTURE IS REQ`
 D. 225-31
 PLEASE NOTE TWO DIFFERENT PLANS ARE
 DONE BY TWO DIFF ENGINEERS.
 PLEASE SUBMIT ONLY TWO SETS FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-10-01 Cont ID  
Sent By dpalmer Date 2001-10-01 Time 18:45 Rev Time 0.00
Received By dpalmer Date 2001-10-01 Time 18:45 Sent To  
Notes
2001-10-01 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT ON ELECTRICAL
 RISER DIAGRAM SHOWS CONDUITS W/ 6-#12`S
 GOING TO BATH BLDG AND STORAGE BLDGS./
 PLEASE NOTE THAT ON EP1.0, BATH BLDG
 SHOWS A 60AMP DISCONNECT? PLEASE CLARIFY
 HOW THIS IS BEING FED BY 6-#12`S?
  
 2)NOTE: PLEASE NOTE THAT BATH/AND
 STORAGE BLDGS ELECTRICAL NEEDS TO BE ON
 ELECTRICAL PLANS. PLEASE SHOW MEANS OF
 DISCONNECT FOR EACH. PER 225-31-32.
  
 3)NOTE: PLEASE NOTE THAT PLANS ARE TO BE
 SIGNED,DATED AND SEALED BY THE ENGINEER
 OF RECORD PER 471.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-10-16 Cont ID  
Sent By mamini Date 2001-10-16 Time 16:00 Rev Time 1.00
Received By mamini Date 2001-10-16 Time 15:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-02-15 Cont ID  
Sent By mcarsill Date 2002-02-15 Time 11:54 Rev Time 0.00
Received By mcarsill Date 2002-02-15 Time 11:54 Sent To  
Notes
2002-02-15 00:00:001) PLEASE PROVIDE GUARDRAIL AT DOCK
 AS REQUIRED BY BUILDING PLAN REVIEWERS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-01-02 Cont ID  
Sent By mcarsill Date 2002-01-02 Time 12:20 Rev Time 0.00
Received By mcarsill Date 2002-01-02 Time 12:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-09-18 Cont ID  
Sent By mcarsill Date 2001-09-18 Time 12:38 Rev Time 0.00
Received By mcarsill Date 2001-09-18 Time 12:38 Sent To  
Notes
2001-09-18 00:00:001) PLANS NOT SIGNED AND SEALED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-10-10 Cont ID  
Sent By hpiskura Date 2001-10-10 Time 14:44 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-01-17 Cont ID  
Sent By pschmitz Date 2002-01-17 Time 14:32 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-01-17 00:00:00PROVISO: SEESHT-8. PES

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-05 Cont ID  
Sent By kstevens Date 2001-10-05 Time 11:37 Rev Time 1.00
Received By kstevens Date 2001-10-05 Time 11:36 Sent To  
Notes
2001-10-05 00:00:00DENIED
  
 1) PLEASE PROVIDE PLANS THAT SHOW DEMO
 AND RECONSTRUCTION OF THE BATHROOM AS
 REFERED TO ON PERMIT APPLICATION PER
 SPC-94 SEC 104.2
  
 2) PLEASE NOTE THAT ALL PLANS SHALL BE
 SIGNED, DATED AND SEALED BY ARCHITECT/
 ENGINEER OF RECORD. FS471.25
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-10-17 Cont ID  
Sent By hpiskura Date 2001-10-24 Time 10:22 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***