Plan Review Stops For Permit 01090574 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2002-02-19 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2002-02-19 |
Time |
16:04 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2002-01-03 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-01-03 |
Time |
17:28 |
Rev Time |
0.75 |
Received By |
hpiskura |
Date |
2002-01-03 |
Time |
17:28 |
Sent To |
|
|
Notes |
2002-01-03 00:00:00 | BUILDING PLAN REVIEW | | PERMIT # 01090574 | | 2957 AUSTRALIAN AV | | CITY OF WEST PALM BEACH | | CONT ALMAZON BROTHERS | | TEL 793-1712 | | | | SBC = 1997 STANDARD BUILDING CODE | | | | 1)- THE DOCK PLANS DO NOT DEPICT THE | | REQUIRED GUARDRAIL AS REQUIRED SBC SEC- | | TION 1015. THE EXCEPTION FOR RESIDENTIAL | | BOAT DOCKS DOES NOT APPLY FOR PUBLIC USE | | | | 2)- SBC 104.2.2 ADDITIONAL INFORMATION | | REQUIRED, THE PLANS DO NOT INDICATE WHAT | | % OF THE 16"X16" CEMENT LOUVERS ARE | | SOLID, NOT KNOWING THE PER CENTAGE OF | | OPEN AREA PER VENT ENABLES THE DETERMINA | | TION OF COMPLIANCE WITH THE 3 SQ FT OR | | GREATER REQUIREMENT FOR VENTILATION REQU | | IRED FOR RESTROOMS PER SBC 1203.4.2. | | | | 3)- THE PRODUCT APPROVAL FOR THE STAND- | | ING SEAM METAL ROOF IS MISSING SBC 1503. | | 3.2 (110 MPH). SBCCI OR DADE COUNTY | | REPORTS REQUIRED, 2 COPIES. | | | | FLORIDA STATE STATUTE 489.113 (B) WILL | | REQUIRE A ROOFING CONTRACTOR TO PULL | | THE ROOFING PERMIT. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561) 659-8096 X 8412 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2001-10-10 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2001-10-10 |
Time |
12:51 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
Z |
|
Notes |
2001-10-10 00:00:00 | THE DOCK REQUIRES A GUARD RAIL IN | | ACCORDANCE WITH SBC 1015. | | | | ON SHEET C-3 OF 4 THE TWO ASSYMETRICAL | | PILINGS NEAR THE END OF THE DOCK DO NOT | | HAVE LOCATION DIMENSIONS. | | | | SHEET A3.0 PAGE 6 OF 8. SPECIFY THE | | SPACING OF THE #5 DOWEL/VERTICAL STEEL. | | | | ENSURE THAT THE TOILET ROOM LOUVERS | | PROVIDE THE 3 SQUARE FEET OR GREATER OF | | FREE AREA FOR VENTILATION REQUIRED BY | | SBC 1203.4.2. | | | | | | | | PLANS SUBMITTED FOR PUBLIC RECORD ARE | | REQUIRED TO HAVE THE EMBOSSED SEAL, | | DATE AND ORIGINAL SIGNATURE OF THE | | DESIGN PROFESSIONAL. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2002-02-19 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-02-19 |
Time |
06:35 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-02-19 |
Time |
06:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2002-01-03 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-01-03 |
Time |
11:44 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-01-03 |
Time |
11:44 |
Sent To |
|
|
Notes |
2002-01-03 00:00:00 | ****************** UNSAT *************** | | | | 1)NOTE: PLEASE NOTE THAT TWO DIFFERENT | | SETS OF PLANS WERE SUBMITTED FOR REVIEW, | | PLEASE NOTE IN ANY CASE, A MEANS OF | | DISCONNECT AT DETACHED STRUCTURE IS REQ` | | D. 225-31 | | PLEASE NOTE TWO DIFFERENT PLANS ARE | | DONE BY TWO DIFF ENGINEERS. | | PLEASE SUBMIT ONLY TWO SETS FOR REVIEW. | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-10-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-10-01 |
Time |
18:45 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-10-01 |
Time |
18:45 |
Sent To |
|
|
Notes |
2001-10-01 00:00:00 | ************** UNSAT ************** | | | | 1)NOTE: PLEASE NOTE THAT ON ELECTRICAL | | RISER DIAGRAM SHOWS CONDUITS W/ 6-#12`S | | GOING TO BATH BLDG AND STORAGE BLDGS./ | | PLEASE NOTE THAT ON EP1.0, BATH BLDG | | SHOWS A 60AMP DISCONNECT? PLEASE CLARIFY | | HOW THIS IS BEING FED BY 6-#12`S? | | | | 2)NOTE: PLEASE NOTE THAT BATH/AND | | STORAGE BLDGS ELECTRICAL NEEDS TO BE ON | | ELECTRICAL PLANS. PLEASE SHOW MEANS OF | | DISCONNECT FOR EACH. PER 225-31-32. | | | | 3)NOTE: PLEASE NOTE THAT PLANS ARE TO BE | | SIGNED,DATED AND SEALED BY THE ENGINEER | | OF RECORD PER 471.025 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
P |
Date |
2001-10-16 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2001-10-16 |
Time |
16:00 |
Rev Time |
1.00 |
Received By |
mamini |
Date |
2001-10-16 |
Time |
15:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2002-02-15 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-02-15 |
Time |
11:54 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-02-15 |
Time |
11:54 |
Sent To |
|
|
Notes |
2002-02-15 00:00:00 | 1) PLEASE PROVIDE GUARDRAIL AT DOCK | | AS REQUIRED BY BUILDING PLAN REVIEWERS. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2002-01-02 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-01-02 |
Time |
12:20 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-01-02 |
Time |
12:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2001-09-18 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-09-18 |
Time |
12:38 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-09-18 |
Time |
12:38 |
Sent To |
|
|
Notes |
2001-09-18 00:00:00 | 1) PLANS NOT SIGNED AND SEALED. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2001-10-10 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2001-10-10 |
Time |
14:44 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2002-01-17 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2002-01-17 |
Time |
14:32 |
Rev Time |
1.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-01-17 00:00:00 | PROVISO: SEESHT-8. PES |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-10-05 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-10-05 |
Time |
11:37 |
Rev Time |
1.00 |
Received By |
kstevens |
Date |
2001-10-05 |
Time |
11:36 |
Sent To |
|
|
Notes |
2001-10-05 00:00:00 | DENIED | | | | 1) PLEASE PROVIDE PLANS THAT SHOW DEMO | | AND RECONSTRUCTION OF THE BATHROOM AS | | REFERED TO ON PERMIT APPLICATION PER | | SPC-94 SEC 104.2 | | | | 2) PLEASE NOTE THAT ALL PLANS SHALL BE | | SIGNED, DATED AND SEALED BY ARCHITECT/ | | ENGINEER OF RECORD. FS471.25 | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2001-10-17 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2001-10-24 |
Time |
10:22 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|