Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-11-05 Cont ID  
Sent By rmcdouga Date 2001-11-05 Time 15:36 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-11-05 00:00:00SEE STOP R 11-5-01 RM

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-10-02 Cont ID  
Sent By rmcdouga Date 2001-10-02 Time 08:18 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-10-02 00:00:00*************BUILDING UNSAT*************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE (2) COPIES OF RECENT SURVEY,
 SIGNED, SEALED AND DATED.
  
 4) PROVIDE SOIL TEST PER SEC. 1804.2.2
 OF CITY AMENDMENTS TO 1997 SBC.
  
 5) THE MEAN ROOF HEIGHT (AVERAGE HEIGHT
 OF HIGHEST ROOF ABOVE FINISH GRADE)
 LISTED ON THE DESIGN CERTIFICATION FORM
 IS NOT CORRECT IT SHOULD BE 17'AND BASIC
 VELOCITY PRESSURE WILL BE 25.6. PLEASE
 CORRECT.
  
 6) PLEASE REVIEW THE TYPICAL WALL
 SECTION ON SHEET A-4. THE CITY OF WPB
 AMENDMENTS TO THE 97 SBC REQUIRE FLOOR
 ELEVATION TO BE A MINIMUM OF 4 INCHES
 ABOVE THE FINISH GRADE.
  
 7) THE REFERENCE MARKS FOR DETAILS 9,10,
 11 AND 12 ON SHEET A-6 ARE INCORRECT.
 THESE DETAILS ARE LOCATED ON SHEET A-5.
 PLEASE CORRECT.
  
 8)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ROOFING
 - STORM PANELS
 - SH AND FIXED GLASS WINDOWS
 - DOUBLE OUTSWING DOORS
 - STRUCTURAL MULLIONS
 - SLIDING GLASS DOORS
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-09 Cont ID  
Sent By btrobaug Date 2002-05-09 Time 07:46 Rev Time 0.00
Received By btrobaug Date 2002-05-09 Time 07:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-09-11 Cont ID  
Sent By dpalmer Date 2001-09-11 Time 16:07 Rev Time 0.00
Received By dpalmer Date 2001-09-11 Time 16:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-09-06 Cont ID  
Sent By hmoser Date 2001-09-06 Time 17:45 Rev Time 0.33
Received By hmoser Date 2001-09-06 Time 17:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-02-28 Cont ID  
Sent By kstevens Date 2002-02-28 Time 15:56 Rev Time 0.50
Received By kstevens Date 2002-02-28 Time 15:56 Sent To  
Notes
2002-02-28 00:00:00REVISIONS OK - SANT RISER DIAGRAM

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-09-06 Cont ID  
Sent By jleech Date 2001-09-06 Time 18:50 Rev Time 0.33
Received By jleech Date 2001-09-06 Time 18:50 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2001-12-27 Cont ID  
Sent By rmcdouga Date 2001-12-27 Time 10:10 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-12-27 00:00:00REVISIONS (A-5 & A-6) AND TRUSSES
 DENIED
  
 1) DETAIL 9 ON A-5 STATES (2) 5/8" DIA.
 THRU- BOLTS EACH GIRDER AND INDICATES
 (2) TWO MEMBER GIRDER TRUSSES JOINED IN
 THE STEEL COLUMN SEAT. GIRDER SG-1 IS
 (1) TWO MEMBER GIRDER TRUSS WITH THE
 STEEL COLUMN SEAT LOCATED AT AN
 INTERMEADIATE POINT OF ITS SPAN.
 THEREFORE, THE 4 THRU-BOLTS INDICATED
 WILL BE LOCATED IN THE 2X6 WEB OF THE
 GIRDER TRUSSES. PLEASE REVIEW THE
 SPECIFIED BOLT SPACING OF THE STEEL
 COLUMN SEAT AND REVISE IF REQUIRED.
  
 2) THERE ARE NO CONNECTORS INDICATED ON
 SHEET A-6 FOR THE HJ7C OR HJ7 TRUSSES.
 PLEASE CORRECT.
  
 3) THE UPLIFT FOR TRUSS H1 (1608#)
 EXCEEDS THE CAPACITY OF THE (2) TC-3S
 (721# EA.) SPECIFIED.
  
 4) TRUSSES H2,H5,AND T1 EXCEED UPLIFT
 CAPACITIES OF SPECIFIED CONNECTORS.
  
 5) TRUSS CJ6A (UPLIFT 468#) EXCEEDS THE
 CAPACITY OF THE SPECIFIED TC1 CONNECTOR
 (417#).
  
 6) TRUSS M3 (UPLIFT 504#) EXCEEDS THE
 CAPACITY OF TC-1 (417#).
  
 7) TRUSS M3A (UPLIFT 1503#) EXCEEDS THE
 CAPACITY OF TC-8 (1410#).
  
 8) TRUSS GR1 (UPLIFT 977# @ JOINT 12)
 EXCEEDS THE CAPACITY OF TC-3 (721#).
  
 9) TRUSS S4 (UPLIFT 1500#) EXCEEDS THE
 CAPACITY OF TC-8 (1410#).
  
 10) TRUSS S8 (UPLIFT 784#) EXCEEDS THE
 CAPACITY OF TC-3 (721#).
  
 11) THERE IS NO TRUSS CONNECTOR GIVEN
 ON REVISED SHEET A-6 FOR TRUSS GR6 WITH
 UPLIFT 971# @ JOINT 14.
  
 THE UPLIFT CAPACITIES OF THE CONNECTORS
 MUST MEET OR EXCEED THE CALCULATED
 UPLIFTS OF THE TRUSSES. PLEASE REVIEW
 AND CORRECT ALL ITEMS LISTED.
 PLEASE CALL IF YOU HAVE ANY QUESTIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2001-11-28 Cont ID  
Sent By rmcdouga Date 2001-11-28 Time 12:16 Rev Time 0.50
Received By rmcdouga Date   Time   Sent To  
Notes
2001-11-28 00:00:00REVISION FOR LINTELS OK 11-28-01

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2001-11-21 Cont ID  
Sent By rmcdouga Date 2001-11-21 Time 09:44 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-11-26 00:00:00TRUSSES
 DENIED
  
 1) NO CONNECTOR IS INDICATED ON SHEET
 A-6 FOR TRUSS HJ7 (786# UPLIFT). THERE
 ARE SEVERAL OTHER HIP TRUSSES WITH NO
 CONNECTORS INDICATED.
  
 2) THE TRUSS ENGINEER IS IMPROPERLY
 SIGNING AND SEALING COPIES OF ANOTHER
 ENGINEER'S DRAWINGS (ROOF VALLEY DETAIL,
 PIGGY-BACK CONNECTION DETAIL, LATERAL
 BRACE DETAIL, STANDARD FALSE BOTTOM
 DETAIL, ETC.) THE CRITERIA SITED IS ALSO
 INCORRECTLY GIVEN AS TPI-92 &SSBC-91.
 SHOULD BE TPI 1-95 AND SBC-97.
  
 3) THE UPLIFT FOR TRUSS H1 (1608#)
 EXCEEDS THE CONNECTOR (TC-8, 1410#)
 DESIGN CAPACITY.
  
 4) TRUSS H2 EXCEEDS CONNECTOR RATING.
  
 5) TRUSS H5 EXCEEDS CONNECTOR RATING.
  
 6) TRUSS T1 EXCEEDS CONNECTOR RATING.
  
 7) THE PLANS DO NOT CORRESPOND WITH THE
 TRUSS LAYOUT FOR TRUSSES S8 THROUGH S11.
  
 8) NO UPLIFT VALUES ARE LISTED ON THE
 TRUSS DRAWINGS FOR TRUSSES S4,S5,S6 AND
 S7.
  
 9) TRUSS CJ6A EXCEEDS CAPACITY OF
 SPECIFIED CONNECTOR.
  
 10) TRUSS M3 EXCEEDS CONNECTOR RATING.
  
 11) TRUSS M3A EXCEEDS CONNECTOR RATING.
  
 12) TRUSS S14 EXCEEDS CONNECTOR RATING.
  
 13) TRUSS SG1 (UPLIFT 6871#) EXCEEDS
 UPLIFT OF 4225# GIVEN ON SHEET A-6 FOR
 STEEL COLUMN.
  
 14) MOST OF THE OTHER TRUSSES' UPLIFTS
 ALSO EXCEED THE SPECIFIED CONNECTORS
 LISTED CAPACITIES.
 PLEASE REVIEW ALL TRUSS CONNECTORS AND
 UPLIFT VALUES FOR ALL TRUSSES AND
 PROVIDE REVISED TRUSS CONNECTOR SCHEDULE
 AND/OR ROOF FRAMING PLAN (A-6). PLEASE
 NOTE THAT WHEN TWO OR MORE CONNECTORS
 ARE LOCATED WITHIN 8" OF EACH OTHER IN
 A CONCRETE BEAM THE CAPACITY VALUES ARE
 REDUCED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2001-11-05 Cont ID  
Sent By rmcdouga Date 2001-11-05 Time 13:20 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-11-05 00:00:00************BUILDING PROVISO************
  
 1) STRUCTURE IS LOCATED IN AN "A0" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL
 BE REQUIRED.
  
 2)PROVIDE SITE SPECIFIC PRODUCT APPROVAL
 SUBMITTAL FORMS THAT ARE SIGNED, SEALED
 AND DATED BY THE ENGINEER CERTIFYING THE
 COMPONENT AND THE DESIGNER OF RECORD FOR
 THE STRUCTURE APPROVING THE PRODUCT FOR
 USE IN THEIR STRUCTURE. THE DRAWINGS
 SUBMITTED FOR THE SINGLE HUNG WINDOWS
 AND WINDOW MULLIONS WERE MISSING THESE
 FORMS.
  
 3) THE PRODUCT APPROVAL SUBMITTAL FORMS
 FOR THE SLIDING GLASS DOORS MUST BE
 SEALED BY THE DESIGNER OF RECORD AND THE
 ENGINEER, IN ADDITION TO THE DATE,
 SIGNATURE AND SEAL, SHALL LEGIBLY
 INDICATE THEIR NAME, ADDRESS AND NUMBER
 ON EACH DOCUMENT. 61 G15- 23.002 FAC
  
 3) THE PRODUCT APPROVAL SUBMITTAL FORMS
 FOR THE OUTSWING EXTERIOR DOORS MUST BE
 SEALED BY THE DESIGNER OF RECORD. THE
 WET SIGNATURE OF THE ENGINEER IS
 REQUIRED. A COPY OR SIGNATURE STAMP IS
 NOT ACCEPTABLE.
  
 4) PROVIDE SOIL TEST PER SEC. 1804.2.2
 OF CITY AMENDMENTS TO 1997 SBC.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-10-24 Cont ID  
Sent By sgraham Date 2001-10-24 Time 10:13 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***