Plan Review Details - Permit 01080403
Plan Review Stops For Permit 01080403
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-01-08 Cont ID  
Sent By rbrown Date 2002-01-08 Time 17:38 Rev Time 2.00
Received By rbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-08-31 Cont ID  
Sent By lmartine Date 2001-08-31 Time 14:34 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2001-08-31 00:00:00PROVISO
 ---------
  
  
 SUBMIT ENERGY EFFICIENCY REPORT
  
  
 L MARTINEZ
 SUBMIT ENERGY EFFICIENCY
  
  
 L MARTINEZ

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2002-01-30 Cont ID  
Sent By dpalmer Date 2002-01-30 Time 16:40 Rev Time 0.00
Received By dpalmer Date 2002-01-30 Time 16:40 Sent To M
Notes
2002-01-30 00:00:00****************** UNSAT **************
  
 PLEASE NOTE THAT SOME ITEMS FROM PROVISO
 WERE NOT ADDRESSED FROM PREVIOUS REVIEW.
  
 1)NOTE: PLEASE NOTE WIRE SIZE SHOWN AT
 #3, IS ONLY RATED FOR 100AMPS. PLEASE
 NOTE PLANS SHOW 125A DISC AND PANEL?
  
 2)NOTE: PLEASE SHOW EQUIPMENT GROUNDING
 CONDUCTOR FROM MAIN DISC TO PANEL.
  
 3)NOTE: PLEASE SHOW LOAD CALCAULATIONS
 PER 220-3/220-10/220-11/220-13 AND
 ALL CONTINUOUS LOADS AT 125%.
  
 4)NOTE:PLEASE CLARFIY LOAD SHOWN FOR
 A/C. SHOWN AT 4500W? TYPICAL A/C HEAT
 IS 5KW/7KW ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-01-10 Cont ID  
Sent By dpalmer Date 2002-01-10 Time 06:21 Rev Time 0.00
Received By dpalmer Date 2002-01-10 Time 06:21 Sent To  
Notes
2002-01-10 00:00:00******** PROVISO /REVISION************
  
  
 1)NOTE: PLEASE NOTE, LOAD CALCULATIONS
 NEED TO BE REVISED. PLEASE SEE 220-3,
 220-10,220-11,220-13. LIGHTING=WATTS/PER
 SQ FT.TRACK LIGHTING PER 220-12B 150VA
 PER 2' OF TRACK.
 PLEASE NOTE ALL CONTINUOUS LOADS TO BE
 SHOWN AT 125%.(LIGHTING) 215-3/230-42
 OUTLETS PER 220-13 180VA PER OUTLET.
  
 2)NOTE: PLEASE NOTE THAT CONDUCTORS
 FEEDING PANEL 3A ARE ONLY RATED FOR
 100AMPS. PLEASE SEE 310-16 FOR CORRECT
 CONDUCTOR SIZING FOR 125A`S. IF 125A
 DISCONNECT OS FUSED DOWN? PLEASE SHOW.
  
 3)NOTE: PLEASE NOTE THAT NOTE ON PLAN
 SHOWS CIRCUITS FOR THE TENANT SPACE
 TO BE CIRCUITED TO ELECTRICAL ROOM?
 PLEASE NOTE ALL OTHER TENANT SPACES HAVE
 THERE OWN ELECTRICAL PANEL,PLEASE NOTE
 EACH TENANT MUST HAVE ACCESS TO THEIR
 OWN PANEL/CIRCUITS IN ORDER TO TURN
 OFF IF NEEDED/OR IF SOMETHING TRIPPED,
 THEY WOULD BE ABLE TO RESET. PLEASE
 ALSO NOTE THAT ELECTRICAL ROOMS MUST
 BE ACCESSIBLE TO QUALIFIED PERSONNEL
 ONLY? PLEASE NOTE THAT A NEW PANEL IN
 SPACE WOULD MOST LIKELY BE REQUIRED.
 A BLDG UNDER SINGLE MANGAMENT CAN MEET
 THE REQUIREMENT AS LONG AS A "QUALIFIED"
 PERSON IS AVAILABLE DURING BUSINESS HOUR
 -S. PLEASE NOTE THAT A "QUALIFIED PERSON
 IS SOMEONE THAT HOLDS AN ELECTRICAL
 LICENSE OF SOMEKIND(JOURNEYMAN) ETC.
 PLEASE CALL TO GO OVER THIS. PER NEC
 REGULATIONS.
  
 PLEASE SUBMIT THE ABOVE REVISION FOR
 REVIEW BEFORE ANY ROUGH INSPECTION IS
 CALLED IN. IF THERE ARE ANY QUESTIONS
 PLEASE CALL. IF A MEETING IS NEEDED TO
 GO OVER ANYTHING, PLEASE DO NOT HESITATE
 IN CONTACTING ME.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-09-24 Cont ID  
Sent By dpalmer Date 2001-09-24 Time 08:25 Rev Time 0.00
Received By dpalmer Date 2001-09-24 Time 08:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-21 Cont ID  
Sent By dpalmer Date 2001-08-21 Time 19:09 Rev Time 0.00
Received By dpalmer Date 2001-08-21 Time 19:09 Sent To  
Notes
2001-08-21 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT ALL EXITING
 AND EMERGENCY LIGHTING NEEDS TO BE
 SHOWN ON LAYOUT. PLEASE NOTE THAT SUITE
 301 EXISTINGSHOWS NEW WIRING? PLEASE
 SHOW EM LIGHTING AND EXIT LTS.
  
 2)NOTE: PLEASE NOTE THAT ALL BRANCH
 CIRCUITING NEEDS TO BE SHOWN ON PLANS
 INCLUDING LIGHTING.
  
 3)NOTE: PLEASE CLARIFY MEANS OF EQUIP-
 -MENT GROUNDING BETWEEN DISC AND PANEL.
 250-122
  
 4)NOTE: PLEASE SUBMIT THE AIC RATING FOR
 NEW DISCONNECT ALSO. 110-9/215-5
  
 5)NOTE: PLEASE CLARIFY LOAD SHOWN FOR
 SERVICE? LOAD SHOWN AT 85AMPS. 11,120/
 240V.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE NOTE THAT COMMENTS CAN
 BE GONE OVER ON THE PHONE OR IN PERSON.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-01-09 Cont ID  
Sent By mcarsill Date 2002-01-08 Time 09:42 Rev Time 0.00
Received By mcarsill Date 2002-01-08 Time 09:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-10-04 Cont ID  
Sent By mcarsill Date 2001-10-04 Time 16:07 Rev Time 0.00
Received By mcarsill Date 2001-10-04 Time 16:07 Sent To  
Notes
2001-10-04 00:00:00APPROVED PROVISO:
  
 FIRE SPRINKLER AND FIRE ALARM SYSTEM
 MUST BE PRESENT IN THESE AREAS PRIOR
 TO OCCUPYING.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-09 Cont ID  
Sent By mcarsill Date 2001-08-09 Time 09:14 Rev Time 0.00
Received By mcarsill Date 2001-08-09 Time 09:14 Sent To  
Notes
2001-08-09 00:00:001) NO INDICATION ON PLANS WHERE EXISTING
 OR NEW FIRE ALARM EQUIPMENT IS LOCATED
 ON THE THIRD FLOOR.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2002-02-01 Cont ID  
Sent By pkrauss Date 2002-02-01 Time 08:04 Rev Time 0.35
Received By pkrauss Date 2002-02-01 Time 07:39 Sent To  
Notes
2002-02-01 00:00:00REVISION TO MECH PERMIT 01080404

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2002-01-14 Cont ID  
Sent By dpalmer Date 2002-01-30 Time 17:26 Rev Time 0.30
Received By pkrauss Date 2002-01-14 Time 12:18 Sent To  
Notes
2002-01-14 00:00:00 
 MECHANICAL SUBMITTAL FOR THE C.U. STAND
  
 PROVISO:A MINIMUM OF 18" REQUIRED FROM
 THE ROOF SURFACE TO THE BOTTOM
 OF THE SUPPORT RAIL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-01-11 Cont ID  
Sent By pkrauss Date 2002-01-11 Time 15:56 Rev Time 0.45
Received By pkrauss Date 2002-01-11 Time 15:56 Sent To  
Notes
2002-01-11 00:00:00 
 PROVISO ON PLAN - MECH PERMIT 01080404
  
 O.A. SHALL BE SCREENED
  
 C.U. STANDS TO BE SUBMITTED PRIOR TO
 INSPECTIONS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2002-01-10 Cont ID  
Sent By pkrauss Date 2002-01-10 Time 13:32 Rev Time 0.40
Received By pkrauss Date 2002-01-10 Time 13:12 Sent To  
Notes
2002-01-10 00:00:00 
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-1989.
  
 2.INDICATE OUTSIDE AIR ON PLAN.
  
 3.ENERGY CALCULATIONS NEED TO BE
 REVISED TO COINSIDE WITH PLAN.
  
 4.PLEASE INDICATE LOCATION OF
 CONDENSER UNITS.PLEASE SUBMIT
 MANUFACTURER'S CUT SHEETS IF ANY
 NEW STANDS ARE BEING INSTALLED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-10-10 Cont ID  
Sent By pkrauss Date 2001-10-08 Time 11:24 Rev Time 0.45
Received By pkrauss Date 2001-10-08 Time 10:20 Sent To  
Notes
2001-10-08 00:00:00********************DENIED**************
  
 PLEASE SHOW COMPLIANCE WITH THE 1997
 FLORIDA ENERGY CODE.
  
  
 THE SUPPLY OF HEATING AND COOLING TO
 EACH ZONE SHALL BE CONTROLLED BY
 INDIVIDUAL THERMOSTATIC CONTROLS FOR
 CONTROLLING THE TEMPERATURE WITHIN THE
 ZONE.
  
 SYSTEMS THAT SERVE ZONES WHICH CAN BE
 EXPECTED TO OPERATE NON-SIMULTANEOUSLY
 FOR MORE THAN 750 HOURS PER YEAR SHALL
 INCLUDE ISOLATION DEVISES AND CONTROLS
 TO SHUT OFF OR SET BACK THE SUPPLY OF
 HEATING AND COOLING TO EACH ZONES
 INDEPENDENTLY.ISOLATION IS NOT
 REQUIRED FOR ZONES EXPECTED TO BE
 INOPERATIVE ONLY WHEN ALL OTHER ZONES
 ARE INOPERATIVE.
  
 FOR BUILDINGS WHERE OCCUPANCY PATTERNS
 ARE NOT KNOWN AT THE TIME OF SYSTEM
 DESIGN, SUCH AS SHELL BUILDINGS,
 ISOLATION AREAS MAY BE PREDESIGNATED.
  
 THE EXISTING OFFICE SPACE (NO SUITE
 DESIGNATED) SHALL HAVE A RETURN AIR
 FROM THIS SPACE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-24 Cont ID  
Sent By pkrauss Date 2001-08-24 Time 09:38 Rev Time 0.35
Received By pkrauss Date 2001-08-24 Time 09:36 Sent To  
Notes
2001-08-24 00:00:00*******************DENIED***************
  
  
 1.CFM DISTRIBUTION ON PLAN ADDS UP TO
 2200 CFM, WHEREAS A/C EQUIPMENT
 SCHEDULE INDICATES UNIT CFM = 1850.
 PLEASE CORRELATE SCHEDULE AND PLAN.
  
 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO SUPERVISORY
 SIGNAL AT A CONSTANTLY ATTENDED
 LOCATION OR TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS. NFPA 90A
 4-4.4.2 OR 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop Z ZONING
Rev No 1 Status N Date 2001-10-09 Cont ID  
Sent By pkrauss Date 2001-10-09 Time 13:09 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***