Plan Review Stops For Permit 01080081 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
N |
Date |
2001-11-20 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-11-20 |
Time |
13:29 |
Rev Time |
0.05 |
Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-11-20 00:00:00 | PLATFORM SUBMITTED WITH LAST FAILED | | REVISION WAS REMOVED FROM PLAN....WAS | | NOT REQUIRED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2001-11-02 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2001-11-02 |
Time |
09:30 |
Rev Time |
1.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-11-02 00:00:00 | | | BUILDING COMMENTS | | ----------------- | | | | 1] | | LOCATE SHAFT WALL. | | 2] | | SBC 2309.2.4 REQUIRES ADDITIONAL | | ENGINEERING FOR ADDITIONAL LOADING TO | | EXISTINGTRUSSES. | | 3] | | EXPLAIN FURTHER IN DETAIL, PLATFORM | | CONSTRUCTION, ACCESS AND HARDWARE. | | | | | | LUIS MARTINEZ | | 659-8096 | | #8456 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
6 |
Status |
P |
Date |
2001-11-20 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-11-20 |
Time |
12:56 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-11-20 |
Time |
12:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
5 |
Status |
F |
Date |
2001-11-15 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-11-15 |
Time |
15:16 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-11-15 |
Time |
15:16 |
Sent To |
|
|
Notes |
2001-11-15 00:00:00 | 1) NO CLEAN-OUTS PROVIDED WHEN EXHUAST | | DUCT CHANGES DIRECTION. | | 2) PLEASE INDICATE SLOPE OF EXHUAST | | DUCT. | | 3) MINIMUM DISTANCES MUST BE 10 FEET | | FROM PROPERTY LINES, OTHER BUILDINGS, | | ETC. | | 4) PLEASE EXPLAIN DUCT INSTALLATION | | ON SIDE VIEW AND ELEVATION VIEWS. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
F |
Date |
2001-10-30 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-10-30 |
Time |
09:22 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-10-30 |
Time |
09:22 |
Sent To |
|
|
Notes |
2001-10-30 00:00:00 | 1) NO PRODUCT APPROVAL INFORMATION | | PROVIDED FOR "JOHNS-MANVILLE | | FIREBOARD. PLEASE PROVIDE INFORMATION. | | 2) ROOF TERMINATIONS SHALL PROVIDE | | AT LEAST 10 FEET CLEARANCE TO SEPARATE | | BUILDINGS, PROPERTY LINES, ETC. | | 3) NO MAKE-UP AIR INFORMATION PROVIDED | | WITH PLANS. | | 4) ONE HOUR SHAFT WALL IS LOCATED | | WHERE. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2001-09-05 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-09-05 |
Time |
10:56 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-09-05 |
Time |
10:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2001-08-28 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-08-28 |
Time |
15:38 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-08-28 |
Time |
15:38 |
Sent To |
|
|
Notes |
2001-08-28 00:00:00 | 1) WRONG SUBMITTAL DATA PROVIDED WITH | | PLANS. PAPERWORK PROVIDED FOR FIREWRAP | | WAS SPECIFICALLY FOR WRAPPING PIPE NOT | | DUCTWORK. PLEASE PROVIDE THE APPROPRIATE | | PAPERWORK. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2001-08-03 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-08-03 |
Time |
16:00 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-08-03 |
Time |
16:00 |
Sent To |
|
|
Notes |
2001-08-03 00:00:00 | 1) NO DETAILS FOR 3M FIREWRAP PLANNED | | FOR USE. PRODUCT APPROVALS REQUIRED | | FOR MATERIAL IF SHOWN ON THE PLANS. | | 2) ANSWER MECHANICAL CODE QUESTIONS | | WITH REGARDS TO PLANS. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
6 |
Status |
P |
Date |
2001-11-20 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-11-20 |
Time |
13:26 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2001-11-20 |
Time |
13:26 |
Sent To |
|
|
Notes |
2001-11-20 00:00:00 | PROVISO - | | | | TEST AND BALANCE REQUIRED FOR FINAL | | INSPECTION. | | | | AIR VELOCITY WITHIN THE DUCT SYSTEM OF | | NOT LESS THAN 1,500 FT. PER MINUTE. | | 1997 SMC 505.7 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
F |
Date |
2001-11-15 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2001-11-15 |
Time |
15:48 |
Rev Time |
0.50 |
Received By |
ndenmark |
Date |
2001-11-15 |
Time |
15:48 |
Sent To |
|
|
Notes |
2001-11-15 00:00:00 | DENIED | | 1. PROVIDE SHAFT DETAIL SHOWING REQUIRED | | 6" CLEARANCE FROM DUCT TO INTERIOR OF | | ENCLOSURE | | 2. SHOW LOCATION OF CLEANOUTS | | 3. ROOF PITCH OF 4:12 OR MORE REQUIRE | | LEVEL PLATFORM FOR SERVICE. SEE 1997 | | SMC 304.6 | | 4. PROVIDE LISTING OF HOOD OR COMPLIANCE | | WITH 504.2 1997 SMC |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
F |
Date |
2001-10-30 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-10-30 |
Time |
15:43 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2001-10-30 |
Time |
15:43 |
Sent To |
|
|
Notes |
2001-10-30 00:00:00 | *******************DENIED*************** | | | | | | PLEASE SUBMIT THE FOLLOWING INFORMATION | | FOR REVIEW. | | | | 1.INDICATE LOCATION OF SHAFT. | | | | 2.CLEANOUTS/ACCESS DOORS NOT INDICATED | | ON PLAN AS PER 1997 SMC 505.5.1. | | | | 3.PLAN SHEET 2 OF 3, SUPPLY DUCT | | LOOKS TO BE IN THE TRUSS AREA. | | PLEASE CLARIFY. | | | | 4.PLEASE INDICATE HOW GREASE DUCT IS | | BEING SUPPORTED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2001-09-05 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-09-05 |
Time |
10:24 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2001-09-05 |
Time |
10:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2001-08-28 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-08-28 |
Time |
15:06 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2001-08-28 |
Time |
15:06 |
Sent To |
|
|
Notes |
2001-08-28 00:00:00 | SUBMITTED 3M FIREMASTER WRAP FOR | | PLASTICPIPE.WRONG APPLICATION NEED 3M | | FIREMASTER WRAP TO GREASE DUCT | | APPLICATION. | | | | CALLED CONTRACTOR (STEVE) WILL BRING COR | | RECT SUBMITTAL DATA 8-29-01.PHK |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2001-08-02 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-08-02 |
Time |
15:43 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2001-08-02 |
Time |
15:43 |
Sent To |
|
|
Notes |
2001-08-02 00:00:00 | *******************DENIED*************** | | | | | | EF-1 ON ROOF - ROOF SLOPE IS INDICATED | | AS HAVING A SLOPE GREATER THAN 4:12 | | SHALL HAVE A LEVEL WORKING PLATFORM NOT | | LESS THAN 30" AND COMPLY WITH 1997 SMC | | 304.6.2. | | | | EF-1 SHALL COMPLY WITH 1997 SMC 506.1, | | SHALL BE LOCATED 10' FROM ADJACENT | | BUILDING, PARKING AREA, ADJACENT | | PROPERTY LINE, OR AIR INTAKE. | | | | PLEASE CLARIFY SF-1, AS TO LOCATION OF | | DUCT WORK FROM FAN TO CEILING DIFFUSER. | | PLAN 2 OF 2 LOOKS AS IF FAN HAS A CURB | | BUT THERE IS NOTHING INDICATING WHERE | | THE PENETRATION IS AT. IS DUCT UNDER | | ROOF OR ON TOP? | | | | PLEASE SUBMIT MANUFACTURER DATA ON 3M | | FIREWRAP. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|