Plan Review Details - Permit 01090332
Plan Review Stops For Permit 01090332
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-10-18 Cont ID  
Sent By jwitmer Date 2001-10-18 Time 16:29 Rev Time 2.00
Received By jwitmer Date 2001-10-18 Time 16:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-09-19 Cont ID  
Sent By jwitmer Date 2001-09-19 Time 07:34 Rev Time 1.00
Received By jwitmer Date 2001-09-19 Time 07:34 Sent To  
Notes
2001-09-19 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01090332
 1601 BELVEDERE RD./ #211
 SERVICO CENTRE ASSOCIATES, LTD.
 TEL: (561) 394-5200
 FAX: (561) 394-5498
  
 SBC= 1997 STANDARD BUILDING CODE
 "PLAN REVIEW"
 1)- SHEET #1 INDICATES THAT WOOD BUCKS
 WILL BE USED, SBC 604/ 609.2.1 TYPE I&
 TYPE II BUILDINGS REQUIRE NON-COMBUST-
 IBLE MATERIALS IN WALLS, BACKING, BUCKS
 ARE INCLUDED, FIRE RESISTANT TREATED
 WOOD IS ACCEPTED.
  
 2)- SHEET #3 GENERAL NOTES, NOTE #1,
 THIS BUILDING IS A TYPE I /OR TYPE II
 BUILDING APPROX. 16 STORIES HIGH.
  
 3)- SBC 1004.1.4. ARRANGEMENTS & NUMBER
 OF EXITS. WHERE 2 OR MORE EXITS OR EXIT
 ACCESS DOORS ARE REQUIRED, AT LEAST 2 OF
 THE EXIT DOORS SHALL BE PLACED A DIS-
 TAANCE APART EQUAL TO NOT LESS THAN ONE
 HALF THE LENGTH OF THE MAXIMUM DIAGONAL
 DIMENSION OF THE BUILDING OR AREA.
  
 4)_SBC TABLE 803.3 MISSING INFORMATION
 FOR MINIMUM INTERIOR FINISH CLASSIFICA-
 TION.
  
 5)- TYPE I TYPE II BUILDINGS ARE
 REQUIRED TO HAVE FIRE SPRINKLERS, PLANS
 FOR FIRE SPRINKLERS THERE LAYOUT ALL
 DEVICESTO BE INCLUDED BEFORE A BUILD-
 ING PERMIT CAN BE ISSUED.
  
 6)- FL ACCESSIBILITY CODE4.1.6.2.2.
 ALTERATIONA MADE TO PROVIDE AN ACCESS-
 IBLE PATH OF TRAVEL TO ALTERED AREAS
 SHALL BE DEEEMED DISPROPORTIONATE TO THE
 OVERALL ALTERATION WHEN THE COST EXCEEDS
 20 % OF THE CODT OF THE ALTERATION TO
 THE PRIMARY FUNCTION AREA.
  
 THE CONTRACTOR TO SHOW WHERE $4,000 WILL
 BE USED UP DATING THE AREA TO THE FL
 ACCESSIBILITY CODE, SHEET 3 NOTE 21 WILL
 QUALIFY AS PART OF THESE MONIES REQUIRED
 TO BE ALLOCATED.
 THE CONFRENCE ROOM DOOR DOESN'T MEET THE
 MANEUVERING CLEARENCES 4.13.6.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-09-18 Cont ID  
Sent By dpalmer Date 2001-09-18 Time 22:30 Rev Time 0.00
Received By dpalmer Date 2001-09-18 Time 22:30 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-10-03 Cont ID  
Sent By kstevens Date 2001-10-03 Time 18:30 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-10-18 Cont ID  
Sent By mcarsill Date 2001-10-18 Time 13:33 Rev Time 0.00
Received By mcarsill Date 2001-10-18 Time 13:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-09-11 Cont ID  
Sent By mcarsill Date 2001-09-11 Time 08:01 Rev Time 0.00
Received By mcarsill Date 2001-09-11 Time 08:01 Sent To  
Notes
2001-09-11 00:00:001) PLEASE INDICATE LOCATIONS OF ANY NEW
 OR EXISTING FIRE ALARM EQUIPMENT
 CONTAINED WITHIN TENANT SPACE.
 2) NO INTERIOR FINISH CLASSIFICATION
 PROVIDED WITH PLANS.
 3) ENSURE THAT DOORS FROM THE TENANT
 SPACE TO THE CORRIDOR ARE AT LEAST
 20 MINUTE FIRE RATED.
 4) PLEASE PROVIDE CEILING HEIGHTS FOR
 ALL AREAS WITHIN TENANT SPACE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-09-25 Cont ID  
Sent By pkrauss Date 2001-09-25 Time 10:31 Rev Time 0.40
Received By pkrauss Date 2001-09-25 Time 10:31 Sent To  
Notes
2001-09-25 00:00:00PROVISO:PRIOR TO CONNECTING TO ANY
 EXISTING DUCTWORK, CALL FOR
 AN INSPECTION.
  
 (ON PLAN)

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-10-18 Cont ID  
Sent By kstevens Date 2001-10-18 Time 09:24 Rev Time 0.33
Received By kstevens Date 2001-10-18 Time 09:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-03 Cont ID  
Sent By kstevens Date 2001-10-03 Time 17:48 Rev Time 0.25
Received By kstevens Date 2001-10-03 Time 18:01 Sent To  
Notes
2001-10-03 00:00:00DENIED
 REFERENCE FACBC-97
  
 BREAK ROOM DOES NOT COMPLY WITH FACBC-97
 SEC 4.2.3.
 BREAK ROOM SINK DOES NOT COMPLY WITH
 FACBC-97 4.24.2
 PLEASE INDICATE COMPLIENCE WITH FACBC-97
 SEC 4.1.6.2.2. SHOW HOW 20 PERCENT OVER
 CONTRACT COST IS ADDRESSED FOR ACCESSI-
 BILITY.
  
 REVIEW BY KEN STEVENS
 (561) 569-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-10-03 Cont ID  
Sent By kstevens Date 2001-10-03 Time 18:31 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***