Plan Review Details - Permit 01080081
Plan Review Stops For Permit 01080081
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2001-11-20 Cont ID  
Sent By pkrauss Date 2001-11-20 Time 13:29 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
2001-11-20 00:00:00PLATFORM SUBMITTED WITH LAST FAILED
 REVISION WAS REMOVED FROM PLAN....WAS
 NOT REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-11-02 Cont ID  
Sent By lmartine Date 2001-11-02 Time 09:30 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2001-11-02 00:00:00 
 BUILDING COMMENTS
 -----------------
  
 1]
 LOCATE SHAFT WALL.
 2]
 SBC 2309.2.4 REQUIRES ADDITIONAL
 ENGINEERING FOR ADDITIONAL LOADING TO
 EXISTINGTRUSSES.
 3]
 EXPLAIN FURTHER IN DETAIL, PLATFORM
 CONSTRUCTION, ACCESS AND HARDWARE.
  
  
 LUIS MARTINEZ
 659-8096
 #8456

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2001-11-20 Cont ID  
Sent By mcarsill Date 2001-11-20 Time 12:56 Rev Time 0.00
Received By mcarsill Date 2001-11-20 Time 12:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2001-11-15 Cont ID  
Sent By mcarsill Date 2001-11-15 Time 15:16 Rev Time 0.00
Received By mcarsill Date 2001-11-15 Time 15:16 Sent To  
Notes
2001-11-15 00:00:001) NO CLEAN-OUTS PROVIDED WHEN EXHUAST
 DUCT CHANGES DIRECTION.
 2) PLEASE INDICATE SLOPE OF EXHUAST
 DUCT.
 3) MINIMUM DISTANCES MUST BE 10 FEET
 FROM PROPERTY LINES, OTHER BUILDINGS,
 ETC.
 4) PLEASE EXPLAIN DUCT INSTALLATION
 ON SIDE VIEW AND ELEVATION VIEWS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2001-10-30 Cont ID  
Sent By mcarsill Date 2001-10-30 Time 09:22 Rev Time 0.00
Received By mcarsill Date 2001-10-30 Time 09:22 Sent To  
Notes
2001-10-30 00:00:001) NO PRODUCT APPROVAL INFORMATION
 PROVIDED FOR "JOHNS-MANVILLE
 FIREBOARD. PLEASE PROVIDE INFORMATION.
 2) ROOF TERMINATIONS SHALL PROVIDE
 AT LEAST 10 FEET CLEARANCE TO SEPARATE
 BUILDINGS, PROPERTY LINES, ETC.
 3) NO MAKE-UP AIR INFORMATION PROVIDED
 WITH PLANS.
 4) ONE HOUR SHAFT WALL IS LOCATED
 WHERE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-09-05 Cont ID  
Sent By mcarsill Date 2001-09-05 Time 10:56 Rev Time 0.00
Received By mcarsill Date 2001-09-05 Time 10:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-08-28 Cont ID  
Sent By mcarsill Date 2001-08-28 Time 15:38 Rev Time 0.00
Received By mcarsill Date 2001-08-28 Time 15:38 Sent To  
Notes
2001-08-28 00:00:001) WRONG SUBMITTAL DATA PROVIDED WITH
 PLANS. PAPERWORK PROVIDED FOR FIREWRAP
 WAS SPECIFICALLY FOR WRAPPING PIPE NOT
 DUCTWORK. PLEASE PROVIDE THE APPROPRIATE
 PAPERWORK.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-03 Cont ID  
Sent By mcarsill Date 2001-08-03 Time 16:00 Rev Time 0.00
Received By mcarsill Date 2001-08-03 Time 16:00 Sent To  
Notes
2001-08-03 00:00:001) NO DETAILS FOR 3M FIREWRAP PLANNED
 FOR USE. PRODUCT APPROVALS REQUIRED
 FOR MATERIAL IF SHOWN ON THE PLANS.
 2) ANSWER MECHANICAL CODE QUESTIONS
 WITH REGARDS TO PLANS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2001-11-20 Cont ID  
Sent By pkrauss Date 2001-11-20 Time 13:26 Rev Time 0.40
Received By pkrauss Date 2001-11-20 Time 13:26 Sent To  
Notes
2001-11-20 00:00:00PROVISO -
  
 TEST AND BALANCE REQUIRED FOR FINAL
 INSPECTION.
  
 AIR VELOCITY WITHIN THE DUCT SYSTEM OF
 NOT LESS THAN 1,500 FT. PER MINUTE.
 1997 SMC 505.7

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2001-11-15 Cont ID  
Sent By ndenmark Date 2001-11-15 Time 15:48 Rev Time 0.50
Received By ndenmark Date 2001-11-15 Time 15:48 Sent To  
Notes
2001-11-15 00:00:00DENIED
 1. PROVIDE SHAFT DETAIL SHOWING REQUIRED
 6" CLEARANCE FROM DUCT TO INTERIOR OF
 ENCLOSURE
 2. SHOW LOCATION OF CLEANOUTS
 3. ROOF PITCH OF 4:12 OR MORE REQUIRE
 LEVEL PLATFORM FOR SERVICE. SEE 1997
 SMC 304.6
 4. PROVIDE LISTING OF HOOD OR COMPLIANCE
 WITH 504.2 1997 SMC

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2001-10-30 Cont ID  
Sent By pkrauss Date 2001-10-30 Time 15:43 Rev Time 0.45
Received By pkrauss Date 2001-10-30 Time 15:43 Sent To  
Notes
2001-10-30 00:00:00*******************DENIED***************
  
  
 PLEASE SUBMIT THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.INDICATE LOCATION OF SHAFT.
  
 2.CLEANOUTS/ACCESS DOORS NOT INDICATED
 ON PLAN AS PER 1997 SMC 505.5.1.
  
 3.PLAN SHEET 2 OF 3, SUPPLY DUCT
 LOOKS TO BE IN THE TRUSS AREA.
 PLEASE CLARIFY.
  
 4.PLEASE INDICATE HOW GREASE DUCT IS
 BEING SUPPORTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-09-05 Cont ID  
Sent By pkrauss Date 2001-09-05 Time 10:24 Rev Time 0.30
Received By pkrauss Date 2001-09-05 Time 10:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-08-28 Cont ID  
Sent By pkrauss Date 2001-08-28 Time 15:06 Rev Time 0.35
Received By pkrauss Date 2001-08-28 Time 15:06 Sent To  
Notes
2001-08-28 00:00:00SUBMITTED 3M FIREMASTER WRAP FOR
 PLASTICPIPE.WRONG APPLICATION NEED 3M
 FIREMASTER WRAP TO GREASE DUCT
 APPLICATION.
  
 CALLED CONTRACTOR (STEVE) WILL BRING COR
 RECT SUBMITTAL DATA 8-29-01.PHK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-02 Cont ID  
Sent By pkrauss Date 2001-08-02 Time 15:43 Rev Time 0.45
Received By pkrauss Date 2001-08-02 Time 15:43 Sent To  
Notes
2001-08-02 00:00:00*******************DENIED***************
  
  
 EF-1 ON ROOF - ROOF SLOPE IS INDICATED
 AS HAVING A SLOPE GREATER THAN 4:12
 SHALL HAVE A LEVEL WORKING PLATFORM NOT
 LESS THAN 30" AND COMPLY WITH 1997 SMC
 304.6.2.
  
 EF-1 SHALL COMPLY WITH 1997 SMC 506.1,
 SHALL BE LOCATED 10' FROM ADJACENT
 BUILDING, PARKING AREA, ADJACENT
 PROPERTY LINE, OR AIR INTAKE.
  
 PLEASE CLARIFY SF-1, AS TO LOCATION OF
 DUCT WORK FROM FAN TO CEILING DIFFUSER.
 PLAN 2 OF 2 LOOKS AS IF FAN HAS A CURB
 BUT THERE IS NOTHING INDICATING WHERE
 THE PENETRATION IS AT. IS DUCT UNDER
 ROOF OR ON TOP?
  
 PLEASE SUBMIT MANUFACTURER DATA ON 3M
 FIREWRAP.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.