Plan Review Details - Permit 01071422
Plan Review Stops For Permit 01071422 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2001-08-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-08-20 |
Time |
20:26 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-08-20 |
Time |
20:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2001-08-21 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-08-21 |
Time |
12:56 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-08-21 |
Time |
12:56 |
Sent To |
|
|
Notes |
2001-08-21 00:00:00 | 1) BUILDING ADDRESSES REQUIRED. | | 2) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | TO,DURING AND AFTER CONSTRUCTION. | | 3) ELECTRIC POWERED SMOKE DETECTORS ARE | | REQUIRED. WHEN ACTIVATED, THESE DEVICES | | ARE TO BE AUDIBLE IN THE SLEEPING ROOMS | | OF THAT UNIT. | | 4) PORTABLE FIRE EXTINGUISHERS REQUIRED. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2001-09-20 |
|
|
Cont ID |
|
Sent By |
lhatten |
Date |
2001-09-20 |
Time |
19:27 |
Rev Time |
0.30 |
Received By |
lhatten |
Date |
2001-09-10 |
Time |
19:22 |
Sent To |
|
|
Notes |
2001-09-20 00:00:00 | OK PER PATTY KRAUSS 09/10/2001 | | OKED PER PATTY KRAUSS 09/10/2001 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2001-08-15 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2001-08-15 |
Time |
17:55 |
Rev Time |
0.33 |
Received By |
hmoser |
Date |
2001-08-15 |
Time |
17:55 |
Sent To |
|
|
Notes |
2001-08-15 00:00:00 | PLAN DENIED | | #1 NO MECHANICAL PLANS | | #2 NO ENERGY CALC | | PLAN REVIEW BY HAROLD MOSER | | [561] 659-8096 EXT.8390 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2001-09-18 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-09-18 |
Time |
12:28 |
Rev Time |
0.33 |
Received By |
kstevens |
Date |
2001-09-18 |
Time |
12:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-08-13 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-08-13 |
Time |
12:16 |
Rev Time |
1.00 |
Received By |
kstevens |
Date |
2001-08-13 |
Time |
12:16 |
Sent To |
|
|
Notes |
2001-08-13 00:00:00 | DENIED | | | | 1) PAGES 1A & 2 GENERAL NOTES #11 CHANGE | | TO READ FHA 1998 DESIGN MANUAL. | | | | 2) MODEL 1527 (L) & (R), M/B SHOWS 1'7" | | TO CENTER OF W/C. AND IT SHOULD BE 1'6" | | ALSO SHOW CLEAR FLOOR SPACE FOR LAV. | | PAGES 1A & 1B | | | | 3) IN BATH 2 SHOW CLEAR FLOOR SPACE FOR | | W/C AND LAV. PAGES 1A & 1B | | | | 4) MODEL 1409 (L) & (R), M/B SHOWS 1'7" | | TO CENTER OF W/C, AND IT SHOULD BE 1'6" | | ALSO SHOW CLEAR FLOOR SPACE FOR LAV. | | PAGES 1A & 1B | | | | 5) BATH 2 SHOWS 2'8" OPENING FOR W/C. | | 2'9" MINIMUM SPACE REQUIRED FOR W/C. | | ALSO SHOW CLEAR FLOOR SPACE FOR W/C AND | | LAV. PAGES 1A & 1B. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT. 8377 |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2001-09-19 |
|
|
Cont ID |
|
Sent By |
lhatten |
Date |
2001-09-19 |
Time |
20:04 |
Rev Time |
4.00 |
Received By |
lhatten |
Date |
2001-09-04 |
Time |
20:01 |
Sent To |
|
|
Notes |
2001-09-19 00:00:00 | REVIEW & STAMPED PLANS 09/04/2001 | | GOT WITH MICHELLE ON MECH & PLUMBING | | PROBLEMS TO BE CORRECTED PRIOR TO PERMIT | | BEING ISSUEDPER LOU HATTEN | | ALL SUB TRADES PROBLEMS -- BOTH MECH & | | PLUMBING RESOLVED09/19/2001 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2001-08-03 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2001-08-03 |
Time |
10:35 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|