Plan Review Details - Permit 01070708
Plan Review Stops For Permit 01070708
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-04-23 Cont ID  
Sent By btrobaug Date 2002-04-23 Time 17:39 Rev Time 0.00
Received By btrobaug Date 2002-04-23 Time 17:39 Sent To R
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-04-04 Cont ID  
Sent By dpalmer Date 2002-04-04 Time 06:38 Rev Time 0.00
Received By dpalmer Date 2002-04-04 Time 06:38 Sent To R
Notes
2002-04-04 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT NOTES FROM
 FIRST AND SECOND REVIEW ARE STILL NOT
 ADDRESSED????
  
 2)NOTE: PLEASE NOTE MISSING REQ`D BATH
 RECEPT PER 210-52D, ALSO ALL TO BE
 SHOWN AS GFI/GFI PROTECTED.210-8
  
 3)NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 4)NOTE: PLEASE NOTE THAT PANEL SCHEDULE
 AND LOAD CALCULATIONS,,,DO NOT CORRELATE
 PLEASE NOTE THAT THERE ARE MANY THINGS
 THAT DO NOT MATCH UP???
  
 5)NOTE: PLEASE NOTE THAT PLANS ARE NOTED
 THAT NO CENTRAL A/C IS EXISTING AND YET
 THEY ARE SHOWN ON LOAD CALCULATIONS?????
 PLEASE CLARIFY!!! IF NEW SHOW EQUIPMNET
 AND DISC`S PER 440-11.
 IF THERE IS NONE THEN PLEASE REMOVE.
  
 6)NOTE: PANEL IS SHOWN TO BE 125A AS
 EXISTING AND ALSO SHOWN AS 150A AS EXIST
 ING??? WHICH ONE. ALSO SHOWN AS 15A
 ABOVE LOAD CALCS.
  
 7)NOTE: PLEASE NOTE THAT BOTH SMALL
 APPLIANCE CIRCUITS ARE SHOWN AS 2000W`S
 PLEASE SEE 210-52B, 210-11C-1.
  
 8)NOTE: PLEASE NOTE THAT THERE IS
 NOTHING SHOWN FOR "HOW" DETACHED GARAGE
 IS FED??? MEANS OF DISC? 225-31,
 GROUNDING??250-32
  
 9)NOTE: PLEASE HAVE PLANS PLACED INTO
 TWO SET FOR REVIEW. PLEASE KEEP ALL OLD
 SETS SEPARATE. PLEASE DATE PLANS AS REQ`
 D.
 PLEASE CLARIFY PROVIDE INFORMATION ON
 PERSON WHO DREW PLANS. ARCH/OR DRAFTSMAN
 PLEASE NOTE THAT IF DONE BY AN ARCH,
 THEN PLANS MUST BE SIGNED AND SEALED BY
 THAT PERSON.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE NOTE ONCE AGAIN, IF THERE
 ARE ANY QUESTIONS,,,,,,, PLEASE CALL!!!!
 IF A MEETING IS NEEDED TO GO OVER PLANS
 AND CODE ISSUES,,,,, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-12-24 Cont ID  
Sent By dpalmer Date 2001-12-24 Time 15:20 Rev Time 0.00
Received By dpalmer Date 2001-12-24 Time 15:20 Sent To P
Notes
2001-12-24 00:00:00****************** UNSAT ***************
  
  
 1)NOTE: PLEASE NOTE THAT NOT ALL NOTES
 FROM FIRST REVIEW WERE ADDRESSED.
 PLANS NOT COMPLETE FOR SUFF ELECTRICAL
 REVIEW.
  
 PLEASE SUBMIT THE INFORMATION FROM FIRST
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-02 Cont ID  
Sent By dpalmer Date 2001-08-02 Time 18:25 Rev Time 0.00
Received By dpalmer Date 2001-08-02 Time 18:25 Sent To  
Notes
2001-08-02 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT RECEPTS IN GAR
 ARE TO BE GFI/GFI PROTECTED PER 210-8.
  
 2)NOTE: PLEASE SUBMIT INFORMATION FOR
 MEANS OF DISCONNECT AT DETACHED
 STRUCTURE.225-31
  
 3) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
 PLEASE SUBMIT A PANEL SCHEDULE FOR
 REQ`DCIRCUITS (EXISTING AND NEW)
  
 5)NOTE: PLEASE CLARIFY NEW A/C SHOWN ON
 RISER DIAGRAM? PLEASE SHOW ON PLANS AND
 PROVIDE A/C RECEPT AND DISC`S PER
 440-11AND 309.1 (MECH CODE)
  
 6) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 7) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
 MISSING REAR.
  
 PLEASE MAKE NOTE THAT IF THERE IS GOING
 TO BE ANY CATV AND/OR TELEPHONE IN NEW
 ADDITION, THEN IT NEEDS TO BE DRAWN ON
 PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2001-12-27 Cont ID  
Sent By ndenmark Date 2001-12-27 Time 07:42 Rev Time 0.25
Received By ndenmark Date 2001-12-27 Time 07:42 Sent To  
Notes
2001-12-27 00:00:00NO INFORMATION PROVIDED FOR MECH REVIEW
 SEPARATE PLANS AND PERMIT APPLICATON
 WILL BE REQUIRED PRIOR TO ANY MECH WORK
 BEING PERFORMED AT THIS ADDRESS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-07 Cont ID  
Sent By pkrauss Date 2001-08-07 Time 07:13 Rev Time 0.35
Received By pkrauss Date 2001-08-07 Time 07:01 Sent To  
Notes
2001-08-07 00:00:00******************DENIED****************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
  
 1.CFM DISTRIBUTION TO EACH SUPPLY
 GRILLE.
  
 2.CLARIFY LOCATION OF AHU...IS IT IN
 A CLOSET, ATTIC, HANGING, OR ON A
 STAND?
  
 3.PLEASE SUPPLY MATERIAL AND R-VALUE
 OF DUCT BEING USED.
  
 4.INDICATE CONDENSATE TERMINATION.
  
  
 NOTE:ANY ROOMS/AREAS WITH 300 CFM OR
 GREATER REQUIRE A RETURN AIR
 FROM THAT SPACE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-12-26 Cont ID  
Sent By dpalmer Date 2001-12-24 Time 15:44 Rev Time 0.33
Received By jleech Date 2001-12-26 Time 09:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-08-06 Cont ID  
Sent By kstevens Date 2001-08-06 Time 09:38 Rev Time 0.50
Received By kstevens Date 2001-08-06 Time 09:38 Sent To  
Notes
2001-08-06 00:00:00PROVISO
  
 SIGNED AND SEALED PLANS REQUIRE A TITLE
 BLOCK. PLEASE FURNISH TITLE BLOCK ON
 PLANS.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2002-04-24 Cont ID  
Sent By rmcdouga Date 2002-04-24 Time 15:58 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-04-24 00:00:00************BUILDING PROVISO************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2002-04-10 Cont ID  
Sent By btrobaug Date 2002-04-23 Time 17:40 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-04-10 00:00:00*************BUILDING UNSAT*************
  
 1) THE MINIMUM FOOTING THICKNESS OF A
 MONOLITHIC SLAB ON GRADE IS 20 INCHES
 PER SSTD 10-97 SECT. 303.3.1. PLEASE
 CORRECT.
  
 2) THE MINIMUM ANCHOR BOLT DIAMETER IS
 5/8" WITH A MINIMUM OF 7" EMBEDMENT. THE
 WASHERS ARE REQUIRED TO BE 3"X 3"X 1/8"
 PER SSTD 10-97 SECT. 303.3.2. PLEASE
 CORRECT.
  
 3) A DOUBLE LAYER OF 6X6 NO.10 WELDED
 WIRE FABRIC 3 FEET WIDE SHALL BE
 PROVIDED AROUND THE PERIMETER OF THE
 SLAB PER SSTD 10-97 SECT. 304.1.3.
  
 4) INDICATE THE LOCATION OF HOLDDOWN
 CONNECTORS REQUIRED AT THE EXTERIOR
 SHEAR WALLS PER SSTD 10-97 SECT.305.4.
  
 5) A MECHANICAL EXHAUST VENT TO THE
 EXTERIOR IS REQUIRED IN THE EXISTING
 BATHROOM IN WHICH THE WINDOW IS BEING
 REMOVED.
  
 6) THE WEST ELEVATION OF THE ADDITION
 DOES NOT COMPLY WITH TABLE 600 OF THE
 97 SBC FOR THE PERCENTAGE OF WALL AREA
 OPENINGS ALLOWED BASED ON THE INFO THAT
 WAS SUBMITTED. THE WALL AREA OF THE
 EXISTING STRUCTURE CAN BE USED IF THE
 OPENINGS (WINDOW, DOOR, ETC.) ARE
 INDICATED ON THE PLANS. TWENTY PERCENT
 OF THE WALL AREA (FLOOR TO CEILING HT.)
 IS ALLOWED AS OPENINGS BASED ON A
 DISTANCE OF 3'TO 10'TO THE PROPERTY
 LINE.
  
 7) THE SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN IS REQUIRED
 ON THE DRAWINGS PER CITY OF W.P.B.
 AMENDMENTS TO THE 97 SBC SECT. 104.2.1.
  
 8) THE NOTES FOR ROOF SHEATHING NAILING
 REQUIREMENTS ARE NOT CLEAR. IN ZONES 1&
 2 THE REQUIRED NAIL SPACING IS 6" O.C.
 ON THE EDGES AND 6"O.C. INTERMEDIATE. IN
 ZONE 3 THE NAIL SPACING IS 4"O.C. AT THE
 EDGES AND 6"O.C. INTERMEDIATE. SEE CITY
 OF WPB AMENDMENTS TO 97 SBC SECT. 2306.
 PLEASE CLARIFY.
  
 9)THE TOTAL NOMINAL THICKNESS FOR STUCCO
 ON METAL LATH OVER SOLID BASE IS 7/8"
 PER 97SBC SECT.2405.2.1 AND ASTM C 926.
 PLEASE CORRECT.
  
 10) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - STRUCTURAL WINDOW MULLIONS THAT WILL
 BE USED TO CONNECT WINDOWS IN ADDITION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-01-03 Cont ID  
Sent By rmcdouga Date 2002-01-03 Time 12:51 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-01-03 00:00:00*************BUILDING UNSAT*************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) INDICATE ON PLANS THE METHOD OF
 OF ATTACHMENT THAT WILL BE USED TO
 CONNECT THE WOOD FRAME WALLS OF THE
 ADDITION TO THE EXISTING STRUCTURE.
  
 4) PLEASE CLARIFY IF THE PLANS ARE TO BE
 CERTIFIED BY THE ENGINEER (JOHN HOLT) AS
 INDICATED BY THE DESIGN CERTIFICATION
 FORM THAT YOU SUBMITTED (NEEDS EMBOSSED
 SEAL) OR IS BEING DESIGNED TO COMPLY
 WITH SSTD 10-97, WHICH DOES NOT REQUIRE
 AN ARCHITECT OR ENGINEER.
  
 5) PROVIDE ENERGY CALCULATIONS FOR THE
 NEW ADDITION AS REQUIRED BY THE 1997
 FLORIDA ENERGY EFFICIENCY CODE SEC.
 101.2.2 AND 101.5.3.
  
 6) NOTES FOR GARAGE INDICATE 4:12 ROOF
 PITCH AND DRAWINGS INDICATE 3:12 PITCH.
 PLEASE CORRECT.
  
 7) ROOF SHEATHING IS REQUIRED TO BE
 NAILED 4" O.C. AT EDGES AND 6" O.C.
 INTERMEDIATE WITHIN 5' OF ROOF EDGE
 INCLUDING 1' OVERHANG AT GABLE ENDS
 (ZONE 3). CITY OF WPB AMENDMENTS TO
 97 SBC SEC. 2306.
  
 8) INDICATE ATTIC ACCESS FOR ADDITION
 AND GARAGE. 97 SBC 2309.6
  
 9) INDICATE THE TYPE AND SIZE OF THE TWO
 WINDOWS IN THE FLORIDA ROOM.
  
 10) PROVIDE ADDITIONAL COPIES OF ALL
 PRODUCT APPROVALS THAT WERE SUBMITTED.
 TWO COPIES ARE REQUIRED.
  
 11)PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS. REQUIRED
 FOR ALL EXTERIOR GLAZED OPENINGS ON
 NEW ADDITION AND GARAGE.
  
 12) PROVIDE TWO LEGIBLE COPIES OF SURVEY
 INDICATING THE FRONT, REAR AND SIDE
 SET BACKS TO THE ADDITION AND THE
 DETACHED GARAGE.
  
 13) THE BOTTOM OF THE FOOTING SHALL BE
 A MINIMUM OF 12" BELOW FINISH GRADE, AND
 AN APPROVED STUCCO STOP PLACED NOT LESS
 THAN 6" ABOVE FINISH GRADE IS REQUIRED
 TO TERMINATE THE STUCCO AT THE BASE OF
 THE WALL. PLEASE INDICATE THESE ITEMS ON
 THE PLANS.
  
 IF YOU HAVE QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-07-31 Cont ID  
Sent By rmcdouga Date 2001-07-31 Time 11:16 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-07-31 00:00:00*************BUILDING UNSAT*************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) THE ENGINEER'S TITLE BLOCK IS
 REQUIRED ON EACH SHEET OF THE PLANS
 THATARE SIGNED AND SEALED BY HIM.
  
 3) THE BUCK DETAILS AND WALL DETAIL ARE
 ILLEGIBLE. PLEASE PROVIDE PLANS THAT
 ARECLEAR AND READABLE.
  
 4) INDICATE METHODS OF ATTACHMENT FOR
 SECURING FRAME WALLS AND CONCRETE FOOT-
 INGS TO EXISTING STRUCTURE.
  
 5) PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL
 J)AS REQUIRED BY THE 1997 FLORIDA
 ENERGYEFFICIENCY CODE FOR BUILDING
 CONSTRUCTION.
  
 6) INDICATE SPECIAL ROOF SHEATHING
 NAILING ZONES COMPLYING WITH SECTION
 2306 OF THE CITY AMENDMENTS TO THE 97
 SBC.
  
 7) PROVIDE GABLE END BRACING DETAILS.
  
 8) INDICATE HOW ATTIC ACCESS TO NEW
 ADDITION WILL BE ACHIEVED.
  
 9) THE ROOF PLANS INDICATE # 11
 CONNECTORS FROM THE SCHEDULE FOR
 ATTACHING THE TRUSSES TO THE WALLS.
 THESE CONNECTORS ARE FOR WOOD TRUSS TO
 CONCRETE BEAM CONNECTIONS. PLEASE
 INDICATE THE APPROPRIATE CONNECTORS
 WHICH ARE CAPABLE OF WITHSTANDING THE
 CALCULATED LOADS.
  
 10) INDICATE THE POSITIVE AND NEGATIVE
 PRESSURES FOR ALL EXTERIOR WINDOW AND
 DOOR OPENINGS OF ADDITION AND DETACHED
 GARAGE.
  
 11) INDICATE THE SPECIFICATE TYPES OF
 CONNECTORS THAT WILL BE USED TO PROVIDE
 A CONTINOUS TIE FROM THE FOUNDATION TO
 THE ROOF.
  
 12) INDICATE THE TYPES AND SIZES OF THE
 WINDOWS AND DOORS ON THE PLANS.
  
 13) TABLE 600 IN THE 97 SBC IS USED TO
 DETERMINE THE PERCENTAGE OF WALL AREA
 THAT IS ALLOWED AS OPENINGS BASED ON
 THEDISTANCE TO THE PROPERTY LINE OR
 ASSUMEDPROPERTY LINE. PLEASE PROVIDE
 BOTH SIDE AND REAR ELEVATIONS FOR THE
 ADDITION ANDALL FOUR ELEVATIONS FOR THE
 GARAGE.
  
 14) PROVIDE TWO (2) LEGIBLE COPIES OF
 THE SURVEY, WHICH INDICATE THE
 DISTANCESTO THE PROPERTY LINES AND THE
 DISTANCE
 BETWEEN THE ADDITION AND THE GARAGE.
  
 15) THE BEDROOM WINDOW MUST COMPLY WITH
 EGRESS REQUIREMENTS. 97 SBC SEC. 1005.4
  
 16) SAFETY GLASS IS REQUIRED IN THE
 BATHROOM WINDOWS IF LOCATED LESS THAN
 60"
 ABOVE THE TUB DRAIN INLET.
  
 17) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ROOFING MATERIAL
 - GARAGE DOOR
 - WINDOWS (THE ONE SUBMITTED IS
 EXPIRED)- SIDE SWING DOOR (THE ONE
 SUBMITTED
 DOES NOT CORRESPOND TO THE PLANS)
 NOTE: TWO COPIES ARE REQUIRED
  
 18) THE BOTTOM OF THE FOOTINGS SHALL BE
 A MINIMUM OF 12" BELOW FINISH GRADE.
 97 SBC SEC.1804.1.3
  
 19) WHERE LATH AND STUCCO IS APPLIED
 OVER THE EXTERIOR OF WOOD FRAME
 CONSTRUCTION, AN APPROVED WEEP SCREED
 (STUCCO STOP) PLACED NOT LESS THAN 6"
 ABOVE FINISH GRADE SHALL BE USED TO
 TERMINATE STUCCO AT THE BASE OF THE
 WALL2304.2.5 OF CITY AMENDEMENTS TO 97
 SBC.
  
 20) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF
 ANCHORS TO BE USED FOR STORM PANELS.
 NOTE: MISSLE IMPACT PROTECTION IS
 REQUIRED FOR ALL GLAZED EXTERIOR
 OPENINGS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-07-17 Cont ID  
Sent By sgraham Date 2001-07-17 Time 06:57 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***