Plan Review Details - Permit 01090537
Plan Review Stops For Permit 01090537
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-10-29 Cont ID  
Sent By dpalmer Date 2001-10-29 Time 22:16 Rev Time 0.00
Received By dpalmer Date 2001-10-29 Time 22:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-09-28 Cont ID  
Sent By dpalmer Date 2001-09-28 Time 10:44 Rev Time 0.00
Received By dpalmer Date 2001-09-28 Time 10:44 Sent To  
Notes
2001-09-28 00:00:00**************** UNSAT *****************
  
  
 1)NOTE: PLEASE NOTE THAT OUTLET SPACING
 FOR BEDROOOM #3, DINING ROOM. 210-52
  
 2)NOTE: PLEASE NOTE, PLANS NEED TO BE
 CLARIFIED FOR GARAGE? PLEASE NOTE THAT
 OUTLET SPACING WILL NEED TO MEET 210-52
 FOR HABITABLE ROOM.
 PLEASE ALSO NOT EGRESS LIGHTING PER
 210-70
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-11-28 Cont ID  
Sent By pkrauss Date 2001-11-28 Time 12:00 Rev Time 0.35
Received By pkrauss Date 2001-11-28 Time 11:53 Sent To  
Notes
2001-11-28 00:00:00THIS IS NOT A REVISION...CHANGE OF
 CONTRACTOR...NEW MECH PERMIT 01110864.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-09-26 Cont ID  
Sent By hmoser Date 2001-09-26 Time 18:47 Rev Time 0.33
Received By hmoser Date 2001-09-26 Time 18:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-09-25 Cont ID  
Sent By jleech Date 2001-09-25 Time 19:36 Rev Time 0.33
Received By jleech Date 2001-09-25 Time 19:36 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-11-03 Cont ID  
Sent By rmcdouga Date 2001-11-03 Time 12:08 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-11-03 00:00:00************BUILDING PROVISO************
  
 1) PROVIDE AN ACCESSIBLE ROUTE COMPLYING
 WITH 4.3 OF THE FLORIDA ACCESSIBILITY
 CODE FOR BUILDING CONSTRUCTION FROM THE
 ACCESSIBLE PARKING SPACES TO AN
 ACCESSIBLE BUILDING ENTRANCE. 97 FL
 ACCESSIBILITY CODE SEC. 4.1.2(1) AND
 97SBC SEC. 1103.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-10-06 Cont ID  
Sent By rmcdouga Date 2001-10-06 Time 11:46 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-10-06 00:00:00*************BUILDING UNSAT*************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE 8050 HORIZONTAL SLIDING WINDOW
 INTHE MASTER BEDROOM MUST COMPLY WITH
 SEC.1005.4 OF THE 97 SBC FOR EMERGENCY
 EGRESS REQUIREMENTS. (MINIMUM NET CLEAR
 OPENING HEIGHT 24" AND WIDTH OF 20")
  
 3) ONE OF THE INTERIOR BEARING WALLS
 EXTENDS TO THE CENTER OF THE FRENCH
 DOORS AT THE STUDY. INDICATE ON THE
 PLANS THE SIZE OF THIS LOAD BEARING
 HEADER.
  
 4) THE ROOF SHEATHING AT GABLE ENDS IS
 REQUIRED TO BE NAILED WITH 8D COMMON
 NAILS AT 4"O.C. AT EDGES AND 6"O.C.
 INTERMEDIATE WITHIN FIVE FEET (5') OF
 THE ROOF EDGE INCLUDING OVERHANG.
  
 5) THE ENERGY CODE INCORRECTLY LISTS
 EXTERIOR WALLS AS WOOD FRAME WITH AN R
 VALUE OF 4.2. PLEASE CORRECT.
  
 6) TEMPORARY SALES OFFICE IN GARAGE OF
 MODEL MUST BE APPROVED BY THE PLANNING
 AND ZONING DEPARTMENT AND THE BUILDING
 OFFICIAL. YOU WILL BE REQUIRED TO SUB-
 MIT A PROPOSAL FOR REVIEW. THE FOLLOWING
 ITEMS MUST BE ADDRESSED. ADDITIONAL
 INFORMATION MAY BE REQUIRED AFTER REVIEW
 BY BUILDING OFFICIAL.
 A) A SURVEY SHOWING OFF STREET PARKING
 ON A NON-DUSTING SURFACE. ONE SPACE FOR
 EACH 350 SQ.FT. TO INCLUDE REQUIRED
 ACCESSIBLE PARKING.
 B) SALES OFFICE MUST MEET ACCESSIBILITY
 REQUIREMENTS INCLUDING ACCESSIBLE TOILET
 FACILITIES.
 C)A CONDITIONAL CERTIFICATE OF OCCUPANCY
 WILL BE REQUIRED BEFORE THE OFFICE CAN
 BE OPENED.
 THE FINAL C.O. FOR THE RESIDENCE WILL BE
 ISSUED AFTER THE TEMPORARY COMPONENTS
 HAVE BEEN REMOVED.
 D) YOU MUST SUBMIT A LETTER FROM ONE OF
 THE PRINCIPLES WITH THE COMPANY (SIGNED
 AND SEALED OR WITH CORPRATE SEAL) TO THE
 BUILDING OFFICIAL WITH YOUR REQUEST,
 INDICATING THE LENGTH OF TIME THIS
 CONDITION WILL EXIST AND THAT THE WALLS,
 A/C DROPS, ETC. WILL BE REMOVED AND THAT
 THE GARAGE DOOR WILL BE INSTALLED.
  
 7) TEMPORARY EXTERIOR WALL MUST MEET
 WINDLOAD REQUIREMENTS. PROVIDE A DETAIL
 OF THIS WALL INDICATING ATTACHMENT TO
 STRUCTURE.
  
 8) PROVIDE PRODUCT APPROVALS FOR FRENCH
 DOORS AND WINDOW.
  
 9) PROVIDE IMPACT PROTECTION FOR FRENCH
 DOORS AND WINDOW AT GARAGE.
  
 10) PROVIDE DETAIL OF TRAP FENCE AT
 GARAGE INDICATING TYPE OF CONSTRUCTION,
 METHOD OF ANCHORING, ETC.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-09-21 Cont ID  
Sent By sgraham Date 2001-09-21 Time 11:28 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***