Plan Review Details - Permit 01070803
Plan Review Stops For Permit 01070803
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-08-21 Cont ID  
Sent By mcarsill Date 2001-08-21 Time 11:54 Rev Time 0.00
Received By mcarsill Date 2001-08-21 Time 11:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-07-25 Cont ID  
Sent By mcarsill Date 2001-07-25 Time 15:53 Rev Time 0.00
Received By mcarsill Date 2001-07-25 Time 15:53 Sent To  
Notes
2001-07-25 00:00:001) PLEASE PROVIDE DETAILS ON 3M FIREWRAP
 PLANNED FOR USE. PLEASE PROVIDE
 MANUFACTURER'S INFORMATION WITH
 REGARDS TO PROPER INSTALLATION.
 2) A MINIMUM 10 FOOT SEPARATION IS
 REQUIRED BETWEEN EXHAUST AND SUPPLY AIR.
 3) WRONG PITCH NOTED ON PLANS FOR
 EXHAUST DUCT.
 4) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SUPPRESSION SYSTEM.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-08-21 Cont ID  
Sent By pkrauss Date 2001-08-21 Time 09:12 Rev Time 0.40
Received By pkrauss Date 2001-08-21 Time 09:12 Sent To  
Notes
2001-08-21 00:00:00PROVISO:MINIMUM OF 10' BETWEEN EXHAUST
 & FRESH AIR INTAKES.
  
 (ON PLAN)

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-07-18 Cont ID  
Sent By pkrauss Date 2001-07-18 Time 08:43 Rev Time 0.50
Received By pkrauss Date 2001-07-18 Time 08:43 Sent To  
Notes
2001-07-18 00:00:00********************DENIED**************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
  
 1.AS INDICATED ON PLAN SHEET #1,
 3M FIRE MASTER WRAP IS BEING
 INSTALLED.PLEASE SUBMIT 2 COPIES
 OF MANUFACTURER SUBMITTAL DATA AND
 INSTALLATION DETAILS.
  
 2.MANUFACTURER SUBMITTAL DATA/DETAIL
 ON HOOD.
  
 3.AS NOTED ON PLAN SHEET #2, 1/4" PER
 FOOT PITCH ON GREASE DUCT...THIS
 SHALL BE A MINIMUM OF 1" PER FOOT
 AS REQUIRED BY THE 1997 SMC 505.4.
  
 4.MINIMUM OF 10' BETWEEN EXHAUST
 AND AIR INTAKES, 1997 SMC 506.1.
  
 NOTE:ADDITIONAL PERMIT REQUIRED FOR
 FIRE SUPRESSION SYSTEM.PLEASE
 SUBMIT PLANS WITH PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.