Plan Review Details - Permit 01090145
Plan Review Stops For Permit 01090145
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-10-22 Cont ID  
Sent By lmartine Date 2001-10-22 Time 12:27 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-09-18 Cont ID  
Sent By jwitmer Date 2001-09-18 Time 17:40 Rev Time 1.00
Received By jwitmer Date 2001-09-18 Time 17:40 Sent To  
Notes
2001-09-18 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01090145
 700 S DIXIE / 205-208
 GEORGE A RAY JR
 (561) 714-3740
  
 SBC= 1997 STANDARD BUILDING CODE
  
 1)- EGRESS REQUIREMENTS FAIL TO MEET
 SINGLE EGRESS REQUIREMENTS
 1020.(2) OVER 3500 SQ FT
 1020. (4) OVER THE 75' LIMIT COMMON PATH
  
 1004.1.3 COMMON PATH OF TRAVEL SHALL NOT
 EXCEED 75'.
  
 1004.1.4. WHERE 2 OR MORE EXITS OR EXIT
 ACCESS DOORS ARE REQUIRED, AT LEAST 2
 OF THE EXIT DOORS SHALL BE PLACED A DIS-
 TANCE APART EQUAL TO NOT LESS THAN ONE
 HALF OF THE LENGTH OF THE MAXIMUM OVER-
 ALL DIAGONAL DIMENSION OF THE BUILDING
 OR AREA.
  
 2)- SBC TABLE 803.3 MISSING IS THE
 MINIMUM FINISH CLASSIFCATION SCHEDULE.
  
 3)- PLANS INDICATE THE BUILDING IS SPRIN
 KLERED, SPRINKLE PLANS WILL BE REQUIRED
 BEFORE THE ISSUANCE OF THE BUILDING
 PERMIT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-11-13 Cont ID  
Sent By dpalmer Date 2001-11-13 Time 07:56 Rev Time 0.00
Received By dpalmer Date 2001-11-13 Time 07:56 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-10-29 Cont ID  
Sent By dpalmer Date 2001-10-29 Time 12:09 Rev Time 0.00
Received By dpalmer Date 2001-10-29 Time 12:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-10-10 Cont ID  
Sent By dpalmer Date 2001-10-10 Time 20:15 Rev Time 0.00
Received By dpalmer Date 2001-10-10 Time 20:15 Sent To  
Notes
2001-10-10 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE
 SIGNED AND SEALED BY AN ENGINEER, PLEASE
 NOTE THAT ALL CHANGES ON PLANS MUST
 EITHER BE INITIALED BY ENGINEER OR
 REPRINT PLAN AND HAVE HAVE PLANS SIGNED,
 DATED AND SEALED BY ENGINEER OF RECORD
 471.025.
  
 2)NOTE: PLEASE NOTE THAT BRANCH CIRCUIT
 #`S NEED TO CORRELATE WITH PANEL(S) AND
 PANEL SCHEDULES. WHICH CIRCUITS TO WHICH
 PANEL? PANEL "L" OR "LP-4"
 PLEASE CALRIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. THIS WAS THE SAME NOTE FROM
 FIRST REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-09-18 Cont ID  
Sent By dpalmer Date 2001-09-18 Time 18:35 Rev Time 0.00
Received By dpalmer Date 2001-09-18 Time 18:35 Sent To  
Notes
2001-09-18 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT ALL BRANCH
 CIRCUIT #`S ON PLANS THAT CORRELATE
 W/ PANEL SCHEDULES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-10-19 Cont ID  
Sent By lmartine Date 2001-10-19 Time 08:51 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-10-09 Cont ID  
Sent By mcarsill Date 2001-10-09 Time 12:10 Rev Time 0.00
Received By mcarsill Date 2001-10-09 Time 12:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-09-10 Cont ID  
Sent By mcarsill Date 2001-09-10 Time 15:52 Rev Time 0.00
Received By mcarsill Date 2001-09-10 Time 15:52 Sent To  
Notes
2001-09-10 00:00:001) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
 2) NO FIRE-ALARM EQUIPMENT SHOWN ON
 DRAWINGS.
 3) NO INTERIOR FINISH CLASSIFICATION
 INFORMATION NOTED ON PLANS.
 4) DOES THE EM REFERENCED ON THE PLANS
 INDICATE EMERGENCY LIGHTING.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-11-19 Cont ID  
Sent By pkrauss Date 2001-11-19 Time 12:46 Rev Time 0.40
Received By pkrauss Date 2001-11-19 Time 12:45 Sent To  
Notes
2001-11-19 00:00:00MECH REV 01090230

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-10-15 Cont ID  
Sent By dpalmer Date 2001-11-13 Time 07:58 Rev Time 0.40
Received By pkrauss Date 2001-10-15 Time 13:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-09-27 Cont ID  
Sent By pkrauss Date 2001-09-27 Time 09:54 Rev Time 0.50
Received By pkrauss Date 2001-09-27 Time 09:54 Sent To  
Notes
2001-09-27 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION FOR REVIEW.
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89.
  
 2.EXPLAIN HOW FRESH AIR IS BEING
 INTRODUCED TO SYSTEM.PLAN
 INDICATES OUTSIDE AIR SUPPLIED TO
 SUPPLY/STORAGE ROOM.PLEASE NOTE
 AIR SHALL BE DUCTED INTO AHU NOT
 A "FREE" RETURN INTO A STORAGE/
 SUPPLY ROOM.
  
 3.PROVIDE MAKE, MODEL, BTU OF EXISTING
 EQUIPMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-10-21 Cont ID  
Sent By pschmitz Date 2001-10-21 Time 08:11 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-10-21 00:00:00PLUMBING PROVISO,SHT-1 FACBC-97,SINK.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-01 Cont ID  
Sent By kstevens Date 2001-10-01 Time 17:51 Rev Time 0.50
Received By kstevens Date 2001-10-01 Time 17:51 Sent To  
Notes
2001-10-01 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PLEASE PROVIDE A SANITARY RISER DIA-
 GRAM SHOWING PIPE SIZE AND DEVELOPED
 LENGTH AND VENTING. SPC-94 SEC 104.2.1.
  
 2) PLEASE PROVIDE DETAIL ON KITCHEN SINK
 AND SHOW COMPLIANCE WITH FACBC-97 SEC
 4.24.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-10-22 Cont ID  
Sent By lmartine Date 2001-10-22 Time 12:27 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***