Plan Review Stops For Permit 01090145 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2001-10-22 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2001-10-22 |
Time |
12:27 |
Rev Time |
1.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2001-09-18 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-09-18 |
Time |
17:40 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
2001-09-18 |
Time |
17:40 |
Sent To |
|
|
Notes |
2001-09-18 00:00:00 | BUILDING PLAN REVIEW | | PERMIT # 01090145 | | 700 S DIXIE / 205-208 | | GEORGE A RAY JR | | (561) 714-3740 | | | | SBC= 1997 STANDARD BUILDING CODE | | | | 1)- EGRESS REQUIREMENTS FAIL TO MEET | | SINGLE EGRESS REQUIREMENTS | | 1020.(2) OVER 3500 SQ FT | | 1020. (4) OVER THE 75' LIMIT COMMON PATH | | | | 1004.1.3 COMMON PATH OF TRAVEL SHALL NOT | | EXCEED 75'. | | | | 1004.1.4. WHERE 2 OR MORE EXITS OR EXIT | | ACCESS DOORS ARE REQUIRED, AT LEAST 2 | | OF THE EXIT DOORS SHALL BE PLACED A DIS- | | TANCE APART EQUAL TO NOT LESS THAN ONE | | HALF OF THE LENGTH OF THE MAXIMUM OVER- | | ALL DIAGONAL DIMENSION OF THE BUILDING | | OR AREA. | | | | 2)- SBC TABLE 803.3 MISSING IS THE | | MINIMUM FINISH CLASSIFCATION SCHEDULE. | | | | 3)- PLANS INDICATE THE BUILDING IS SPRIN | | KLERED, SPRINKLE PLANS WILL BE REQUIRED | | BEFORE THE ISSUANCE OF THE BUILDING | | PERMIT. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561) 659-8096 X 8412 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2001-11-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-11-13 |
Time |
07:56 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-11-13 |
Time |
07:56 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2001-10-29 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-10-29 |
Time |
12:09 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-10-29 |
Time |
12:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2001-10-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-10-10 |
Time |
20:15 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-10-10 |
Time |
20:15 |
Sent To |
|
|
Notes |
2001-10-10 00:00:00 | **************** UNSAT ************* | | | | 1)NOTE: PLEASE NOTE THAT PLANS ARE | | SIGNED AND SEALED BY AN ENGINEER, PLEASE | | NOTE THAT ALL CHANGES ON PLANS MUST | | EITHER BE INITIALED BY ENGINEER OR | | REPRINT PLAN AND HAVE HAVE PLANS SIGNED, | | DATED AND SEALED BY ENGINEER OF RECORD | | 471.025. | | | | 2)NOTE: PLEASE NOTE THAT BRANCH CIRCUIT | | #`S NEED TO CORRELATE WITH PANEL(S) AND | | PANEL SCHEDULES. WHICH CIRCUITS TO WHICH | | PANEL? PANEL "L" OR "LP-4" | | PLEASE CALRIFY. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. THIS WAS THE SAME NOTE FROM | | FIRST REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-09-18 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-09-18 |
Time |
18:35 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-09-18 |
Time |
18:35 |
Sent To |
|
|
Notes |
2001-09-18 00:00:00 | ************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE THAT ALL BRANCH | | CIRCUIT #`S ON PLANS THAT CORRELATE | | W/ PANEL SCHEDULES. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2001-10-19 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2001-10-19 |
Time |
08:51 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2001-10-09 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-10-09 |
Time |
12:10 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-10-09 |
Time |
12:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2001-09-10 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-09-10 |
Time |
15:52 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-09-10 |
Time |
15:52 |
Sent To |
|
|
Notes |
2001-09-10 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS PROVIDED | | WITH PLANS. | | 2) NO FIRE-ALARM EQUIPMENT SHOWN ON | | DRAWINGS. | | 3) NO INTERIOR FINISH CLASSIFICATION | | INFORMATION NOTED ON PLANS. | | 4) DOES THE EM REFERENCED ON THE PLANS | | INDICATE EMERGENCY LIGHTING. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2001-11-19 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-11-19 |
Time |
12:46 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2001-11-19 |
Time |
12:45 |
Sent To |
|
|
Notes |
2001-11-19 00:00:00 | MECH REV 01090230 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2001-10-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-11-13 |
Time |
07:58 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2001-10-15 |
Time |
13:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2001-09-27 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-09-27 |
Time |
09:54 |
Rev Time |
0.50 |
Received By |
pkrauss |
Date |
2001-09-27 |
Time |
09:54 |
Sent To |
|
|
Notes |
2001-09-27 00:00:00 | *******************DENIED*************** | | | | | | PLEASE PROVIDE THE FOLLOWING | | INFORMATION FOR REVIEW. | | | | 1.OUTSIDE AIR CALCULATIONS AS PER | | ASHRAE 62-89. | | | | 2.EXPLAIN HOW FRESH AIR IS BEING | | INTRODUCED TO SYSTEM.PLAN | | INDICATES OUTSIDE AIR SUPPLIED TO | | SUPPLY/STORAGE ROOM.PLEASE NOTE | | AIR SHALL BE DUCTED INTO AHU NOT | | A "FREE" RETURN INTO A STORAGE/ | | SUPPLY ROOM. | | | | 3.PROVIDE MAKE, MODEL, BTU OF EXISTING | | EQUIPMENT. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2001-10-21 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2001-10-21 |
Time |
08:11 |
Rev Time |
1.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-10-21 00:00:00 | PLUMBING PROVISO,SHT-1 FACBC-97,SINK. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-10-01 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-10-01 |
Time |
17:51 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2001-10-01 |
Time |
17:51 |
Sent To |
|
|
Notes |
2001-10-01 00:00:00 | DENIED | | REFERENCE: SPC-94 - FACBC-97 | | | | 1) PLEASE PROVIDE A SANITARY RISER DIA- | | GRAM SHOWING PIPE SIZE AND DEVELOPED | | LENGTH AND VENTING. SPC-94 SEC 104.2.1. | | | | 2) PLEASE PROVIDE DETAIL ON KITCHEN SINK | | AND SHOW COMPLIANCE WITH FACBC-97 SEC | | 4.24. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT. 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2001-10-22 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2001-10-22 |
Time |
12:27 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|