Plan Review Details - Permit 01080047
Plan Review Stops For Permit 01080047
Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-10-01 Cont ID  
Sent By pkrauss Date 2001-10-01 Time 12:14 Rev Time 1.00
Received By pkrauss Date 2001-10-01 Time 12:10 Sent To  
Notes
2001-10-01 00:00:00******************PROVISO***************
  
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR WITH
 NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS. (1997 SMC
 406.1 AND NFPA 90A 4-4.4.2 OR 4-4.4.3)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-08-01 Cont ID  
Sent By ndenmark Date 2001-08-01 Time 13:18 Rev Time 0.25
Received By ndenmark Date 2001-08-01 Time 13:18 Sent To  
Notes
2001-08-01 00:00:00PER PLAN REVIEW ON 010510002