Plan Review Details - Permit 01090437
Plan Review Stops For Permit 01090437
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-09-14 Cont ID  
Sent By pkrauss Date 2001-09-14 Time 09:58 Rev Time 0.40
Received By pkrauss Date 2001-09-14 Time 09:55 Sent To  
Notes
2001-09-14 00:00:00PROVISO - ATTIC ACCESS FOR AHU SHALL BE
 NO LESS THAT 22" X 36"CONTINUOUS TO
 EQUIPMENT, DISCONNECT, CONVENIENCE
 OUTLET, AND LIGHT ON EQUIPMENT SIDE
 COTROLLED BY A SWITCH AT ACCESS
 OPENING. AUXILIARY DRAIN PAN WITH
 OVERFLOW PROTECTION.ALL THE ABOVED
 ITEMS REQUIRED FOR ATTIC INSTALLATION.
  
 EXHAUST FANS NOT INIDICATED ON PLAN.
 SHOW COMPLIANCE WITH 1997 SMC 503.3.1,
 SHALL BE MECHANICALLY EXHAUSTED TO THE
 OUTDOORS OR HAVE WINDOWS WITH NO LESS
 THAN 3 SQ FT OF OPEN SPACE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.