Plan Review Details - Permit 01071271
Plan Review Stops For Permit 01071271
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-01-07 Cont ID  
Sent By jwitmer Date 2002-01-07 Time 18:46 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-09-24 Cont ID  
Sent By hpiskura Date 2001-09-24 Time 13:49 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-08-13 Cont ID  
Sent By hpiskura Date 2001-08-13 Time 14:43 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-08-13 00:00:00PLEASE PROVIDE A RECENT SURVEY AND A
 SITE PLAN.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 PROVIDE TEST REPORTS FOR THE WINDOWS,
 DOORS AND ROOF COVERING.
  
 PROVIDE A SEATING PLAN FOR THE CARDIAC
 THEATRE AND ALL OF THE DINING AREAS.
 SEE SBC 1003.1.2.
  
 SHOW THE MEANS OF ROOF DRAINAGE AND
 EMERGENCY OVERFLOW FOR THE NEW FLAT
 ROOF AREA.SEE SBC 1517.6.4.
  
 PROVIDE TWO EXITS FROM THE DINING AREA(S
 SEE SBC 1004.2.
  
 SHOW THE METHOD OF TRUSS CONNECTION TO
 THE EXISTING CONDITIONS AS WELL AS THE
 DESIGN LOADS INCLUDING THE ROOF TOP
 EQUIPMENT.SEE SBC 104.2.
  
 PROVIDE THREE COPIES OF ENERGY CODE
 CALCULATIONS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-12-26 Cont ID  
Sent By dpalmer Date 2001-12-26 Time 20:42 Rev Time 0.00
Received By dpalmer Date 2001-12-26 Time 20:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-09-19 Cont ID  
Sent By dpalmer Date 2001-09-19 Time 22:23 Rev Time 0.00
Received By dpalmer Date 2001-09-19 Time 22:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-13 Cont ID  
Sent By dpalmer Date 2001-08-13 Time 19:03 Rev Time 0.00
Received By dpalmer Date 2001-08-13 Time 19:03 Sent To  
Notes
2001-08-13 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT ALL BRANCH
 CIRCUIT #`S NEED TO BE SHOWN PLANS AND
 CORRELATE WITH SUBMITTED PANEL SCHEDULES
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR ADDING LOADS TO EXISTING.215-5
  
 3)NOTE: PLEASE CLARIFY EQUIPMNET GROUND-
 -ING METHOD. SIZE PER 250-122
  
 4)NOTE: PLEASE CLARIFY BONDING OF NEW
 FOOTER STEEL OF NEW ADDITION. 250-50
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-09-24 Cont ID  
Sent By hpiskura Date 2001-09-24 Time 07:41 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-12-27 Cont ID  
Sent By mcarsill Date 2001-12-27 Time 09:14 Rev Time 0.00
Received By mcarsill Date 2001-12-27 Time 09:14 Sent To  
Notes
2001-12-27 00:00:00SEPARATE PLANS AND PERMITS REQUIRED FOR
 THE HOOD, DUCT AND EXTINGUISHING
 SYSTEM.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-09-18 Cont ID  
Sent By mcarsill Date 2001-09-18 Time 08:05 Rev Time 0.00
Received By mcarsill Date 2001-09-18 Time 08:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-02 Cont ID  
Sent By mcarsill Date 2001-08-02 Time 15:50 Rev Time 0.00
Received By mcarsill Date 2001-08-02 Time 15:50 Sent To  
Notes
2001-08-02 00:00:001) PLEASE CLEARLY IDENTIFY ALL EXIT
 SIGN LOCATIONS.
 2) PLEASE CLEARLY IDENTIFY ALL
 EMERGENCY LIGHT FIXTURES LOCATIONS.
 3) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION.
 4) PLEASE PROVIDE A LIFE SAFETY PLAN
 AND AN OCCUPANT LOAD PLAN.
 5) ARE THERE ANY FIRE SPRINKLER OR FIRE
 ALARM EQUIPMENT PRESENT WITHIN THE
 BUILDING.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2002-01-11 Cont ID  
Sent By pkrauss Date 2002-01-07 Time 07:32 Rev Time 0.35
Received By pkrauss Date 2002-01-05 Time 11:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2001-12-20 Cont ID  
Sent By pkrauss Date 2001-12-20 Time 10:02 Rev Time 0.50
Received By pkrauss Date 2001-12-20 Time 10:01 Sent To  
Notes
2001-12-20 00:00:00 
 ADDITIONAL PLANS AND PERMIT REQUIRED FOR
 HOOD, FIRE SUPRESSION, AND WALK-IN
 COOLER.PLEASE PROVIDE MANUFACURER
 SUBMITTAL DATA/PRODUCT APPROVAL FOR THE
 FIRE WRAP.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-09-26 Cont ID  
Sent By pkrauss Date 2001-09-26 Time 09:40 Rev Time 0.45
Received By pkrauss Date 2001-09-26 Time 09:25 Sent To  
Notes
2001-09-26 00:00:00*******************PROVISO**************
  
  
 MANUFACUTURER SUBMITTAL AND INSTALLATION
 INFORMATION FOR THE CURB TO THE RTU'S
 SHALL BE ON THE JOBSITE WITH PLANS AT
 THE TIME OF INPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-13 Cont ID  
Sent By pkrauss Date 2001-08-13 Time 16:46 Rev Time 0.40
Received By ndenmark Date 2001-08-13 Time 16:46 Sent To  
Notes
2001-08-14 00:00:00PROVIDE INFORMATION ON CONDENSATE DRAIN
 LOCATION AND TERMINATION.(NOT ON ROOF)
  
 NO ENERGY EFFICIENCY VALUES SHOWN FOR
 AIR HANDLING EQUIPMENT. PROVIDE
 INFORMATION SHOWING COMPLIANCE WITH FL
 ENERGY CODE.
  
 PROVIDE CURB ATTACHMENT INFORMATION
 SHOWING COMPLIANCE WITH WIND LOAD
 (STRUCTURAL SHOWS RAILS NOT CURBS)
  
 EXHAUST PER ASHRAE 62-89 AND SMC
 503.3.2SHALL BE PROVIDED. PROVIDE
 INFORMATION ON FANS AND INSTALLATION
 DETAILS FOR SHOWER AREAS.
  
 CEILING PADDLE FANS TO BE MINIMUM 8 FOOT
 ABOVE FINISHED FLOOR PER SMC 404.3.2
  
 PROVIDE INFORMATION ON EQUIPMENT ACCESS
 ON ROOF. ELECTRIC FOR ROOF EQUIPMENT
 SHALL INCLUDE 115V GFIC OUTLET.
2001-08-13 00:00:00********************DENIED**************
  
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89.
  
 2.AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2.
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS AS PER
 1997 SMC 406.1 AND NFPA 90A 4-4.4.3.

Review Stop P PLUMBING
Rev No 4 Status F Date 2002-01-14 Cont ID  
Sent By kstevens Date 2002-01-14 Time 12:20 Rev Time 1.25
Received By kstevens Date 2002-01-14 Time 12:20 Sent To  
Notes
2002-01-14 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT K-PLUMB SANITARY RISER DIAGRAM,
 TRAP FOR CAN WASH TO BE UNDERGROUND, NOT
 ON STACK AS SHOWN
  
 2) RISER DIAGRAM, HORIZONTAL DRY VENT
 NOT APPROVED PER SPC SEC 906.2.1
  
 3) SEPARATE PLUMBING PERMIT REQUIRED
  
 4) SEPARATE GAS PERMIT REQUIRED. SEE
 ATTACHED GAS PERMIT REQUIREMENT SHEET
 FOR INFORMATION REQUIRED FOR GAS PLAN
 REVIEW.
  
 5) PLEASE SUBMIT KITCHEN EQUIPMENT IDENT
 IFICATION SHEET.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-10-02 Cont ID  
Sent By kstevens Date 2001-10-02 Time 10:15 Rev Time 1.00
Received By kstevens Date 2001-10-02 Time 10:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-09-26 Cont ID  
Sent By kstevens Date 2001-09-26 Time 17:17 Rev Time 1.25
Received By kstevens Date 2001-09-26 Time 17:17 Sent To  
Notes
2001-09-26 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97 - SMC-97
 1) PAGES D-1/A-6 PROVIDE SANITARY RISER
 DIAGRAM AND WATER RISER DIAGRAM FOR NEW
 SINKS.
 2) PAGES D-1/A-6 PLEASE PROVIDE INFOR-
 MATION FOR STEAM GENERATOR. WHAT IS THE
 STEAM FOR? PROVIDE PIPING INFORMATION.
 3) PAGES D-1/A-7 RELOCATION OF WATER
 HEATER. PREVIOUS PLAN REVIEW NOT ADDRES-
 SED. PLEASE SHOW INFORMATION ON WORKING
 PLATFORM, LIGHT, WALKWAK TO HEATER (MIN-
 IMUM 24" WIDE) AND ACCESS SIZE. PER
 SMC-97 SEC 304.4, SPC-94 SEC 501.7.
 4) PAGE A-7 PROVIDE DETAILS ON PAN, PAN
 DRAIN AND T&P DRAIN LINE FROM W/HEATER.
 SPC-94 SEC 507.8.1,2,2 AND 4.
 5) PAGE A-3 PLEASE PROVIDE ROOF DRAIN
 CALCULATIONS FOR ROOF DRAIN PER SPC-94
 SEC 1108. ALSO PROVIDE SECONDARY ROOF
 DRAIN CALCULATIONS USING SEC 1109.
 SHOW RISER DIAGRAMS FOR BOTH WITH ALL
 PIPE SIZES.
 6) PAGE A-6 PREVIOUS COMMENTS #1 AND #2
 FROM PLAN REVIEW DATED 8-9-01 WERE NOT
 ADDRESSED. PLEASE SHOW COMPLIANCE FOR
 DRESSING ROOMS PER FACBC SEC 4.35 THRU
 4.35.5. ALSO SHOW COMPLIANCE FOR SHOWERS
 PER FACBC SEC 4.21 THRU 4.21.4 AND FIG.
 35.
 7) PAGE A-6 WATER RISER DIAGRAM. PLEASE
 LOCATE WATER HAMMER ARRESTORS PER MANU-
 FACTURES INSTALLATION INSTRUCTIONS AND
 WH-PDI 201, NOT AT TOP OF DROP AS SHOWN.
 8) PAGE A-6 PLEASE PROVIDE CALCULATIONS
 FOR MINIMUM FIXTURES USING SPC-94 TABLE
 407. SHOW DETAILS OF ALL RESTROOMS, GIVE
 ROOM DIMENTIONS ECT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-09 Cont ID  
Sent By jleech Date 2001-08-09 Time 18:00 Rev Time 1.50
Received By jleech Date 2001-08-09 Time 18:00 Sent To  
Notes
2001-08-09 00:00:00DENIED;
  
 1.PAGE A-6 DRESSING ROOMS SHALL COMPLY
 WITH FACBC SEC. 4.35 THRU 4.35.5.
 2.SHOWER STALLS SHALL COMPLY WITH FACBC
 SEC. 4.21 THRU 4.21.4, ALSO SEE FIG.
 35.
 3.PAGE A-6 WHAT IS 2" PLUMBING DRAIN FOR
 SHOWER DRAIN IS 3" WHAT ELSE IS BEING
 ADDED?
 4.WATER HEATER MUST BE READILY ACCESS-
 IBLE. IF RELOCATED IN ATTIC A FIXED
 LADDERSHALL BE AVAILABLE AND A WORKING
 PLATFORM MUST BE IN PLACE WITH A LIGHT
 SPC SEC. 501.7.
 5.WATER HEATER PAN AND DRAIN SHALL
 COMPLY WITH SEC. 507.8.1,2,3, AND .4.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 1 Status P Date 2001-07-31 Cont ID  
Sent By sgraham Date 2001-07-31 Time 09:00 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-07-31 00:00:00NEED MINOR AMENDMENT & FORMAL SITE PLAN