Plan Review Details - Permit 01081040
Plan Review Stops For Permit 01081040
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-08-27 Cont ID  
Sent By lmartine Date 2001-08-27 Time 07:28 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2001-08-31 Cont ID  
Sent By dpalmer Date 2001-08-31 Time 09:16 Rev Time 0.00
Received By dpalmer Date 2001-08-31 Time 09:15 Sent To  
Notes
2001-08-31 00:00:00ELECTRICAL WAS PULLED OUT PER LAND
 STEWARTSHIP CO.REQUEST.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-24 Cont ID  
Sent By dpalmer Date 2001-08-24 Time 11:26 Rev Time 0.00
Received By dpalmer Date 2001-08-24 Time 11:26 Sent To  
Notes
2001-08-24 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT PLANS SHOW
 AN ELEC PANEL AND CONTROL PANEL, BUT
 NO DETAIL FOR SIZE, FEEDS, ETC ETC.
 PLEASE SUBMIT AND ELECTRICAL RISER
 DIAGRAM.
 PLEASE SHOWING GROUNDING ELECTRODE
 SYSTEM.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-08-24 Cont ID  
Sent By mamini Date 2001-08-24 Time 16:10 Rev Time 0.00
Received By mamini Date 2001-08-24 Time 16:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-09-04 Cont ID  
Sent By mcarsill Date 2001-09-04 Time 10:53 Rev Time 0.00
Received By mcarsill Date 2001-09-04 Time 10:53 Sent To  
Notes
2001-09-04 00:00:001) AN APPROVED OPENING OF AT LEAST
 20 FEET IN CLEAR WIDTH IS TO BE
 PROVIDED FOR FIRE RESCUE ACCESS IN THE
 FUTURE. THIS OPENING IS TO BE PERMITTED
 THRU CONSTRUCTION SERVICES AND WILL
 PROVIDE AN ADEQUATE OPENING FOR ACCESS.
  
 APPROVED PROVISO:
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-27 Cont ID  
Sent By mcarsill Date 2001-08-27 Time 10:03 Rev Time 0.00
Received By mcarsill Date 2001-08-27 Time 10:03 Sent To  
Notes
2001-08-27 00:00:001) ENTRANCE IS NOT WIDE ENOUGH FOR
 FIRE AND PARAMEDICAL EQUIPMENT. PLEASE
 BE ADVISED THAT AT LEAST 20' IN CLEAR
 WIDTH IS TO BE PROVIDED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-08-24 Cont ID  
Sent By kstevens Date 2001-08-24 Time 13:34 Rev Time 0.33
Received By kstevens Date 2001-08-24 Time 13:34 Sent To  
Notes
2001-08-24 00:00:00PROVISO..
  
 RAIN SENSOR REQUIRED AT PUMP STATION -
 IRRIGATION PERMIT REQUIRED.
  
 ANY MORE INFORMATION PLEASE CONTACT
 KEN STEVENS (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-08-23 Cont ID  
Sent By sgraham Date 2001-08-23 Time 13:35 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***