Plan Review Details - Permit 01080991
Plan Review Stops For Permit 01080991
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-09-13 Cont ID  
Sent By hpiskura Date 2001-09-13 Time 09:13 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-10-09 Cont ID  
Sent By dpalmer Date 2001-10-09 Time 17:26 Rev Time 0.00
Received By dpalmer Date 2001-10-09 Time 17:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-09-24 Cont ID  
Sent By dpalmer Date 2001-08-30 Time 15:57 Rev Time 0.00
Received By dpalmer Date 2001-08-30 Time 15:57 Sent To  
Notes
2001-08-30 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT ALL BRANCH
 CIRCUIT #`S ARE TO BE SHOWN ON PLANS AND
 CORRELATE WITH SUBMITTED PANEL SCHEDULES
  
  
 2)NOTE: PLEASE NOTE, WHAT IS THE SIZE OF
 EXISTING MAIN AND LOAD? PLANS SHOW
 ADDING NEW PANEL "B". PLEASE CLARFIY
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATINGS WERE SHOWN
 FOR PANELS BUT NOT FOR MAINS.
  
 4)NOTE: PLEASE NOTE CLEARENCES ON PLANS
 FOR DISCONNECT SHOWN FOR AHU #2.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-09-13 Cont ID  
Sent By hpiskura Date 2001-09-13 Time 09:13 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-08-20 Cont ID  
Sent By mcarsill Date 2001-08-20 Time 16:59 Rev Time 0.00
Received By mcarsill Date 2001-08-20 Time 16:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-09-13 Cont ID  
Sent By hpiskura Date 2001-09-13 Time 09:13 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-10-26 Cont ID  
Sent By kstevens Date 2001-10-26 Time 17:40 Rev Time 0.50
Received By kstevens Date 2001-10-26 Time 17:40 Sent To  
Notes
2001-10-26 00:00:00PASSED/PROVISO
  
 1) CONDENSATE EXISTING. INSPECTOR TO SEE
 IF IT MEETS CODE. AS BUILTS REVISION TO
 FOLLOW FOR 2ND ROUGH INSPECTION.
  
 2) WATER LINES EXISTING. INSPECTOR TO
 SEE IF THEY MEET CODE. NEW WATER LINES
 WILL HAVE WATER HAMMER ARRESTORS PLACED
 NEAR FIXTURES. RISER DIAGRAM AS BUILTS
 TO BE SUBMITTED FOR 2ND ROUGH.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-10-23 Cont ID  
Sent By kstevens Date 2001-10-23 Time 10:53 Rev Time 1.25
Received By kstevens Date 2001-10-23 Time 10:53 Sent To  
Notes
2001-10-23 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) FULL SETS OF PLANS REQUIRED. PAGE A-2
 NOT INCLUDED IN RESUBMITED SET, AND DEMO
 PAGES NEED TO BE INSERTED. PLEASE SUBMIT
 FULL SETS FOR REVIEW.
 2) PAGE A-1, RM 111. DOOR OUT OF ROOM
 SO AS NOT TO SWING INTO TURNING RADIUS.
 FACBC-97 4.22.3
 3) PAGE A-1 LUNCH ROOM. CLEAR FLOOR
 SPACE FOR PARALLEL, FIXTURE MUST CENTER
 ON CLEAR FLOOR SPACE. SINK ONLY 18" INTO
 CLEAR FLOOR SPACE. FRONTAL APPROACH IS
 REQUIRED. PLEASE SHOW DETAIL AND SHOW
 COMPLIANCE WITH ALL DETAILS OF SEC 4.24
 4) PLEASE SHOW WATER RISER DIAGRAM AS
 REQUESTED IN PREVIOUS PLAN REVIEW. NOTE
 #7 IN PLUMBING NOTES ON PAGE E-1 CALLS
 FOR AIR CHAMBERS, BUT NOTE BY SANITARY
 RISER CALLS FOR AIR HAMMER ARRESTORS. IF
 WATER HAMMER ARRESTORS ARE USED PLEASE
 NOTE IN NOTE #7 AND SHOW THEM IN WATER
 RISER DIAGRAM. PLACEMENT AND SIZE SHALL
 BE PER MANUFACTURES INSTALLATION INSTRU-
 CTIONS AND WH-PDI 201. PLACEMENT SHALL
 BE CLOSE TO FIXTURE NOT AT TOP OF DROP.
 5) PAGE E-1 NOTE #4. FROM PREVIOUS RE-
 VIEW SHOW CONDENSATE SYSTEM SO PLUMBING
 CONTRACTOR CAN INSTALL. SHOW TERMINATION
 OF CONDENSATE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-27 Cont ID  
Sent By jleech Date 2001-08-27 Time 17:34 Rev Time 1.50
Received By jleech Date 2001-08-27 Time 17:34 Sent To  
Notes
2001-08-27 00:00:00DENIED;
 1.NEW HANDICAP BATHROOM #104. DOOR SHALL
 BE DIAGONAL TO THE WATER CLOSET. FACBC
 4.17.3.
 2.LUNCH ROOM. SHOW CLEAR FLOOR SPACE FOR
 SINK FACBC 4.24.5.
 3.SHOW WATER RISER DIAGRAM. SIZE ALL
 PIPE. SHOW LOCATION OF AIR HAMMER
 ARRESTERS AND SIZE PER. MANUFACTORS
 RECOMMENDATIONS. SPC 104.1.2.
 4.SANITARY RISER DIAGRAM. PIPE UNDER
 SLAB SHALL BE MINIMUM OF TWE INCH.
 SPC 714.4.
 5.PLUMBING NOTE #4. SHOW CONDENSATE
 SYSTEM SO PLUMBING CONTRACTOR KNOWS
 HOW TO INSTALL. SHOW WHERE CONDENSATE
 TERMINATES.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369

Review Stop Z ZONING
Rev No 1 Status N Date 2001-09-13 Cont ID  
Sent By hpiskura Date 2001-09-13 Time 09:14 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***