Plan Review Details - Permit 01080613
Plan Review Stops For Permit 01080613
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-01-15 Cont ID  
Sent By jwitmer Date 2002-01-15 Time 07:49 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-01-15 00:00:00PROVISO: RAMP TO COMPLY WITH FL ACC CODE
 FOR ALL PROVISIONS TOP & BOTTOM LANDINGS
 CLEARANCE AT ENTRY DOOR, IF RISE OVER
 6", RAILINGS BOTH SIDES.SEE FL ACC CODE
 SHEETS ATTACHED TO PLANS.JW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-11-28 Cont ID  
Sent By jwitmer Date 2001-11-28 Time 07:24 Rev Time 1.25
Received By jwitmer Date 2001-11-28 Time 07:23 Sent To  
Notes
2001-11-28 00:00:00BUILDING PLAN REVIEW
 PERMIT# 01080613
 1320 HENRIETTA
 REVISION OCT 2001
 CONT: COMPLETE PROPERTY MAN.
 TEL: 252-8372
  
 1)- STATE REQQUIREMENTS FOR PRE-CONSTRUC
 TION SOIL TREATMENT FOR TTERMITES.STUCCO
 IS TO STOP 6" ABOVE GRADE TO LEAVE AN
 EXTERIOR VERTICAL BARRIER.
 2)- AT THE ENTRY TO THE LAUNDRY A 8" VER
 TICAL STEP IS SHOWN, FAIR HOUSING ACT
 ANSI A117.1.4.5 GROUND AND FLOOR SURFACE
 TREATMENTS. INCLUDES WALKWAYS FOR ALL
 COMMON ELEMENTS, & RAMPS.
 3)- SHOW LOCATION OF PROPOSED LAUNDRY
 PLOT PLAN OR SURVEY.
 4)- SBC1606.2.6.2 PRODUCT APPROVAL FOR
 ENTRY DOOR.
 5)- SBC 1707.5 CLAY & CEMENT TILE ROOF-
 ING SHALL BE REQUIRE PRODUCT TESTING FOR
 110 MPH WIND ZONE. SBCCI OR DADE COUNTY.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-10-16 Cont ID  
Sent By lsmith Date 2001-10-16 Time 08:28 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
2001-10-16 00:00:00ADD TRUSSES OVR EXISTING FLAT ROOF.
 ROOFER TO APPLY FOR SEPARATE ROOF PERMIT
 FOR S TILE

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-09-07 Cont ID  
Sent By lsmith Date 2001-09-07 Time 08:42 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2001-09-07 00:00:00CONTRACTOR TO APPLY FOR SEPARATE ROOF
 & DRIVEWAY PERMITS FOR WORK DESCRIBED IN
 SCOPE OF WORK.
 IMPACT WINDOWS TO BE INSTALLED IN ALL
 WINDOW OPENINGS.
  
 SEE SCOPE OF WORK ON PAGE 2
  
 ANY QUESTIONS CALL LEA SMITH
 659-8096 EXT. 8394

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2002-01-14 Cont ID  
Sent By dpalmer Date 2002-01-14 Time 19:07 Rev Time 0.00
Received By dpalmer Date 2002-01-14 Time 19:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2002-01-08 Cont ID  
Sent By dpalmer Date 2002-01-08 Time 17:42 Rev Time 0.00
Received By dpalmer Date 2002-01-08 Time 17:41 Sent To  
Notes
2002-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE NOTE, PLANS STILL NEED TO
 CORRELATE.
 PLEASE NOTE, 300A FUSES ARE SHOWN ON
 RISER AND 350A FUSES SHOWN ON SCHEDULE?
 PLEASE CLARIFY/
  
 2)NOTE: PLEASE NOTE THAT NOW A NEW SERVI
 CE IS BEING SUBMITTED FOR REVIEW AND
 THERE ARE NEW COMMENTS.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4)NOTE: PLEASENOTE LOAD IS SHOWN
 LARGER THAN 300A OCP.
  
 5)NOTE: PLEASE NOTE LOAD CALCULATIONS
 FOR EACH UNIT IS NOT SHOWN? PLEASE SHOW.
 PLEASE CALL.
  
 6)NOTE: PLEASE PROVIDE LAYOUT FOR UNITS
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2001-12-05 Cont ID  
Sent By dpalmer Date 2001-12-05 Time 20:58 Rev Time 0.00
Received By dpalmer Date 2001-12-05 Time 20:58 Sent To  
Notes
2001-12-05 00:00:00**************** UNSAT ***********
  
 1)NOTE: PLEASE SUBMIT A COMNPLETE SET
 OF ELECTRICAL PLANS BY THE ARCH/ENG OF
 RECORD. A REVISION WAS SUBMITTED BY
 THE ELECTRICAL CONTRACTOR LESS THAN A
 WEEK AGO SHOWING A COMPLETELY DIFERENT
 ELECTRICALSERVICE.
  
 2)NOTE: PLEASE NOTE THAT NEW SERVICE
 SHOWN FOR LAUNDRY ALONG IS NOT PERMITTED
 UNLESS THERE IS A TWO HOUR SEPARATION
 BETWEEN EXISTING AND NEW.
  
 3)NOTE: PLEASE NOTE GROUPING OF DISC`S
 230-72
  
  
 PLEASE SUBMIT NEW PLANS SHOWING COMPLETE
 ELECTRICAL. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-11-30 Cont ID  
Sent By dpalmer Date 2001-11-30 Time 15:29 Rev Time 0.00
Received By dpalmer Date 2001-11-30 Time 15:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-11-20 Cont ID  
Sent By dpalmer Date 2001-11-20 Time 21:44 Rev Time 0.00
Received By dpalmer Date 2001-11-20 Time 21:44 Sent To  
Notes
2001-11-20 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE
 SHOWING NEW SUB-PANEL AND NO INFORMATION
 ON WHERE? HOW? PANEL IS BEING FED?
 LOAD CALCULATIONS FOR LOADS BEING ADDED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANYQUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-08-31 Cont ID  
Sent By dpalmer Date 2001-08-31 Time 13:02 Rev Time 0.00
Received By dpalmer Date 2001-08-31 Time 13:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-21 Cont ID  
Sent By dpalmer Date 2001-08-21 Time 18:29 Rev Time 0.00
Received By dpalmer Date 2001-08-21 Time 18:29 Sent To  
Notes
2001-08-21 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT NOT ENOUGH
 INFORMATION WAS SUBMITTED FOR REVIEW.
 PLEASE NOTE THAT PERMIT APPLICATIONS AND
 PLANS/ MENTIONS NEW A/C UNITS BEING
 ADDED.?
 PLEASE SHOW LOCATIONS AND LAYOUT FOR
 ALL NEW ELECTRICAL DEVICES AND FIXTURE
 LOCATIONS ON A FLOOR LAYOUT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-09-07 Cont ID  
Sent By lsmith Date 2001-09-07 Time 08:42 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2001-12-13 Cont ID  
Sent By mcarsill Date 2001-12-13 Time 12:32 Rev Time 0.00
Received By mcarsill Date 2001-12-13 Time 12:32 Sent To  
Notes
2001-12-13 00:00:001) NEW LAUNDRY ROOM IS TO BE AT LEAST
 ONE HOUR FIRE RATED AS PER NFPA 101,
 THE LIFE SAFETY CODE, 1985 EDITION,
 SECTION 19-3.2.1 WHICH REQUIRES
 "EVERY HAZARDOUS AREA SHALL BE
 SEPARATED FROM OTHER PARTS OF THE
 BUILDING BY CONSTRUCTION HAVING A
 FIRE RESISTANCE RATING OF AT LEAST
 ONE HOUR AND OPENINGS BE PROTECTED
 BY 3/4 FIRE DOORS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-11-21 Cont ID  
Sent By mcarsill Date 2001-11-21 Time 10:49 Rev Time 0.00
Received By mcarsill Date 2001-11-21 Time 10:49 Sent To  
Notes
2001-11-21 00:00:001) MORE DETAILS REQUIRED TO COMPLETE
 PLAN REVIEW. PLEASE INDICATE TYPE OF
 OCCUPANCY, AND OTHER DETAILS REQUIRED
 TO DO REVIEW.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2001-09-07 Cont ID  
Sent By lsmith Date 2001-09-07 Time 08:42 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2001-12-11 Cont ID  
Sent By pkrauss Date 2001-12-11 Time 13:57 Rev Time 0.35
Received By pkrauss Date 2001-12-11 Time 13:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2001-11-28 Cont ID  
Sent By pkrauss Date 2001-11-28 Time 08:06 Rev Time 0.35
Received By pkrauss Date 2001-11-28 Time 08:06 Sent To  
Notes
2001-11-28 00:00:00********************DENIED**************
  
  
 PLEASE PROVIDE DETAIL OF DRYER VENTS.
 ONLY ONE VENT INDICATED ON PLAN, TWO
 DRYERS ARE SHOWN IN THE LAUNDRY ROOM.
  
 PLEASE INDICATE IF DRYERS ARE COMMERCIAL
 OR RESIDENTIAL.PROVIDE MANUFACTURER
 SUBMITTAL DATA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-11-27 Cont ID  
Sent By pkrauss Date 2001-11-27 Time 10:07 Rev Time 0.50
Received By pkrauss Date 2001-11-27 Time 09:54 Sent To  
Notes
2001-11-27 00:00:00CHANGED P-TAC UNITS TO 1.5 TON SPLIT
 UNIT.NANCY DID PRE-INSPECTION
 ACCORDING TO CONTRACTOR (TIM CURRAN)

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-09-04 Cont ID  
Sent By ndenmark Date 2001-09-04 Time 10:47 Rev Time 0.25
Received By ndenmark Date 2001-09-04 Time 10:46 Sent To  
Notes
2001-09-04 00:00:00REPLACEMENT OF A/C W/ PTAC UNITS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-23 Cont ID  
Sent By pkrauss Date 2001-08-23 Time 12:18 Rev Time 0.45
Received By pkrauss Date 2001-08-23 Time 12:18 Sent To  
Notes
2001-08-23 00:00:00*******************DENIED***************
  
  
 INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.PLEASE PROVIDE MANUFACTURER
 INFORMATION ON AC UNITS BEING INSTALLED
 ANDPLANS INDICATING LOCATION OF AC
 UNITS.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-01-02 Cont ID  
Sent By kstevens Date 2002-01-02 Time 18:41 Rev Time 0.50
Received By kstevens Date 2002-01-02 Time 18:41 Sent To  
Notes
2002-01-02 00:00:00REVISION APPROVED

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-11-20 Cont ID  
Sent By kstevens Date 2001-11-20 Time 21:21 Rev Time 0.50
Received By kstevens Date 2001-11-20 Time 21:21 Sent To  
Notes
2001-11-20 00:00:00REVISION DENIED
 REFERENCE: SPC-94
  
 1) FLOOR DRAIN REQUIRED IN WASHING FAC-
 ILITIES PER SPC SEC 409.4.5 MINIMUM 3"
 WITH TRAP PRIMER.
  
 2) 3" VENT THRU ROOF REQUIRED ON EACH
 BLDG DRAIN PER SPC SEC 904.3.1.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-08-16 Cont ID  
Sent By jleech Date 2001-08-16 Time 19:08 Rev Time 0.50
Received By jleech Date 2001-08-16 Time 19:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2001-11-19 Cont ID  
Sent By sgraham Date 2001-11-19 Time 12:20 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-11-19 00:00:00NEED SITE PLAN TO SHOW OF NEW LAUNDRY

Review Stop Z ZONING
Rev No 1 Status N Date 2001-09-07 Cont ID  
Sent By lsmith Date 2001-09-07 Time 08:42 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***