Plan Review Stops For Permit 01080613 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2002-01-15 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2002-01-15 |
Time |
07:49 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-01-15 00:00:00 | PROVISO: RAMP TO COMPLY WITH FL ACC CODE | | FOR ALL PROVISIONS TOP & BOTTOM LANDINGS | | CLEARANCE AT ENTRY DOOR, IF RISE OVER | | 6", RAILINGS BOTH SIDES.SEE FL ACC CODE | | SHEETS ATTACHED TO PLANS.JW. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2001-11-28 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-11-28 |
Time |
07:24 |
Rev Time |
1.25 |
Received By |
jwitmer |
Date |
2001-11-28 |
Time |
07:23 |
Sent To |
|
|
Notes |
2001-11-28 00:00:00 | BUILDING PLAN REVIEW | | PERMIT# 01080613 | | 1320 HENRIETTA | | REVISION OCT 2001 | | CONT: COMPLETE PROPERTY MAN. | | TEL: 252-8372 | | | | 1)- STATE REQQUIREMENTS FOR PRE-CONSTRUC | | TION SOIL TREATMENT FOR TTERMITES.STUCCO | | IS TO STOP 6" ABOVE GRADE TO LEAVE AN | | EXTERIOR VERTICAL BARRIER. | | 2)- AT THE ENTRY TO THE LAUNDRY A 8" VER | | TICAL STEP IS SHOWN, FAIR HOUSING ACT | | ANSI A117.1.4.5 GROUND AND FLOOR SURFACE | | TREATMENTS. INCLUDES WALKWAYS FOR ALL | | COMMON ELEMENTS, & RAMPS. | | 3)- SHOW LOCATION OF PROPOSED LAUNDRY | | PLOT PLAN OR SURVEY. | | 4)- SBC1606.2.6.2 PRODUCT APPROVAL FOR | | ENTRY DOOR. | | 5)- SBC 1707.5 CLAY & CEMENT TILE ROOF- | | ING SHALL BE REQUIRE PRODUCT TESTING FOR | | 110 MPH WIND ZONE. SBCCI OR DADE COUNTY. | | BUILDING PLAN REVIEW | | JIM WITMER | | (561)659-8096X8412 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2001-10-16 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2001-10-16 |
Time |
08:28 |
Rev Time |
0.75 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-10-16 00:00:00 | ADD TRUSSES OVR EXISTING FLAT ROOF. | | ROOFER TO APPLY FOR SEPARATE ROOF PERMIT | | FOR S TILE |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2001-09-07 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2001-09-07 |
Time |
08:42 |
Rev Time |
1.00 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-09-07 00:00:00 | CONTRACTOR TO APPLY FOR SEPARATE ROOF | | & DRIVEWAY PERMITS FOR WORK DESCRIBED IN | | SCOPE OF WORK. | | IMPACT WINDOWS TO BE INSTALLED IN ALL | | WINDOW OPENINGS. | | | | SEE SCOPE OF WORK ON PAGE 2 | | | | ANY QUESTIONS CALL LEA SMITH | | 659-8096 EXT. 8394 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
7 |
Status |
P |
Date |
2002-01-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-01-14 |
Time |
19:07 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-01-14 |
Time |
19:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
F |
Date |
2002-01-08 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-01-08 |
Time |
17:42 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-01-08 |
Time |
17:41 |
Sent To |
|
|
Notes |
2002-01-08 00:00:00 | ************** UNSAT ****************** | | | | 1)NOTE: PLEASE NOTE, PLANS STILL NEED TO | | CORRELATE. | | PLEASE NOTE, 300A FUSES ARE SHOWN ON | | RISER AND 350A FUSES SHOWN ON SCHEDULE? | | PLEASE CLARIFY/ | | | | 2)NOTE: PLEASE NOTE THAT NOW A NEW SERVI | | CE IS BEING SUBMITTED FOR REVIEW AND | | THERE ARE NEW COMMENTS. | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 4)NOTE: PLEASENOTE LOAD IS SHOWN | | LARGER THAN 300A OCP. | | | | 5)NOTE: PLEASE NOTE LOAD CALCULATIONS | | FOR EACH UNIT IS NOT SHOWN? PLEASE SHOW. | | PLEASE CALL. | | | | 6)NOTE: PLEASE PROVIDE LAYOUT FOR UNITS | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
F |
Date |
2001-12-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-12-05 |
Time |
20:58 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-12-05 |
Time |
20:58 |
Sent To |
|
|
Notes |
2001-12-05 00:00:00 | **************** UNSAT *********** | | | | 1)NOTE: PLEASE SUBMIT A COMNPLETE SET | | OF ELECTRICAL PLANS BY THE ARCH/ENG OF | | RECORD. A REVISION WAS SUBMITTED BY | | THE ELECTRICAL CONTRACTOR LESS THAN A | | WEEK AGO SHOWING A COMPLETELY DIFERENT | | ELECTRICALSERVICE. | | | | 2)NOTE: PLEASE NOTE THAT NEW SERVICE | | SHOWN FOR LAUNDRY ALONG IS NOT PERMITTED | | UNLESS THERE IS A TWO HOUR SEPARATION | | BETWEEN EXISTING AND NEW. | | | | 3)NOTE: PLEASE NOTE GROUPING OF DISC`S | | 230-72 | | | | | | PLEASE SUBMIT NEW PLANS SHOWING COMPLETE | | ELECTRICAL. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2001-11-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-11-30 |
Time |
15:29 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-11-30 |
Time |
15:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2001-11-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-11-20 |
Time |
21:44 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-11-20 |
Time |
21:44 |
Sent To |
|
|
Notes |
2001-11-20 00:00:00 | **************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE THAT PLANS ARE | | SHOWING NEW SUB-PANEL AND NO INFORMATION | | ON WHERE? HOW? PANEL IS BEING FED? | | LOAD CALCULATIONS FOR LOADS BEING ADDED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANYQUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2001-08-31 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-08-31 |
Time |
13:02 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-08-31 |
Time |
13:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-08-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-08-21 |
Time |
18:29 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-08-21 |
Time |
18:29 |
Sent To |
|
|
Notes |
2001-08-21 00:00:00 | **************** UNSAT ***************** | | | | 1)NOTE: PLEASE NOTE THAT NOT ENOUGH | | INFORMATION WAS SUBMITTED FOR REVIEW. | | PLEASE NOTE THAT PERMIT APPLICATIONS AND | | PLANS/ MENTIONS NEW A/C UNITS BEING | | ADDED.? | | PLEASE SHOW LOCATIONS AND LAYOUT FOR | | ALL NEW ELECTRICAL DEVICES AND FIXTURE | | LOCATIONS ON A FLOOR LAYOUT. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2001-09-07 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2001-09-07 |
Time |
08:42 |
Rev Time |
0.00 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
F |
Date |
2001-12-13 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-12-13 |
Time |
12:32 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-12-13 |
Time |
12:32 |
Sent To |
|
|
Notes |
2001-12-13 00:00:00 | 1) NEW LAUNDRY ROOM IS TO BE AT LEAST | | ONE HOUR FIRE RATED AS PER NFPA 101, | | THE LIFE SAFETY CODE, 1985 EDITION, | | SECTION 19-3.2.1 WHICH REQUIRES | | "EVERY HAZARDOUS AREA SHALL BE | | SEPARATED FROM OTHER PARTS OF THE | | BUILDING BY CONSTRUCTION HAVING A | | FIRE RESISTANCE RATING OF AT LEAST | | ONE HOUR AND OPENINGS BE PROTECTED | | BY 3/4 FIRE DOORS. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2001-11-21 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-11-21 |
Time |
10:49 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-11-21 |
Time |
10:49 |
Sent To |
|
|
Notes |
2001-11-21 00:00:00 | 1) MORE DETAILS REQUIRED TO COMPLETE | | PLAN REVIEW. PLEASE INDICATE TYPE OF | | OCCUPANCY, AND OTHER DETAILS REQUIRED | | TO DO REVIEW. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
N |
Date |
2001-09-07 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2001-09-07 |
Time |
08:42 |
Rev Time |
0.00 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2001-12-11 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-12-11 |
Time |
13:57 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2001-12-11 |
Time |
13:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
F |
Date |
2001-11-28 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-11-28 |
Time |
08:06 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2001-11-28 |
Time |
08:06 |
Sent To |
|
|
Notes |
2001-11-28 00:00:00 | ********************DENIED************** | | | | | | PLEASE PROVIDE DETAIL OF DRYER VENTS. | | ONLY ONE VENT INDICATED ON PLAN, TWO | | DRYERS ARE SHOWN IN THE LAUNDRY ROOM. | | | | PLEASE INDICATE IF DRYERS ARE COMMERCIAL | | OR RESIDENTIAL.PROVIDE MANUFACTURER | | SUBMITTAL DATA. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2001-11-27 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-11-27 |
Time |
10:07 |
Rev Time |
0.50 |
Received By |
pkrauss |
Date |
2001-11-27 |
Time |
09:54 |
Sent To |
|
|
Notes |
2001-11-27 00:00:00 | CHANGED P-TAC UNITS TO 1.5 TON SPLIT | | UNIT.NANCY DID PRE-INSPECTION | | ACCORDING TO CONTRACTOR (TIM CURRAN) |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2001-09-04 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2001-09-04 |
Time |
10:47 |
Rev Time |
0.25 |
Received By |
ndenmark |
Date |
2001-09-04 |
Time |
10:46 |
Sent To |
|
|
Notes |
2001-09-04 00:00:00 | REPLACEMENT OF A/C W/ PTAC UNITS |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2001-08-23 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-08-23 |
Time |
12:18 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2001-08-23 |
Time |
12:18 |
Sent To |
|
|
Notes |
2001-08-23 00:00:00 | *******************DENIED*************** | | | | | | INSUFFICIENT INFORMATION FOR MECHANICAL | | REVIEW.PLEASE PROVIDE MANUFACTURER | | INFORMATION ON AC UNITS BEING INSTALLED | | ANDPLANS INDICATING LOCATION OF AC | | UNITS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2002-01-02 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-01-02 |
Time |
18:41 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2002-01-02 |
Time |
18:41 |
Sent To |
|
|
Notes |
2002-01-02 00:00:00 | REVISION APPROVED |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2001-11-20 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-11-20 |
Time |
21:21 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2001-11-20 |
Time |
21:21 |
Sent To |
|
|
Notes |
2001-11-20 00:00:00 | REVISION DENIED | | REFERENCE: SPC-94 | | | | 1) FLOOR DRAIN REQUIRED IN WASHING FAC- | | ILITIES PER SPC SEC 409.4.5 MINIMUM 3" | | WITH TRAP PRIMER. | | | | 2) 3" VENT THRU ROOF REQUIRED ON EACH | | BLDG DRAIN PER SPC SEC 904.3.1. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2001-08-16 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-08-16 |
Time |
19:08 |
Rev Time |
0.50 |
Received By |
jleech |
Date |
2001-08-16 |
Time |
19:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2001-11-19 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2001-11-19 |
Time |
12:20 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-11-19 00:00:00 | NEED SITE PLAN TO SHOW OF NEW LAUNDRY |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2001-09-07 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2001-09-07 |
Time |
08:42 |
Rev Time |
0.00 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|