Plan Review Details - Permit 01070803
Plan Review Stops For Permit 01070803 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2001-08-21 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-08-21 |
Time |
11:54 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-08-21 |
Time |
11:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2001-07-25 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-07-25 |
Time |
15:53 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-07-25 |
Time |
15:53 |
Sent To |
|
|
Notes |
2001-07-25 00:00:00 | 1) PLEASE PROVIDE DETAILS ON 3M FIREWRAP | | PLANNED FOR USE. PLEASE PROVIDE | | MANUFACTURER'S INFORMATION WITH | | REGARDS TO PROPER INSTALLATION. | | 2) A MINIMUM 10 FOOT SEPARATION IS | | REQUIRED BETWEEN EXHAUST AND SUPPLY AIR. | | 3) WRONG PITCH NOTED ON PLANS FOR | | EXHAUST DUCT. | | 4) SEPARATE PLANS AND PERMITS REQUIRED | | FOR FIRE SUPPRESSION SYSTEM. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2001-08-21 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-08-21 |
Time |
09:12 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2001-08-21 |
Time |
09:12 |
Sent To |
|
|
Notes |
2001-08-21 00:00:00 | PROVISO:MINIMUM OF 10' BETWEEN EXHAUST | | & FRESH AIR INTAKES. | | | | (ON PLAN) |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2001-07-18 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-07-18 |
Time |
08:43 |
Rev Time |
0.50 |
Received By |
pkrauss |
Date |
2001-07-18 |
Time |
08:43 |
Sent To |
|
|
Notes |
2001-07-18 00:00:00 | ********************DENIED************** | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | FOR REVIEW. | | | | | | 1.AS INDICATED ON PLAN SHEET #1, | | 3M FIRE MASTER WRAP IS BEING | | INSTALLED.PLEASE SUBMIT 2 COPIES | | OF MANUFACTURER SUBMITTAL DATA AND | | INSTALLATION DETAILS. | | | | 2.MANUFACTURER SUBMITTAL DATA/DETAIL | | ON HOOD. | | | | 3.AS NOTED ON PLAN SHEET #2, 1/4" PER | | FOOT PITCH ON GREASE DUCT...THIS | | SHALL BE A MINIMUM OF 1" PER FOOT | | AS REQUIRED BY THE 1997 SMC 505.4. | | | | 4.MINIMUM OF 10' BETWEEN EXHAUST | | AND AIR INTAKES, 1997 SMC 506.1. | | | | NOTE:ADDITIONAL PERMIT REQUIRED FOR | | FIRE SUPRESSION SYSTEM.PLEASE | | SUBMIT PLANS WITH PERMIT | | APPLICATION. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
|