Plan Review Details - Permit 01080609
Plan Review Stops For Permit 01080609
Review Stop E ELECTRICAL
Rev No 3 Status N Date 2001-10-11 Cont ID  
Sent By dpalmer Date 2001-10-11 Time 14:38 Rev Time 0.00
Received By dpalmer Date 2001-10-11 Time 14:38 Sent To  
Notes
2001-10-11 00:00:00ELECTRICAL REVIEW PULLED FROM MASTER
 IN ORDER TO PRINT BLDG PERMIT.
  
 SEPARATE PERMIT APPLICATION AND NEW
 PLANS WILL BE REQ`D TO BE SUBMITTED
 BEFORE ANY ELECTRICAL IS TO BE DONE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-10-09 Cont ID  
Sent By dpalmer Date 2001-10-09 Time 21:37 Rev Time 0.00
Received By dpalmer Date 2001-10-09 Time 21:37 Sent To  
Notes
2001-10-09 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE, PLANS ARE JUST NOW
 BEING SUBMITTED WITH AN ELECTRICAL
 RISER DIAGRAM/PANEL SCHEDULE AND LOAD
 CALCULATIONS.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
  
 5)NOTE: PLEASE NOTE THAT RISER SHOWS AN
 EQUIPMENT GROUNDING CONDUCTOR BEING
 INSTALLED BETWEEN METER AND FIRST MEANS
 OF DISCONNECT? PLEASE NOTE THAT THIS IS
 PARALLELING THE NEUTRAL.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-23 Cont ID  
Sent By dpalmer Date 2001-08-23 Time 16:01 Rev Time 0.00
Received By dpalmer Date 2001-08-23 Time 16:01 Sent To  
Notes
2001-08-23 00:00:00***************** UNSAT ***************
  
 1) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 PLEASE SEE MISSING LOCATIONS THROUGHOUT.
  
 2) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
  
 3)NOTE: PLEASE NOTE THAT SMOKE DETECTORS
 ARE TO BE INSTALL A MIN OF 3` FROM
 BATHS/ PER NFPA-72 2-5.2.1.6
  
 4)NOTE: PLEASE NOTE MISSING OUTLET FOR
 GARAGE PER 210-52G AND GFI PER 210-8.
  
 5)NOTE: PLEASE NOTE THAT NO RISER
 DIAGRAM WAS SUBMITTED FOR REVIEW????
 PLEASE NOTE THAT NO LOAD CALCULATIONS
 WERE SUBMITTED. 215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELELCTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-10-08 Cont ID  
Sent By hmoser Date 2001-10-08 Time 10:17 Rev Time 0.30
Received By hmoser Date 2001-10-08 Time 10:17 Sent To  
Notes
2001-10-08 00:00:00NO MECHANICAL PERMIT NUMBER ON THIS
 APLICATION

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-21 Cont ID  
Sent By hmoser Date 2001-08-21 Time 18:35 Rev Time 0.33
Received By hmoser Date 2001-08-21 Time 18:35 Sent To  
Notes
2001-08-21 00:00:00PLAN DENIED
 #1 NO DUCT SIZE ON PLAN
 #2 EXHAUST FANS MUST BE INSTALLED IN
 BATHROOMS WITH WINDOWS LESS THAN
 3 SQ. FT. OF OPEN AREA
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-12-16 Cont ID  
Sent By pschmitz Date 2001-12-16 Time 09:08 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-12-16 00:00:00REVISION, APPROVED.PES

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-10-05 Cont ID  
Sent By kstevens Date 2001-10-05 Time 17:52 Rev Time 0.33
Received By kstevens Date 2001-10-05 Time 17:52 Sent To  
Notes
2001-10-05 00:00:00PASSED/PROVISO
  
 SUBMIT REVISION IF INSTALLED DIFFERENT
 THAN SANT RISER.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-08-18 Cont ID  
Sent By jleech Date 2001-08-18 Time 07:02 Rev Time 0.33
Received By jleech Date 2001-08-18 Time 07:01 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 7 Status P Date 2002-03-11 Cont ID  
Sent By rmcdouga Date 2002-03-11 Time 13:39 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-03-11 00:00:00TRUSSES OK W/LETTER FROM ENGINEER,
 DESIGNER OF RECORD FOR STRUCTURE.
 3-11-01 RM

Review Stop R ROOF PLAN REVIEW
Rev No 6 Status F Date 2002-03-06 Cont ID  
Sent By rmcdouga Date 2002-03-06 Time 08:51 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-03-06 00:00:00*************TRUSSES DENIED*************
  
 1) THE TRUSS DRAWINGS ARE REQUIRED TO
 HAVE THE EMBOSSED SEAL OF THE TRUSS
 ENGINEER.
  
 2) PLEASE CORRECT WINDLOAD LISTED ON THE
 TRUSS LAYOUT TO THE SAME AS THAT LISTED
 ON THE TRUSS DRAWINGS.
  
 3) THE DESIGNER OF RECORD FOR THE
 STRUCTURE IS REQUIRED TO STAMP, SIGN AND
 DATE THE TRUSS LAYOUT. THE STAMP SHOULD
 STATE THAT THE LAYOUT AND DRAWINGS HAVE
 BEEN REVIEWED AND APPROVED BY HIM.
 THIS IS IN ADDITION TO THE LETTER FROM
 DESIGNER OF RECORD.
  
 4)THE UPLIFT GIVEN ON THE TRUSS DRAWINGS
 EXCEEDS THE CAPACITIES OF THE CONNECTORS
 SPECIFIED IN THE SCHEDULE ON SHEET 6 OF
 THE PLANS FOR SEVERAL OF THE TRUSSES.
 T-21 @ 15= 1869# > A2 = 1060#
 T-7 @ 2= 3339# > A5 = 2650#
 T-8 @ 2= 2167# > A3 = 1300#
 T-9 @ 2= 2234# > A3 = 1300#
 T-3 @ 2&6= 1516# > A1 =755#
 T-32,T-33,T-26,T-27,T-28,ETC.
 PLEASE REVIEW TRUSS DRAWINGS AND
 CONNECTOR SCHEDULE AND MAKE CORRECTIONS
 AS NECESSARY.
  
 AN ADDITIONAL RESUB FEE WILL BE ASSESSED
 FOR SUBSEQUENT RESUBS. THERE WAS NO
 CHARGE FOR THE FIRST RESUB. SEE ATTACH-
 MENT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status F Date 2002-02-01 Cont ID  
Sent By rmcdouga Date 2002-02-01 Time 11:26 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-02-01 00:00:00TRUSSES DENIED
  
 1) SUBMIT REVISED PLANS AND CONNECTOR
 SCHEDULE AS INDICATED IN LETTER FROM
 THE ENGINEER.
  
 2) TRUSS DRAWINGS CONTAIN INCORRECT
 DESIGN INFORMATION. IF TRUSSES ARE
 DESIGNED USING ASCE 7-95 THE CORRECT
 WIND SPEED TO USE IS 140 MPH. SEE MAP IN
 ASCE 7-95. IF USING 110 MPH WIND SPEED
 USE 1997 SBC SECTION 1606.
  
 3) PROVIDE ENGINEERED DRAWINGS OF THE
 REPAIRS TO THE TRUSSES WITH DEFLECTIONS
 GREATER THAN L/360, AS INDICATED IN THE
 LETTER FROM MR. AVERKAMP.
  
 4) PROVIDE THE TRUSS LAYOUT AND DRAWINGS
 TO THE DESIGNER OF RECORD FOR THE
 STRUCTURE FOR HIS REVIEW AND APPROVAL.
 THE DESIGNER OF RECORD OF THE STRUCTURE
 IS TO ACKNOWLEDGE HIS APPROVAL WITH HIS
 SIGNATURE AND DATE ON THE LAYOUT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2002-01-09 Cont ID  
Sent By rmcdouga Date 2002-01-09 Time 10:19 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-01-09 00:00:00TRUSSES DENIED
  
 1) PROVIDE (2) SETS OF TRUSS DRAWINGS
 AND LAYOUTS. THE LAYOUTS ARE REQUIRED TO
 BE SIGNED, SEALED AND DATED BY THE TRUSS
 ENGINEER. THE ENGINEER'S TITLE BLOCK IS
 REQUIRED. INDICATE THE DESIGN CRITERIA
 USED ON THE LAYOUT. ASCE7-95 (140 MPH
 WINDLOAD) OR 97 SBC SECTION 1606 (110MPH
 WINDLOAD).
  
 2) THE LAYOUT MUST BE REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD FOR
 THE STRUCTURE (JOHN AVERKAMP, INC.).
 THIS IS TO BE INDICATED ON THE TRUSS
 LAYOUT.
  
 3) THE DESIGN CRITERIA INDICATED ON THE
 TRUSS DRAWINGS IS INCORRECT. THE CORRECT
 DESIGN CRITERIA IS ASCE7-95 (140 MPH
 WINDLOAD) OR 1997 STANDARD BUILDING CODE
 SECTION 1606 (110 MPH WINDLOAD).
  
 4) THE TRUSS DRAWINGS ARE REQUIRED TO BE
 DATED BY THE TRUSS ENGINEER INDICATING
 THE DATE THEY WERE SEALED.
  
 5) THE TRUSS LAYOUT AND THE ROOF FRAMING
 PLAN (SHEET 6) HAVE SIGNIFICANT
 DIFFERENCES. PLEASE SUBMIT A REVISED
 ROOF FRAMING PLAN.
  
 6) TRUSS T1 (UPLIFT 1891#) EXCEEDS THE
 CAPACITY OF THE SPECIFIED CONNECTOR, A3
 (1360#). PLEASE CORRECT.
  
 7) T30 AT JOINT 10 (UPLIFT 912#) EXCEEDS
 CAPACITY OF A1 (755#). PLEASE CORRECT.
  
 8) T32 (UPLIFTS 839# AND 1112#) EXCEED
 CAPACITY OF A1 (755#). PLEASE CORRECT.
  
 TO AVOID DELAYS, CHECK THE UPLIFT
 CAPACITIES OF THE SPECIFIED CONNECTORS
 TO ENSURE THAT THEY ARE CAPABLE OF
 RESISTING THE IMPOSED LOADS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2001-11-20 Cont ID  
Sent By rmcdouga Date 2001-11-20 Time 09:46 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-11-20 00:00:00REVISION TO ADD COVERED PORCH IS OK
 11-20-01 RM

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-10-11 Cont ID  
Sent By rmcdouga Date 2001-10-11 Time 13:45 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-09-12 Cont ID  
Sent By rmcdouga Date 2001-09-12 Time 14:04 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-09-12 00:00:00*************BUILDING UNSAT*************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) PROVIDE ENERGY CALCULATIONS THAT HAVE
 SIGNATURE OF OWNER/AGENT.
  
 4)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - FIXED GLASS (ARCHED TOP)
 - STRUCTURAL MULLIONS
 - EXTERIOR OUTSWING DOUBLE DOORS
 - SLIDING GLASS DOORS
  
 5) PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE FOR STORM PANELS. INDICATE
 TYPE OF ANCHORS THAT WILL BE USED.
  
 6) THE INFORMATION PROVIDED FOR THE
 EMERGENCY EGRESS WINDOWS CONTAINS ERRORS
 THERE ARE NO SECTIONS 1005.42, 1005A2 OR
 1005.43 IN THE 1997 SBC. THE CODE DOES
 NOT SPECIFY A MINIMUM TOTAL GLASS AREA.
 ONLY THE MINIMUM NET CLEAR OPENING AREA
 AND MINIMUM NET CLEAR OPENING DIMENSIONS
 ARE SPECIFIED. PLEASE CORRECT. (SHEET 1)
  
 7) THERE IS NO STEEL REINFORCEMENT
 INDICATED FOR THE 8" THICKENED FOOTER AT
 THE GARAGE. PLEASE INDICATE ON PLANS.
 (SHEET2)
  
 8) THE WALL BETWEEN THE HOUSE AND THE
 GARAGE IS REQUIRED TO BE INSULATED AND
 THE DOOR IN THIS WALL MUST BE SOLID CORE
 WOOD, WOOD PANEL OR INSULATED DOOR PER
 97 FLORIDA ENERGY CODE. PLEASE INDICATE
 THIS ON PLANS.
  
 9) PLEASE INDICATE THE MEAN ROOF HEIGHT
 ON THE PLANS.
  
 10) THE MINIMUM BUILDING FLOOR ELEVATION
 AT HABITABLE AREAS SHALL BE A MINIMUM OF
 4 INCHES ABOVE FINISH GRADE AND THE
 BOTTOM OF THE FOOTER SHALL BE A MINIMUM
 OF 12 INCHES BELOW FINISH GRADE. PLEASE
 INDICATE THIS ON THE PLANS. (SHEET 7)
  
 11) THE GIRDER TRUSS AT BEDROOM 3 AND
 THE FAMILY ROOM WITH AN UPLIFT GIVEN OF
 4700# HAS ONE A5 ANCHOR INDICATED WHICH
 IS ONLY GOOD FOR 1815# OF UPLIFT. PLEASE
 CORRECT. (SHEET 6)
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 2 Status P Date 2001-11-19 Cont ID  
Sent By sgraham Date 2001-11-19 Time 15:20 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-08-15 Cont ID  
Sent By sgraham Date 2001-08-15 Time 15:50 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***