Plan Review Stops For Permit 01080403 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2002-01-08 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2002-01-08 |
Time |
17:38 |
Rev Time |
2.00 |
Received By |
rbrown |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2001-08-31 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2001-08-31 |
Time |
14:34 |
Rev Time |
1.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-08-31 00:00:00 | PROVISO | | --------- | | | | | | SUBMIT ENERGY EFFICIENCY REPORT | | | | | | L MARTINEZ | | SUBMIT ENERGY EFFICIENCY | | | | | | L MARTINEZ |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2002-01-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-01-30 |
Time |
16:40 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-01-30 |
Time |
16:40 |
Sent To |
M |
|
Notes |
2002-01-30 00:00:00 | ****************** UNSAT ************** | | | | PLEASE NOTE THAT SOME ITEMS FROM PROVISO | | WERE NOT ADDRESSED FROM PREVIOUS REVIEW. | | | | 1)NOTE: PLEASE NOTE WIRE SIZE SHOWN AT | | #3, IS ONLY RATED FOR 100AMPS. PLEASE | | NOTE PLANS SHOW 125A DISC AND PANEL? | | | | 2)NOTE: PLEASE SHOW EQUIPMENT GROUNDING | | CONDUCTOR FROM MAIN DISC TO PANEL. | | | | 3)NOTE: PLEASE SHOW LOAD CALCAULATIONS | | PER 220-3/220-10/220-11/220-13 AND | | ALL CONTINUOUS LOADS AT 125%. | | | | 4)NOTE:PLEASE CLARFIY LOAD SHOWN FOR | | A/C. SHOWN AT 4500W? TYPICAL A/C HEAT | | IS 5KW/7KW ETC. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2002-01-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-01-10 |
Time |
06:21 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2002-01-10 |
Time |
06:21 |
Sent To |
|
|
Notes |
2002-01-10 00:00:00 | ******** PROVISO /REVISION************ | | | | | | 1)NOTE: PLEASE NOTE, LOAD CALCULATIONS | | NEED TO BE REVISED. PLEASE SEE 220-3, | | 220-10,220-11,220-13. LIGHTING=WATTS/PER | | SQ FT.TRACK LIGHTING PER 220-12B 150VA | | PER 2' OF TRACK. | | PLEASE NOTE ALL CONTINUOUS LOADS TO BE | | SHOWN AT 125%.(LIGHTING) 215-3/230-42 | | OUTLETS PER 220-13 180VA PER OUTLET. | | | | 2)NOTE: PLEASE NOTE THAT CONDUCTORS | | FEEDING PANEL 3A ARE ONLY RATED FOR | | 100AMPS. PLEASE SEE 310-16 FOR CORRECT | | CONDUCTOR SIZING FOR 125A`S. IF 125A | | DISCONNECT OS FUSED DOWN? PLEASE SHOW. | | | | 3)NOTE: PLEASE NOTE THAT NOTE ON PLAN | | SHOWS CIRCUITS FOR THE TENANT SPACE | | TO BE CIRCUITED TO ELECTRICAL ROOM? | | PLEASE NOTE ALL OTHER TENANT SPACES HAVE | | THERE OWN ELECTRICAL PANEL,PLEASE NOTE | | EACH TENANT MUST HAVE ACCESS TO THEIR | | OWN PANEL/CIRCUITS IN ORDER TO TURN | | OFF IF NEEDED/OR IF SOMETHING TRIPPED, | | THEY WOULD BE ABLE TO RESET. PLEASE | | ALSO NOTE THAT ELECTRICAL ROOMS MUST | | BE ACCESSIBLE TO QUALIFIED PERSONNEL | | ONLY? PLEASE NOTE THAT A NEW PANEL IN | | SPACE WOULD MOST LIKELY BE REQUIRED. | | A BLDG UNDER SINGLE MANGAMENT CAN MEET | | THE REQUIREMENT AS LONG AS A "QUALIFIED" | | PERSON IS AVAILABLE DURING BUSINESS HOUR | | -S. PLEASE NOTE THAT A "QUALIFIED PERSON | | IS SOMEONE THAT HOLDS AN ELECTRICAL | | LICENSE OF SOMEKIND(JOURNEYMAN) ETC. | | PLEASE CALL TO GO OVER THIS. PER NEC | | REGULATIONS. | | | | PLEASE SUBMIT THE ABOVE REVISION FOR | | REVIEW BEFORE ANY ROUGH INSPECTION IS | | CALLED IN. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. IF A MEETING IS NEEDED TO | | GO OVER ANYTHING, PLEASE DO NOT HESITATE | | IN CONTACTING ME. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2001-09-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-09-24 |
Time |
08:25 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-09-24 |
Time |
08:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-08-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-08-21 |
Time |
19:09 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-08-21 |
Time |
19:09 |
Sent To |
|
|
Notes |
2001-08-21 00:00:00 | ************ UNSAT **************** | | | | 1)NOTE: PLEASE NOTE THAT ALL EXITING | | AND EMERGENCY LIGHTING NEEDS TO BE | | SHOWN ON LAYOUT. PLEASE NOTE THAT SUITE | | 301 EXISTINGSHOWS NEW WIRING? PLEASE | | SHOW EM LIGHTING AND EXIT LTS. | | | | 2)NOTE: PLEASE NOTE THAT ALL BRANCH | | CIRCUITING NEEDS TO BE SHOWN ON PLANS | | INCLUDING LIGHTING. | | | | 3)NOTE: PLEASE CLARIFY MEANS OF EQUIP- | | -MENT GROUNDING BETWEEN DISC AND PANEL. | | 250-122 | | | | 4)NOTE: PLEASE SUBMIT THE AIC RATING FOR | | NEW DISCONNECT ALSO. 110-9/215-5 | | | | 5)NOTE: PLEASE CLARIFY LOAD SHOWN FOR | | SERVICE? LOAD SHOWN AT 85AMPS. 11,120/ | | 240V. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. PLEASE NOTE THAT COMMENTS CAN | | BE GONE OVER ON THE PHONE OR IN PERSON. | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2002-01-09 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-01-08 |
Time |
09:42 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-01-08 |
Time |
09:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2001-10-04 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-10-04 |
Time |
16:07 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-10-04 |
Time |
16:07 |
Sent To |
|
|
Notes |
2001-10-04 00:00:00 | APPROVED PROVISO: | | | | FIRE SPRINKLER AND FIRE ALARM SYSTEM | | MUST BE PRESENT IN THESE AREAS PRIOR | | TO OCCUPYING. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2001-08-09 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-08-09 |
Time |
09:14 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-08-09 |
Time |
09:14 |
Sent To |
|
|
Notes |
2001-08-09 00:00:00 | 1) NO INDICATION ON PLANS WHERE EXISTING | | OR NEW FIRE ALARM EQUIPMENT IS LOCATED | | ON THE THIRD FLOOR. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
6 |
Status |
P |
Date |
2002-02-01 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-02-01 |
Time |
08:04 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2002-02-01 |
Time |
07:39 |
Sent To |
|
|
Notes |
2002-02-01 00:00:00 | REVISION TO MECH PERMIT 01080404 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2002-01-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-01-30 |
Time |
17:26 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2002-01-14 |
Time |
12:18 |
Sent To |
|
|
Notes |
2002-01-14 00:00:00 | | | MECHANICAL SUBMITTAL FOR THE C.U. STAND | | | | PROVISO:A MINIMUM OF 18" REQUIRED FROM | | THE ROOF SURFACE TO THE BOTTOM | | OF THE SUPPORT RAIL. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2002-01-11 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-01-11 |
Time |
15:56 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2002-01-11 |
Time |
15:56 |
Sent To |
|
|
Notes |
2002-01-11 00:00:00 | | | PROVISO ON PLAN - MECH PERMIT 01080404 | | | | O.A. SHALL BE SCREENED | | | | C.U. STANDS TO BE SUBMITTED PRIOR TO | | INSPECTIONS. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2002-01-10 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-01-10 |
Time |
13:32 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2002-01-10 |
Time |
13:12 |
Sent To |
|
|
Notes |
2002-01-10 00:00:00 | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | FOR REVIEW: | | | | 1.OUTSIDE AIR CALCULATIONS AS PER | | ASHRAE 62-1989. | | | | 2.INDICATE OUTSIDE AIR ON PLAN. | | | | 3.ENERGY CALCULATIONS NEED TO BE | | REVISED TO COINSIDE WITH PLAN. | | | | 4.PLEASE INDICATE LOCATION OF | | CONDENSER UNITS.PLEASE SUBMIT | | MANUFACTURER'S CUT SHEETS IF ANY | | NEW STANDS ARE BEING INSTALLED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2001-10-10 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-10-08 |
Time |
11:24 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2001-10-08 |
Time |
10:20 |
Sent To |
|
|
Notes |
2001-10-08 00:00:00 | ********************DENIED************** | | | | PLEASE SHOW COMPLIANCE WITH THE 1997 | | FLORIDA ENERGY CODE. | | | | | | THE SUPPLY OF HEATING AND COOLING TO | | EACH ZONE SHALL BE CONTROLLED BY | | INDIVIDUAL THERMOSTATIC CONTROLS FOR | | CONTROLLING THE TEMPERATURE WITHIN THE | | ZONE. | | | | SYSTEMS THAT SERVE ZONES WHICH CAN BE | | EXPECTED TO OPERATE NON-SIMULTANEOUSLY | | FOR MORE THAN 750 HOURS PER YEAR SHALL | | INCLUDE ISOLATION DEVISES AND CONTROLS | | TO SHUT OFF OR SET BACK THE SUPPLY OF | | HEATING AND COOLING TO EACH ZONES | | INDEPENDENTLY.ISOLATION IS NOT | | REQUIRED FOR ZONES EXPECTED TO BE | | INOPERATIVE ONLY WHEN ALL OTHER ZONES | | ARE INOPERATIVE. | | | | FOR BUILDINGS WHERE OCCUPANCY PATTERNS | | ARE NOT KNOWN AT THE TIME OF SYSTEM | | DESIGN, SUCH AS SHELL BUILDINGS, | | ISOLATION AREAS MAY BE PREDESIGNATED. | | | | THE EXISTING OFFICE SPACE (NO SUITE | | DESIGNATED) SHALL HAVE A RETURN AIR | | FROM THIS SPACE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2001-08-24 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-08-24 |
Time |
09:38 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2001-08-24 |
Time |
09:36 |
Sent To |
|
|
Notes |
2001-08-24 00:00:00 | *******************DENIED*************** | | | | | | 1.CFM DISTRIBUTION ON PLAN ADDS UP TO | | 2200 CFM, WHEREAS A/C EQUIPMENT | | SCHEDULE INDICATES UNIT CFM = 1850. | | PLEASE CORRELATE SCHEDULE AND PLAN. | | | | 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | WITH NOTIFICATION TO SUPERVISORY | | SIGNAL AT A CONSTANTLY ATTENDED | | LOCATION OR TO ALARM/STROBE IN | | NORMALLY OCCUPIED AREAS. NFPA 90A | | 4-4.4.2 OR 4-4.4.3. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2001-10-09 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-10-09 |
Time |
13:09 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|