Plan Review Stops For Permit 01080287 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2001-11-13 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-11-13 |
Time |
11:05 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
2001-11-13 |
Time |
11:05 |
Sent To |
|
|
Notes |
2001-11-13 00:00:00 | PRODUCT APP 11/13/01 WINDOW/ DOORJW |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2001-09-14 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-09-14 |
Time |
09:24 |
Rev Time |
1.99 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2001-08-14 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-08-14 |
Time |
17:49 |
Rev Time |
1.50 |
Received By |
jwitmer |
Date |
2001-08-14 |
Time |
17:49 |
Sent To |
|
|
Notes |
2001-08-14 00:00:00 | BUILDING PLAN REVIEW | | PERMIT # 01080287 | | 700 S ROSEMARY #106 | | "PLAN REVIEW" | | SBC= STANDARD BUILDING CODE (1997) | | FL ACC CODE= FLORIDA ACCESSIBILITY CODE | | | | 1)- SHEET A-1 BLOCKING ALL WOOD USED IN | | WALLS ARE TO BE NON-COMBUSTIBLE OR FRT | | FIRE RETARDANT TREATED SBC 609.22.1 | | SHEET A-6 HEADERS / JAMBS FRT WOOD. | | 2)- SHEET A-2 DETAIL #1 SPACING OF METAL | | HIGH HAT NOT GIVEN, NOR IS THE SPACING | | OF THE C-CHANNEL. SPACING OF THE HANGER | | WIRE OR GAUGE. TYPE OF FASTENER TO DECK | | ABOVE? | | | | 3)- SHEET A-2 DETAIL # 1 & 3 DO NOT GIVE | | THE ANCHORING OF THE TOP PLATE OR THE | | SPACING OF THE STUDS. | | | | 4)_ SHEET A-6 SBC 1204.2 REQUIRES A NON- | | ABSORBANT MATERIAL ON FLOORS AND WALLS | | TO A HEIGTH OF 4'-0" IN PUBLIC RESTROOMS | | | | 5)- SBC 1001.1.2 SHOW MEANS OF EGRESS | | THROUGH OUT THE TENANT SPACE INDICATE | | THE 44" ACCESS (MINIMUM). STORAGE AREAS | | THOUGH NOT PROHIBITED AS A COMPONENT OF | | A MEANSOF EGRESS, REQUIRE SPECIAL | | CONSIDERATION. IT IS CRITICAL THAT THE | | REQUIRED MEANS OF EGRESS BE DESIGNATED & | | MAINTAINED TO INSURE THAT OBSTRUCTIONS | | ARE ELIMINATED. SPECIAL MARKINGS OR RAIL | | INGS OR SCREENS MAY BE USED TO SEPERATE | | THE DESIGNATED MEANS OF EGRESS FROM THE | | STORAGE USE. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561)659-8096 X 8412 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2001-09-11 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-09-11 |
Time |
10:06 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-09-10 |
Time |
22:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-08-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-08-21 |
Time |
22:45 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-08-21 |
Time |
22:45 |
Sent To |
|
|
Notes |
2001-08-21 00:00:00 | **************** UNSAT *************** | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | IT IS SHOWN ON PANELS AS?? PLEASE NOTE | | RATINGS ARE REQ`D FOR ALL.215-5 | | | | 2)NOTE: PLEASE NOTE THAT UNDER CITY OF | | WEST PALM BEACH LOCAL AMENDMENTS, OUTLET | | SPACING AT EVERY 20' OF UNENCUMBERED | | WALL SPACE INCLUDING STORAGE/STOCK AREA. | | 210-50 | | 3)NOTE: PLEASE SUBMIT CLARIFICATION ON | | GROUNDING OF TRANSFORMER PER 250-30. | | | | 4)NOTE: PLEASE ALSO NOTE PER LOCAL | | AMENDMENTS, COLOR CODING OF 277/480V | | IS BROWN/PURPLE/YELLOW PER ART215 OF | | LOCAL AMEND. | | | | 5)NOTE: PLEASE NOTE THAT ALL CONTINUOUS] | | LOADS NEED TO BE SHOWN PER 215-3 AND | | 230-42. PLEASE ALSO NOTE THAT LOAD | | CALCUALTIONS NEED TO BE COMPLETED AND | | SHOWN. PER 215-5 | | | | 6)NOTE: PLEASE SEE A-0, PLEASE NOTE | | THAT PLANS REFERENCE THE 1996 NEC. | | PLEASE NOTE THAT WE ARE UNDER THE 99 NEC | | PLEASE ALSO NOTE THAT GENERAL NOTES ON | | SAME PAGE MENTION THAT ALL WORK TO | | COMPLY WITH "BUCKS COUNTY" PA. | | PLEASE CORRECT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2001-08-24 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2001-08-24 |
Time |
14:43 |
Rev Time |
0.00 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2001-09-14 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-09-14 |
Time |
07:20 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-09-14 00:00:00 | FIRE: PER MEC WPBFR8/29/01 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2001-08-08 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-08-08 |
Time |
08:07 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-08-08 |
Time |
08:07 |
Sent To |
|
|
Notes |
2001-08-08 00:00:00 | 1) BUILDING CODE ANALYSIS BOX INDICATES | | 250 FEET FOR TRAVEL DISTANCE. THE | | PREVAILING FIRE CODE ALLOWS 150 FEET | | MAXIMUM IN SPRINKLER PROTECTED | | MERCANTILE OCCUPANCIES. | | 2) GENERAL NOTES INDICATES BUCKS COUNTY, | | STATE OF PENNSYLVANIA. PROJECT IS | | LOCATED IN PALM BEACH COUNTY, STATE OF | | FLORIDA. | | 3) PROVIDE SEPARATE PLANS AND PERMITS | | FOR FIRE ALARM SYSTEM REMODEL. | | 4) EXITING PERMITTED THRU STOCKROOM IF | | THE FOLLOWING CONDITIONS EXIST: DOOR | | TO STOCKROOM IS NOT LOCKED, AN AISLE OF | | AT LEAST 44" WIDE IS PROVIDED AND | | MAINTAINED. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2001-09-12 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-09-12 |
Time |
14:03 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2001-09-12 |
Time |
09:46 |
Sent To |
|
|
Notes |
2001-09-12 00:00:00 | *******************PROVISO************** | | | | | | AUXILIARY DRAIN PAN SHALL HAVE MEANS OF | | OVERFLOW PROTECTION BY A SEPARATE DRAIN | | LINE EXENDED FROM PAN AND TERMINATING AT | | A CONSPICUOUS POINT TO SERVE AS AN | | ALARM THAT THE REGULAR DRAIN IS | | RESTRICTED OR PROTECTION BY MEANS OF A | | FLOAT SWITCH. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
C |
Date |
2001-08-23 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2001-08-23 |
Time |
08:29 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
2001-08-23 |
Time |
08:29 |
Sent To |
|
|
Notes |
2001-08-23 00:00:00 | PROVISO: | | 1. AIR HANDLING EQUIPMENT SHALL BE | | LOCATED WITH RESPECT TO BUILDING | | CONSTRUCTION TO ALLOW FOR SERVICE AND | | REMOVAL OF COMPONENTS, | | 2. OVERFLOW PROTECTION SHALL BE | | PROVIDED. | | 3. COPPER CHILLED WATER LINES | | SHALL BE BRAZED PER 1997 SMC TABLE 1205. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2001-09-06 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-09-06 |
Time |
17:35 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2001-09-06 |
Time |
17:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-08-22 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-08-22 |
Time |
15:01 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2001-08-22 |
Time |
15:01 |
Sent To |
|
|
Notes |
2001-08-22 00:00:00 | DENIED | | REFERENCES SPC-94/FACBC-97 | | | | 1) DRINKING FOUNTAIN REQUIRED PER SPC-97 | | TABLE 407. MUST COMPLY WITH FACBC-97 | | SECT. 4.15 | | | | 2) PER FACBC-97 SEC. 4.17.3 EXCEPTION | | FOR NEW CONSTRUCTION #2 ACCESSABLE W/C | | SHALL BE LOCATED IN THE CORNER, DIAGONAL | | TO THE DOOR. | | | | 3) W/C'S TO COMPLY WITH FACBC-97 SEC. | | 4.16 | | | | 4) LAVS. TO COMPLY WITH FACBC-97 SEC. | | 4.19 | | | | 5) FITTING ROOM BENCHES TO COMPLY WITH | | FACBC-97 4.35.4 | | | | 6) SBC-97 1204.2 WALLS IN RESTROOMS TO | | BE LINED WITH NONABSORBENT MATERIAL. | | PLEASE SHOW DETAILS. | | | | 7) PAGE P-2 "G" PIPE AND MATERIALS, AND | | "J" FIXTURE STOP AND AIR CHAMBERS, AIR | | CHAMBERS TO COMPLY WITH SPC-94 607.8.2 | | AND 607.8.3. | | | | 8) PAGE P-2 - PLUMBING GENERAL NOTES. | | CONNECTION TO LANDLORDS PLUMBING SYSTEM, | | #13 WATER HAMMER ARRESTORS TO BE INSTALL | | ED IN COMPLIANCE WITH MANUFACTURES IN- | | STALLATION INSTRUCTIONS. | | | | 9) PAGE P-2 - HANGER ROD SPACING. HANGER | | SPACING TO BE ACCORDING TO SPC-94 SEC. | | 310.3 | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT. 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2001-08-24 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2001-08-24 |
Time |
14:43 |
Rev Time |
0.00 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|