Plan Review Details - Permit 01081498
Plan Review Stops For Permit 01081498
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-09-14 Cont ID  
Sent By hpiskura Date 2001-09-14 Time 08:19 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-09-10 Cont ID  
Sent By dpalmer Date 2001-09-10 Time 21:42 Rev Time 0.00
Received By dpalmer Date 2001-09-10 Time 21:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-09-04 Cont ID  
Sent By mcarsill Date 2001-09-04 Time 12:15 Rev Time 0.00
Received By mcarsill Date 2001-09-04 Time 12:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-10-19 Cont ID  
Sent By pkrauss Date 2001-10-19 Time 10:11 Rev Time 0.30
Received By pkrauss Date 2001-10-19 Time 10:07 Sent To  
Notes
2001-10-19 00:00:00SEE COMMENTS FROM 9-12-01 PHK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status C Date 2001-09-12 Cont ID  
Sent By ndenmark Date 2001-09-12 Time 15:10 Rev Time 0.33
Received By ndenmark Date 2001-09-12 Time 15:10 Sent To  
Notes
2001-09-12 00:00:00PROVISO:
 OVERFLOW PROTECTION REQUIRED BY FLOAT
 SWITCH OR DRAIN TO CONSPIQUOUS LOCATION.
  
 DUCT OUTSIDE AIR TO VICINITY OF RETURN
 AIR OF UNIT TO ASSURE REQUIRED CFM OF
 OUTSIDE AIR

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-10-18 Cont ID  
Sent By kstevens Date 2001-10-18 Time 11:39 Rev Time 0.33
Received By kstevens Date 2001-10-18 Time 11:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-09-10 Cont ID  
Sent By kstevens Date 2001-09-10 Time 13:05 Rev Time 0.50
Received By kstevens Date 2001-09-10 Time 13:04 Sent To  
Notes
2001-09-10 00:00:00DENIED
  
 REFERENCE: SPC-94 - FACBC-97
  
 1) PAGE 1, SINK TO COMPLY WITH FACBC-97
 SECT. 2.24. PLEASE SUBMIT DETAIL TO SHOW
 COMPLIANCE FOR THIS SINK.
  
 2) PAGE 8. AIR CHAMBER TO COMPLY WITH
 SPC-94 SECTIONS 607.8.2 & 607.8.3, ACC-
 ESSABLE AND RECHARGABLE. IF WATER HAMMER
 ARRESTOR IS USED IT SHALL COMPLY WITH
 MANUFACTURE'S INSTALLATION INSTRUCTIONS
 AND WH-PDI 201.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-10-12 Cont ID  
Sent By lsmith Date 2001-10-12 Time 14:41 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***