Plan Review Details - Permit 01090319
Plan Review Stops For Permit 01090319
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-09-25 Cont ID  
Sent By lsmith Date 2001-09-25 Time 14:58 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-09-17 Cont ID  
Sent By lsmith Date 2001-09-17 Time 11:32 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-09-17 00:00:00NEED STATE STATUTES 515 FOR PROTECTION
 FROM HOUSE TO POOL AREA

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-09-24 Cont ID  
Sent By dpalmer Date 2001-09-24 Time 11:01 Rev Time 0.00
Received By dpalmer Date 2001-09-24 Time 11:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-09-17 Cont ID  
Sent By dpalmer Date 2001-09-17 Time 11:16 Rev Time 0.00
Received By dpalmer Date 2001-09-17 Time 11:16 Sent To  
Notes
2001-09-17 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE NOTE THAT HEAT PUMP IS
 NOT INCLUDED ON THE ELECTRICAL WIRING
 DIAGRAM.
  
 2)NOTE: PLEASE ALSO NOTE THAT NO LOAD
 CALCUALTIONS WERE SUBMITTED AND NOTHING
 SHOWING SIZE OF EXISTING SERVICE.
 PLEASE SUBMIT
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-09-20 Cont ID  
Sent By kstevens Date 2001-09-20 Time 13:44 Rev Time 0.33
Received By kstevens Date 2001-09-20 Time 13:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-09-13 Cont ID  
Sent By kstevens Date 2001-09-13 Time 18:34 Rev Time 1.00
Received By kstevens Date 2001-09-13 Time 18:34 Sent To  
Notes
2001-09-13 00:00:00DENIED
 REFERENCE: UNIFORM COUNTYWIDE SWIMMING
 POOL AND SPA CODE.
 1) ALL SUCTION LINES SHALL BE VALVED.
 SECTION 39
 2) POOL HEATER NOT SHOWN ON PIPING
 SCHEMATIC. PLEASE SHOW HOW IT WILL BE
 PIPED AT EQUIPMENT PAD.
 3) POOL LAYOUT PAGE, PLEASE SHOW PIPING
 FOR SHEAR DESCENT WATERFALL AND INDIC-
 ATE PIPE SIZE.
 4) SHOW PIPING TO 3RD INLET. NONE SHOWN.
 5) PAGE 4 OF SHEAR DESCENT WATERFALL
 INSTALLATION INSTRUCTIONS, REQUIRES
 A SEPARATE PUMP. PLEASE SHOW A DETAIL
 OF THAT PUMP AND THE VALVES INDICATED
 FOR THIS SYSTEM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-09-10 Cont ID  
Sent By sgraham Date 2001-09-10 Time 15:27 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***