Plan Review Details - Permit 01080067
Plan Review Stops For Permit 01080067
Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-08 Cont ID  
Sent By kstevens Date 2001-08-08 Time 13:51 Rev Time 1.25
Received By kstevens Date 2001-08-08 Time 13:51 Sent To  
Notes
2001-08-08 00:00:00DENIED..
  
 1) GAS PERMIT APPLICATION REQUIREMENT
 SHEET #4. SHOW TYPE OF MATERIAL. BTU
 VALUES ARE DIFFERENT FROM NUMBERS BY
 UNITS (FIXTURES), TO NUMBERS AT LIST
 WHERE THEY WERE ADDED. PLEASE CLEARIFY.
  
 2) INDICATE DELIVERY PRESSURE.
  
 3) SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT.
  
 4) SHOW LOCATION OF SECOND STAGE REGU-
 LATOR IF TWO POUND SYSTEM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377