2001-07-31 00:00:00 | *************BUILDING UNSAT************* |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) THE ENGINEER'S TITLE BLOCK IS |
| REQUIRED ON EACH SHEET OF THE PLANS |
| THATARE SIGNED AND SEALED BY HIM. |
| |
| 3) THE BUCK DETAILS AND WALL DETAIL ARE |
| ILLEGIBLE. PLEASE PROVIDE PLANS THAT |
| ARECLEAR AND READABLE. |
| |
| 4) INDICATE METHODS OF ATTACHMENT FOR |
| SECURING FRAME WALLS AND CONCRETE FOOT- |
| INGS TO EXISTING STRUCTURE. |
| |
| 5) PROVIDE ENERGY CALCULATIONS AND |
| EQUIPMENT SIZING CALCULATIONS (MANUAL |
| J)AS REQUIRED BY THE 1997 FLORIDA |
| ENERGYEFFICIENCY CODE FOR BUILDING |
| CONSTRUCTION. |
| |
| 6) INDICATE SPECIAL ROOF SHEATHING |
| NAILING ZONES COMPLYING WITH SECTION |
| 2306 OF THE CITY AMENDMENTS TO THE 97 |
| SBC. |
| |
| 7) PROVIDE GABLE END BRACING DETAILS. |
| |
| 8) INDICATE HOW ATTIC ACCESS TO NEW |
| ADDITION WILL BE ACHIEVED. |
| |
| 9) THE ROOF PLANS INDICATE # 11 |
| CONNECTORS FROM THE SCHEDULE FOR |
| ATTACHING THE TRUSSES TO THE WALLS. |
| THESE CONNECTORS ARE FOR WOOD TRUSS TO |
| CONCRETE BEAM CONNECTIONS. PLEASE |
| INDICATE THE APPROPRIATE CONNECTORS |
| WHICH ARE CAPABLE OF WITHSTANDING THE |
| CALCULATED LOADS. |
| |
| 10) INDICATE THE POSITIVE AND NEGATIVE |
| PRESSURES FOR ALL EXTERIOR WINDOW AND |
| DOOR OPENINGS OF ADDITION AND DETACHED |
| GARAGE. |
| |
| 11) INDICATE THE SPECIFICATE TYPES OF |
| CONNECTORS THAT WILL BE USED TO PROVIDE |
| A CONTINOUS TIE FROM THE FOUNDATION TO |
| THE ROOF. |
| |
| 12) INDICATE THE TYPES AND SIZES OF THE |
| WINDOWS AND DOORS ON THE PLANS. |
| |
| 13) TABLE 600 IN THE 97 SBC IS USED TO |
| DETERMINE THE PERCENTAGE OF WALL AREA |
| THAT IS ALLOWED AS OPENINGS BASED ON |
| THEDISTANCE TO THE PROPERTY LINE OR |
| ASSUMEDPROPERTY LINE. PLEASE PROVIDE |
| BOTH SIDE AND REAR ELEVATIONS FOR THE |
| ADDITION ANDALL FOUR ELEVATIONS FOR THE |
| GARAGE. |
| |
| 14) PROVIDE TWO (2) LEGIBLE COPIES OF |
| THE SURVEY, WHICH INDICATE THE |
| DISTANCESTO THE PROPERTY LINES AND THE |
| DISTANCE |
| BETWEEN THE ADDITION AND THE GARAGE. |
| |
| 15) THE BEDROOM WINDOW MUST COMPLY WITH |
| EGRESS REQUIREMENTS. 97 SBC SEC. 1005.4 |
| |
| 16) SAFETY GLASS IS REQUIRED IN THE |
| BATHROOM WINDOWS IF LOCATED LESS THAN |
| 60" |
| ABOVE THE TUB DRAIN INLET. |
| |
| 17) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - ROOFING MATERIAL |
| - GARAGE DOOR |
| - WINDOWS (THE ONE SUBMITTED IS |
| EXPIRED)- SIDE SWING DOOR (THE ONE |
| SUBMITTED |
| DOES NOT CORRESPOND TO THE PLANS) |
| NOTE: TWO COPIES ARE REQUIRED |
| |
| 18) THE BOTTOM OF THE FOOTINGS SHALL BE |
| A MINIMUM OF 12" BELOW FINISH GRADE. |
| 97 SBC SEC.1804.1.3 |
| |
| 19) WHERE LATH AND STUCCO IS APPLIED |
| OVER THE EXTERIOR OF WOOD FRAME |
| CONSTRUCTION, AN APPROVED WEEP SCREED |
| (STUCCO STOP) PLACED NOT LESS THAN 6" |
| ABOVE FINISH GRADE SHALL BE USED TO |
| TERMINATE STUCCO AT THE BASE OF THE |
| WALL2304.2.5 OF CITY AMENDEMENTS TO 97 |
| SBC. |
| |
| 20) PROVIDE (2) PRODUCT APPROVALS, KEY |
| PLANS AND INSTALLATION SCHEDULES |
| INDICATING THE SPECIFIC TYPES OF |
| ANCHORS TO BE USED FOR STORM PANELS. |
| NOTE: MISSLE IMPACT PROTECTION IS |
| REQUIRED FOR ALL GLAZED EXTERIOR |
| OPENINGS. |
| |