Plan Review Details - Permit 01080699
Plan Review Stops For Permit 01080699
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-10-01 Cont ID  
Sent By mcarsill Date 2001-10-01 Time 13:46 Rev Time 0.00
Received By mcarsill Date 2001-10-01 Time 13:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-16 Cont ID  
Sent By mcarsill Date 2001-08-16 Time 14:21 Rev Time 0.00
Received By mcarsill Date 2001-08-16 Time 14:21 Sent To  
Notes
2001-08-16 00:00:001) THE EXISTING UNDERGROUND 500 GALLON
 FUEL TANK IS TO BE REMOVED IN
 ACCORDANCE WITH NFPA 30.
 2) NO CUT SHEETS OR PRODUCT APPROVALS
 PROVIDED FOR NEW ABOVEGROUND FUEL
 TANK. PLEASE PROVIDE PRODUCT APPROVALS
 FOR TANK.
 3) NO INFORMATION PROVIDED REGARDING
 IDENTIFICATION OR WARNING LABELS
 PROVIDED FOR TANK.
 4) PLEASE INDICATE DISTANCES FROM THE
 BUILDING TO THE RELOCATED DAY TANK AND
 THE NEW ABOVEGROUND FUEL TANK.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-10-04 Cont ID  
Sent By pkrauss Date 2001-10-04 Time 07:35 Rev Time 0.30
Received By pkrauss Date 2001-10-04 Time 07:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-20 Cont ID  
Sent By pkrauss Date 2001-08-20 Time 11:20 Rev Time 0.35
Received By pkrauss Date 2001-08-20 Time 11:20 Sent To  
Notes
2001-08-20 00:00:00*******************DENIED***************
  
  
 SEE FIRE DEPT COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.