Plan Review Stops For Permit 01080484 |
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2001-09-07 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-09-07 |
Time |
10:02 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2001-09-07 |
Time |
09:57 |
Sent To |
|
|
Notes |
2001-09-07 00:00:00 | PROVISO ON PLAN - DUCTWORK INSTALLED | | UNDER THE HOUSE SHALL NOT BE IN OR | | WITHIN 4" OF THE GROUND.1997 SMC | | 605.4. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2001-08-13 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-08-13 |
Time |
08:27 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2001-08-13 |
Time |
08:05 |
Sent To |
|
|
Notes |
2001-08-13 00:00:00 | *******************PROVISO************** | | | | | | AHU 1 - NO ACCESS INDICATED ON PLAN. | | ACCESS FOR ATTIC INSTALLATION SHALL | | COMPLY WITH 1997 SMC 304.4.1 (ACCESS | | OPENING SHALL BE NO LESS THAN 22" X | | 36").ALL AIR CONDITIONING/HEATING | | EQUIPMENT INSTALLED IN ATTIC SHALL HAVE | | AN ACCESSIBLE DISCONNECT SWITCH AND A | | 110-120 VOLT A/C GROUNDING TYPE | | CONVENIENCE OUTLET. | | | | ALIGHT SHALL BE PROVIDED ON SERVICE | | SIDE OF EQUIPMENT CONTROLLED BY A | | SWITCH AT ATTIC OPENING. | | | | DRAIN PANS WITH OVERFLOW PROTECTION ALSO | | REQUIRED AS PER 1997 SMC 304.8.6.1. | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
|