Plan Review Details - Permit 01081470
Plan Review Stops For Permit 01081470
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-09-28 Cont ID  
Sent By jgomez Date 2001-09-28 Time 19:43 Rev Time 0.50
Received By jgomez Date 2001-09-28 Time 19:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-09-06 Cont ID  
Sent By jgomez Date 2001-09-06 Time 16:03 Rev Time 1.00
Received By jgomez Date 2001-09-06 Time 19:17 Sent To  
Notes
2001-08-31 00:00:00CHECKLIST:
 1-PROVIDE COMPLETE CALCULATIONS SHOWING
 ALL DESIGN LOADS AND DESIGN CRITERIA
 ASSUMPTIONS.
 -BE SPECIFIC: USE SBC 1997 FOR LOADS
 CONSIDERATIONS.
 2-THERE IS NO INFORMATION REGARDING THE
 FOOTINGS FOR THE NEW COLUMNS.
 -WHAT ARE THE DESIGN ASSUMPTIONS? SIZE
 OF FOOTINGS? OFF-SET LOADING?
 -ARE EXISTING FOOTINGS ADEQUATE TO
 CARRY THE ADDITIONAL LOAD? SPECIFY
 SIZES.
 3-HOW MANY STORIES ARE CONSIDERED IN
 THIS BUILDING?

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2001-09-10 Cont ID  
Sent By mcarsill Date 2001-09-10 Time 12:37 Rev Time 0.00
Received By mcarsill Date 2001-09-10 Time 12:37 Sent To  
Notes
***NONE***