Plan Review Details - Permit 01080287
Plan Review Stops For Permit 01080287
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-11-13 Cont ID  
Sent By jwitmer Date 2001-11-13 Time 11:05 Rev Time 1.00
Received By jwitmer Date 2001-11-13 Time 11:05 Sent To  
Notes
2001-11-13 00:00:00PRODUCT APP 11/13/01 WINDOW/ DOORJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-09-14 Cont ID  
Sent By jwitmer Date 2001-09-14 Time 09:24 Rev Time 1.99
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-08-14 Cont ID  
Sent By jwitmer Date 2001-08-14 Time 17:49 Rev Time 1.50
Received By jwitmer Date 2001-08-14 Time 17:49 Sent To  
Notes
2001-08-14 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01080287
 700 S ROSEMARY #106
 "PLAN REVIEW"
 SBC= STANDARD BUILDING CODE (1997)
 FL ACC CODE= FLORIDA ACCESSIBILITY CODE
  
 1)- SHEET A-1 BLOCKING ALL WOOD USED IN
 WALLS ARE TO BE NON-COMBUSTIBLE OR FRT
 FIRE RETARDANT TREATED SBC 609.22.1
 SHEET A-6 HEADERS / JAMBS FRT WOOD.
 2)- SHEET A-2 DETAIL #1 SPACING OF METAL
 HIGH HAT NOT GIVEN, NOR IS THE SPACING
 OF THE C-CHANNEL. SPACING OF THE HANGER
 WIRE OR GAUGE. TYPE OF FASTENER TO DECK
 ABOVE?
  
 3)- SHEET A-2 DETAIL # 1 & 3 DO NOT GIVE
 THE ANCHORING OF THE TOP PLATE OR THE
 SPACING OF THE STUDS.
  
 4)_ SHEET A-6 SBC 1204.2 REQUIRES A NON-
 ABSORBANT MATERIAL ON FLOORS AND WALLS
 TO A HEIGTH OF 4'-0" IN PUBLIC RESTROOMS
  
 5)- SBC 1001.1.2 SHOW MEANS OF EGRESS
 THROUGH OUT THE TENANT SPACE INDICATE
 THE 44" ACCESS (MINIMUM). STORAGE AREAS
 THOUGH NOT PROHIBITED AS A COMPONENT OF
 A MEANSOF EGRESS, REQUIRE SPECIAL
 CONSIDERATION. IT IS CRITICAL THAT THE
 REQUIRED MEANS OF EGRESS BE DESIGNATED &
 MAINTAINED TO INSURE THAT OBSTRUCTIONS
 ARE ELIMINATED. SPECIAL MARKINGS OR RAIL
 INGS OR SCREENS MAY BE USED TO SEPERATE
 THE DESIGNATED MEANS OF EGRESS FROM THE
 STORAGE USE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-09-11 Cont ID  
Sent By dpalmer Date 2001-09-11 Time 10:06 Rev Time 0.00
Received By dpalmer Date 2001-09-10 Time 22:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-21 Cont ID  
Sent By dpalmer Date 2001-08-21 Time 22:45 Rev Time 0.00
Received By dpalmer Date 2001-08-21 Time 22:45 Sent To  
Notes
2001-08-21 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 IT IS SHOWN ON PANELS AS?? PLEASE NOTE
 RATINGS ARE REQ`D FOR ALL.215-5
  
 2)NOTE: PLEASE NOTE THAT UNDER CITY OF
 WEST PALM BEACH LOCAL AMENDMENTS, OUTLET
 SPACING AT EVERY 20' OF UNENCUMBERED
 WALL SPACE INCLUDING STORAGE/STOCK AREA.
 210-50
 3)NOTE: PLEASE SUBMIT CLARIFICATION ON
 GROUNDING OF TRANSFORMER PER 250-30.
  
 4)NOTE: PLEASE ALSO NOTE PER LOCAL
 AMENDMENTS, COLOR CODING OF 277/480V
 IS BROWN/PURPLE/YELLOW PER ART215 OF
 LOCAL AMEND.
  
 5)NOTE: PLEASE NOTE THAT ALL CONTINUOUS]
 LOADS NEED TO BE SHOWN PER 215-3 AND
 230-42. PLEASE ALSO NOTE THAT LOAD
 CALCUALTIONS NEED TO BE COMPLETED AND
 SHOWN. PER 215-5
  
 6)NOTE: PLEASE SEE A-0, PLEASE NOTE
 THAT PLANS REFERENCE THE 1996 NEC.
 PLEASE NOTE THAT WE ARE UNDER THE 99 NEC
 PLEASE ALSO NOTE THAT GENERAL NOTES ON
 SAME PAGE MENTION THAT ALL WORK TO
 COMPLY WITH "BUCKS COUNTY" PA.
 PLEASE CORRECT.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-08-24 Cont ID  
Sent By lsmith Date 2001-08-24 Time 14:43 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-09-14 Cont ID  
Sent By jwitmer Date 2001-09-14 Time 07:20 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-09-14 00:00:00FIRE: PER MEC WPBFR8/29/01

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-08 Cont ID  
Sent By mcarsill Date 2001-08-08 Time 08:07 Rev Time 0.00
Received By mcarsill Date 2001-08-08 Time 08:07 Sent To  
Notes
2001-08-08 00:00:001) BUILDING CODE ANALYSIS BOX INDICATES
 250 FEET FOR TRAVEL DISTANCE. THE
 PREVAILING FIRE CODE ALLOWS 150 FEET
 MAXIMUM IN SPRINKLER PROTECTED
 MERCANTILE OCCUPANCIES.
 2) GENERAL NOTES INDICATES BUCKS COUNTY,
 STATE OF PENNSYLVANIA. PROJECT IS
 LOCATED IN PALM BEACH COUNTY, STATE OF
 FLORIDA.
 3) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE ALARM SYSTEM REMODEL.
 4) EXITING PERMITTED THRU STOCKROOM IF
 THE FOLLOWING CONDITIONS EXIST: DOOR
 TO STOCKROOM IS NOT LOCKED, AN AISLE OF
 AT LEAST 44" WIDE IS PROVIDED AND
 MAINTAINED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-09-12 Cont ID  
Sent By pkrauss Date 2001-09-12 Time 14:03 Rev Time 0.45
Received By pkrauss Date 2001-09-12 Time 09:46 Sent To  
Notes
2001-09-12 00:00:00*******************PROVISO**************
  
  
 AUXILIARY DRAIN PAN SHALL HAVE MEANS OF
 OVERFLOW PROTECTION BY A SEPARATE DRAIN
 LINE EXENDED FROM PAN AND TERMINATING AT
 A CONSPICUOUS POINT TO SERVE AS AN
 ALARM THAT THE REGULAR DRAIN IS
 RESTRICTED OR PROTECTION BY MEANS OF A
 FLOAT SWITCH.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status C Date 2001-08-23 Cont ID  
Sent By ndenmark Date 2001-08-23 Time 08:29 Rev Time 0.33
Received By ndenmark Date 2001-08-23 Time 08:29 Sent To  
Notes
2001-08-23 00:00:00PROVISO:
 1. AIR HANDLING EQUIPMENT SHALL BE
 LOCATED WITH RESPECT TO BUILDING
 CONSTRUCTION TO ALLOW FOR SERVICE AND
 REMOVAL OF COMPONENTS,
 2. OVERFLOW PROTECTION SHALL BE
 PROVIDED.
 3. COPPER CHILLED WATER LINES
 SHALL BE BRAZED PER 1997 SMC TABLE 1205.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-09-06 Cont ID  
Sent By kstevens Date 2001-09-06 Time 17:35 Rev Time 0.50
Received By kstevens Date 2001-09-06 Time 17:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-22 Cont ID  
Sent By kstevens Date 2001-08-22 Time 15:01 Rev Time 0.00
Received By kstevens Date 2001-08-22 Time 15:01 Sent To  
Notes
2001-08-22 00:00:00DENIED
 REFERENCES SPC-94/FACBC-97
  
 1) DRINKING FOUNTAIN REQUIRED PER SPC-97
 TABLE 407. MUST COMPLY WITH FACBC-97
 SECT. 4.15
  
 2) PER FACBC-97 SEC. 4.17.3 EXCEPTION
 FOR NEW CONSTRUCTION #2 ACCESSABLE W/C
 SHALL BE LOCATED IN THE CORNER, DIAGONAL
 TO THE DOOR.
  
 3) W/C'S TO COMPLY WITH FACBC-97 SEC.
 4.16
  
 4) LAVS. TO COMPLY WITH FACBC-97 SEC.
 4.19
  
 5) FITTING ROOM BENCHES TO COMPLY WITH
 FACBC-97 4.35.4
  
 6) SBC-97 1204.2 WALLS IN RESTROOMS TO
 BE LINED WITH NONABSORBENT MATERIAL.
 PLEASE SHOW DETAILS.
  
 7) PAGE P-2 "G" PIPE AND MATERIALS, AND
 "J" FIXTURE STOP AND AIR CHAMBERS, AIR
 CHAMBERS TO COMPLY WITH SPC-94 607.8.2
 AND 607.8.3.
  
 8) PAGE P-2 - PLUMBING GENERAL NOTES.
 CONNECTION TO LANDLORDS PLUMBING SYSTEM,
 #13 WATER HAMMER ARRESTORS TO BE INSTALL
 ED IN COMPLIANCE WITH MANUFACTURES IN-
 STALLATION INSTRUCTIONS.
  
 9) PAGE P-2 - HANGER ROD SPACING. HANGER
 SPACING TO BE ACCORDING TO SPC-94 SEC.
 310.3
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-08-24 Cont ID  
Sent By lsmith Date 2001-08-24 Time 14:43 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***