Plan Review Details - Permit 01080364
Plan Review Stops For Permit 01080364
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-12-27 Cont ID  
Sent By jwitmer Date 2001-12-27 Time 16:18 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-12-27 00:00:00REVISION DATED 10/18/01JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-10-16 Cont ID  
Sent By jwitmer Date 2001-10-16 Time 07:55 Rev Time 2.00
Received By jwitmer Date 2001-10-16 Time 07:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-09-14 Cont ID  
Sent By lmartine Date 2001-09-14 Time 14:51 Rev Time 3.00
Received By lmartine Date   Time   Sent To  
Notes
2001-09-14 00:00:00 
 BUILDING COMMENTS
 -----------------
  
 1]
 SHOWER SHALL COMPY WITH ACCESSIBILITY
 REQUIREMENTS, SEE 4.21 FAC.
 2]
 FOOTING DETAILS SHOW 3 BARS, AND THE
 NOTE ONLY CALLS FOR 2?
 BOTTOM OF FOOTINGS SHALL BE MINIMUM 12"
 BELOW GRADE.
 3]
 THE WEST ELEVATION WALL SHALL NOT HAVE
 ANY OPENINGS PER TABLE 600 SBC, 0-3FT.
 ALSO SEE 705 SBC FOR PROTECTED OPENINGS
 WHEN IF EXTERIOR WALLS ARE LESS THAN
 15FT. FROM P/L.
 4]
 CASEMENT WINDOWS SHALL NOT OPEN OVER
 PUBLIC PROPERTY AT NORTH ELEVATION.
 5]
 PROVIDE COMPLETED FLA. ENERGY EFF.
 REPOTS.
 6]
 SUBMIT PRODUCT TESTING FOR ALL EXTERIOR
 WINDOWS AND DOORS, WIND COMPLIANCE AND
 IMPACT RESISTANCE FOR GLAZING. SUBMIT
 TEST REPORT FOR ROOF COVERS.
 7]
 SHOW ACCESSIBLE ROUTE FROM PARKING
 SPACE TO THE MAIN ENTRANCE, GATES SHALL
 BE ACCESSIBLE TYPE.
 8]
 P.B.C COUNTY IMPACT FEES AND CITY RADON
 FEES ARE DUE.
  
  
 REVIEWED BY:
 LUIS MARTINEZ
 659-8096
 #8456

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-10-10 Cont ID  
Sent By dpalmer Date 2001-10-10 Time 21:03 Rev Time 0.00
Received By dpalmer Date 2001-10-10 Time 21:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-28 Cont ID  
Sent By dpalmer Date 2001-08-28 Time 19:02 Rev Time 0.00
Received By dpalmer Date 2001-08-28 Time 19:02 Sent To  
Notes
2001-08-28 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT PANEL SCHEDULE
 IS SHOWING ALL 2-POLE BRKRS ON LEFT AND
 RIGHT OF PANEL ON THE SAME PHASE. PLEASE
 CORRECT. ALL 2POLE BRKRS SHOULD LINE UP
 ON SAME SIZE FOR 220V
  
 2)NOTE: PLEASE NOTE LOAD FOR WATER HEAT-
 -ER NEEDS TO CORRELATE W/ LOAD SHOWN ON
 PANEL SCHEDULE.
  
 3)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 IS MISSING RISER SIZE, WIRE SIZE FROM
 RISER TO METER TO MAIN DISCONNECT.
  
 4)NOTE: PLEASE ALSO NOTE THAT PLANS SHOW
 MAIN DISCONNECT AND A MCB PANEL. PLEASE
 NOTE PANEL MAY HAVE MAIN ALSO BUT IS NOT
 REQUIRED W/ MAIN DISCONNECT OUTSIDE.
  
 5)NOTE: PLEASE NOTE ALL CONTINOUS LOADS
 TO BE SHOWN AT 125%. (LIGHTING) ETC.
 PER 230-42/215-3
  
 6)NOTE: PLEASE NOTE LOAD SHOWN FOR WATER
 HEATER AT 1500 WATTS AND 20KW ?? WHICH
 ONE? PLEASE ALSO NOTE THAT IF 1500WATTS
 THEM THE MAX OCP IS AT 150%. YOU SHOW
 A 2-P-30. PLEASE CORRECT
  
 7) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50. SHOWS CWP, NOT BLDG STEEL.
  
 8)NOTE: PLEASE NOTE THAT PLANS NEED TO
 SHOW ALL BRANCH CIRCUIT #`S ON PLANS
 AND CORRELATE WITH SUBMITTED PANEL
 SCHEDULES.215-5
  
 9)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATING IS SHOWN FOR
 PANEL, BUT NOT FOR MAIN. PLEASE SUBMIT
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2001-12-27 Cont ID  
Sent By mamini Date 2001-12-27 Time 16:41 Rev Time 1.00
Received By mamini Date 2001-12-27 Time 16:41 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-09-28 Cont ID  
Sent By mamini Date 2001-09-28 Time 08:31 Rev Time 3.00
Received By mamini Date 2001-09-28 Time 08:31 Sent To  
Notes
2001-09-28 00:00:00PASSED :
 1. RESPONSES TO THE PREVIOUS REVIEW
 COMMENTS DATED 8-10-01 STISFACTORY,
 PLANS REVISED PER REVIEW COMMENTS.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-08-10 Cont ID  
Sent By mamini Date 2001-08-10 Time 09:37 Rev Time 5.00
Received By mamini Date 2001-08-10 Time 08:49 Sent To  
Notes
2001-08-10 00:00:00FAILED:
 1. PLEASE PROVIDE A MINIMUM OF 12'-6"
 CLEAR OPENING BETWEEN THE GATE POSTS FOR
 THE PROPOSED DUMPSTER, IF GARBAGE IS TO
 BE PICKED UP BY THE CITY.
 2. ALL OFF-STREET PARKING STALLS MUST BE
 PAINTED WITH DOUBLE 4" WIDE WHITE STRIPE
 PER CITY REQUIREMENT.
 3. SHEET C.1 OF 2 SHOWS GRASSED AREA IN
 FRONT OF DRIVEWAY TO DATURA STREET,
 PLEASE VERIFY.
 4. ALL DRIVEWAY THAT WILL NOT BE USED
 MUST BE REMOVED AND REPLACED WITH THE
 REGULAR CURBS( & GUTTERS).
 5. PLEASE VERIFY THE DETAILS SHOWN FOR
 THE TYPE "C" INLET, SHEET C.2 OF 2.
 6. SHEET C.1 OF 2, NOTES; NO. 2 NOTES
 REFERS TO EXISTING WATER AND SEWER TO BE
 USED, HOWEVER NO PLANS OR DETAILS HAVE
 BEEN PROVIDED, PLEASE NOTE THAT PLANS
 WHICH INCLUDES DETAILS, MAT'L, SIZE AND
 CLEARANCES/CONFLICTS, LOCATIONS OF
 CONNECTIONS AND BACKFLOW PREVENTERS MUST
 BE SUBMITTED FOR OUR REVIEW AND APPROVAL
 7. ANY NEW CONNECTIONS TO CITY SERVICES
 WILL REQUIRE A SEPARATE PERMIT FROM
 PUBLIC UTILITIES ENGINEERING SERVICES
 DEPARTMENT, 659-8040.
 8. ANY WORK WITHIN PUBLIC R.O.W WILL
 REQUIRE A SEPARATE PERMIT FROM CITY
 ENGINEERS OFFICE 659-8040
 9. PLEASE PROVIDE PERVIOUS & IMPERVIOUS
 CALCULATIONS FOR ENTIRE SITE.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-09-26 Cont ID  
Sent By mcarsill Date 2001-09-26 Time 17:29 Rev Time 0.00
Received By mcarsill Date 2001-09-26 Time 17:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-09 Cont ID  
Sent By mcarsill Date 2001-08-09 Time 08:41 Rev Time 0.00
Received By mcarsill Date 2001-08-09 Time 08:41 Sent To  
Notes
2001-08-09 00:00:001) PLEASE BE ADVISED THAT THIS LOCATION
 IS LOCATED WITHIN THE CITY FIRE LIMITS.
 CERTAIN RESTRICTIONS APPLY WITHIN
 THESE FIRE LIMITS. COMPLAINCE WITH
 APPENDIX F OF THE STANDARD BUILDING
 CODE, 1997 EDITION. PLEASE INDICATE
 COMPLIANCE.
 2) BUILDING ADDRESS REQUIRED PER CITY
 CODE REQUIREMENTS 3343-00.
 3) DUCT SMOKE DETECTORS ARE REQUIRED IN
 HVAC SYSTEMS OVER 2000 CFM.
 4) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 5) CANOPIES ARE TO BE FIRE RETARDANT.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-02-19 Cont ID  
Sent By pkrauss Date 2002-02-19 Time 12:53 Rev Time 0.45
Received By pkrauss Date 2002-02-19 Time 12:19 Sent To  
Notes
2002-02-19 00:00:00MECHANICAL PERMIT 010801365

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-10-29 Cont ID  
Sent By pkrauss Date 2001-10-29 Time 10:36 Rev Time 0.40
Received By pkrauss Date 2001-10-29 Time 10:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-10-13 Cont ID  
Sent By pkrauss Date 2001-10-13 Time 07:42 Rev Time 0.40
Received By pkrauss Date 2001-10-13 Time 07:35 Sent To  
Notes
2001-10-13 00:00:00*******************DENIED***************
  
  
 1.AHU #2 INDICATES A FIRE DAMPER ON
 THE O.A. DUCT PENETRATING THE AHU
 CLOSET.IS THE CLOSET RATED?
  
 2.NO COMBUSTIBLES ABOVE THE CEILING
 IN THE RETURN AIR PLENUM.
  
 THE FOLLOWING COMMENTS FROM REVIEW DATED
 8-21-01 WERE NEVER ADDRESSED.
  
 1. CLARIFICATION OF CONDENSATE DRAINS.
  
 2. DUCT SMOKE DETECTORS TIED TO ALARM/
 STROBE.
  
 3. AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-21 Cont ID  
Sent By ndenmark Date 2001-08-21 Time 12:54 Rev Time 0.33
Received By ndenmark Date 2001-08-21 Time 12:54 Sent To  
Notes
2001-08-21 00:00:00*******************DENIED***************
  
 1. PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62.89
 2. PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2
 3. BATHROOM EXHAUST FANS NEED MORE
 INFORMATION, INCLUDING CFM.
 4. NO CFM SHOWN AT A/C DROP IN WOMEN'S
 BATHROOM
 5. DUCT SMOKE DETECTORS WITH
 NOTIFICATION TO BUILDING FIRE ALARM OR
 HORN AND STROBE IF NO BLDG FIRE ALARM
 SYSTEM REQUIRED FOR BOTH AHUS.
 6. PLEASE CLARIFY THE CONDENSATE DRAINS.
 PRIMARY IS NOT SHOWN ON PLAN AND
 EMERGENCY DRAIN NEEDS TO TERMINATE IN
 CONSPICUOUS LOCATION.
 IF CONDENSATE FOR AHU ZONE 2 TERMINATES
 ON WEST SIDE OF BUILDING AS SHOWN,IS
 THERE A PERVIOUS AREA ON THIS PROPERTY
 FOR THE DRAIN TO RUN TO?
 CONDENSATE SHALL EITHER TERMINATE IN A
 STORM SEWER OR APPROVED DRYWELL.
 7. CONDENSING UNITS ARE TO BE ON SOLID
 CONCRETE PADS MINIMUM 3" ABOVE
 ADJOINING GRADE.

Review Stop P PLUMBING
Rev No 5 Status P Date 2001-12-29 Cont ID  
Sent By jleech Date 2001-12-29 Time 06:57 Rev Time 0.50
Received By jleech Date 2001-12-29 Time 06:57 Sent To  
Notes
2001-12-29 00:00:00REVISION;
 RAIN LEADER CALCULATIONS.

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-11-21 Cont ID  
Sent By pschmitz Date 2001-11-21 Time 08:54 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-11-21 00:00:00PROVISO: SPECIAL EXECPTION BBCA. REST/RM
 PES.

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-11-21 Cont ID  
Sent By kstevens Date 2001-10-29 Time 15:56 Rev Time 1.00
Received By pschmitz Date 2001-10-29 Time 15:56 Sent To  
Notes
2001-10-29 00:00:00SEPARATE PERMIT REQUIRED FOR PLUMBING.
 CALCULATIONS FOR MINIMUM FACILITIES ARE
 REQUIRED FOR PLBG PERMIT. NOT ENOUGH W/C
 AND LAV. ON PLANS ATT.
  
 KEN STEVENS

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-10-12 Cont ID  
Sent By kstevens Date 2001-10-12 Time 16:30 Rev Time 1.00
Received By kstevens Date 2001-10-12 Time 16:30 Sent To  
Notes
2001-10-12 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) VARIANCE NOT APPROVED. SPC-97 NOT
 ADOPTED IN PALM BEACH COUNTY. PLEASE
 SUBMIT CALCULATIONS FOR MINIMUM FACILIT-
 IES PER SPC-94 TABLE 407.
  
 2) WATER HAMMER ARRESTORS TO BE PLACED
 NEAR SOURCE NOT AT TOP OF DROPS PER
 MANUFACTURES INSTALLATION INSTRUCTIONS
 AND WH-PDI 201.
  
 3) PAGE A.3 DOOR SHALL NOT OPEN INTO
 CLEAR FLOOR SPACE PER FACBC-9 SEC 4.22.2
 DOORS TO HDCP BATHROOMS SHALL OPEN OUT.
  
 REVIEW BY KEN STEVENS
 (561) 569-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-23 Cont ID  
Sent By kstevens Date 2001-08-23 Time 10:36 Rev Time 0.00
Received By kstevens Date 2001-08-23 Time 10:36 Sent To  
Notes
2001-08-23 00:00:00DENIED
  
 1) MORE FIXTURES REQUIRED. PLEASE SUBMIT
 CALCULATIONS FOR MINIMUM FIXTURES REQ-
 UIRED FOR WATER CLOSETS AND LAVS. PER
 SPC-94 TABLE 407.
  
 2) WATER HEATER TO BE READILY ACCESSABLE
 PER SPC-94 SEC. 501.7. PLEASE SHOW DE-
 TAILS.
  
 3) WATER HAMMER ARRESTORS TO BE INSTALL-
 ED PER MANUFACTURE'S INSTALLATION INSTR-
 UCTIONS AND PDI WH 201.
  
 4) PLEASE SUBMIT CALCULATIONS FOR ROOF
 DOWN SPOUTS AND OVERFLOW SCUPPERS USING
 CHAPTER 11 SPC-94 SECTIONS 1108 AND 1109
  
 REVIEW BY KEN STEVENS
 (561) 569-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-09-28 Cont ID  
Sent By sgraham Date 2001-09-28 Time 08:46 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***