Plan Review Details - Permit 01080408
Plan Review Stops For Permit 01080408
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-01-29 Cont ID  
Sent By dpalmer Date 2002-01-29 Time 11:17 Rev Time 0.00
Received By dpalmer Date 2002-01-29 Time 11:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-08-23 Cont ID  
Sent By dpalmer Date 2001-08-23 Time 14:12 Rev Time 0.00
Received By dpalmer Date 2001-08-23 Time 14:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-01-09 Cont ID  
Sent By pkrauss Date 2002-01-09 Time 11:27 Rev Time 0.40
Received By pkrauss Date 2002-01-09 Time 11:27 Sent To  
Notes
2002-01-09 00:00:00MECH REV PERMIT 01080475

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-08-21 Cont ID  
Sent By hmoser Date 2001-08-21 Time 18:27 Rev Time 0.33
Received By hmoser Date 2001-08-21 Time 18:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-02-21 Cont ID  
Sent By kstevens Date 2002-02-21 Time 17:12 Rev Time 0.50
Received By kstevens Date 2002-02-21 Time 17:12 Sent To  
Notes
2002-02-21 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) SANT. RISER DIAGRAM DOES NOT REFLECT
 FLOOR PLAN. LAUNDRY SINK MISSING, WASH-
 MACHINE TO BE TAKEN OFF BLDG DRAIN BE-
 FORE KITCHEN SINK, MASTER BATH FIXTURES
 ARE NOT THE SAME LAYOUT ON FLOOR PLAN AS
 THEY ARE ON RISER DIAGRAM. PLEASE SUBMIT
 A RISER DIAGRAM TO REFLECT HOW PIPING IS
 INSTALLED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-09-07 Cont ID  
Sent By kstevens Date 2001-09-07 Time 13:12 Rev Time 0.33
Received By kstevens Date 2001-09-07 Time 13:12 Sent To  
Notes
2001-09-07 00:00:00PASSED/PROVISO
  
 REVISED SANITARY RISER DIAGRAM REQUIRED
 SUBMIT DIAGRAM THAT REFLECTS FLOOR PLAN

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-16 Cont ID  
Sent By kstevens Date 2001-08-16 Time 07:31 Rev Time 0.50
Received By kstevens Date 2001-08-16 Time 07:31 Sent To  
Notes
2001-08-16 00:00:00DENIED
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS, AND DOES NOT REFLECT
 FLOOR PLAN.
  
 2) NO 1-1/2" PIPE UNDER SLAB. BOTH TUBS
 SHOW 1-1/2" AND 2" MINIMUM REQUIRED.
  
 3) NO SHOWER FOR MASTER BATH SHOWN ON
 SANT. RISER DIAGRAM.
  
 4) PLEASE SUBMIT RISER DIAGRAM THAT RE-
 FLECTS FLOOR PLAN AND COMPLIES WITH SPC-
 94 CODE REQUIREMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2001-09-10 Cont ID  
Sent By lsmith Date 2001-09-10 Time 08:32 Rev Time 2.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-09-07 Cont ID  
Sent By sgraham Date 2001-09-07 Time 07:23 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***