Plan Review Stops For Permit 01070579 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2001-10-15 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-10-15 |
Time |
14:06 |
Rev Time |
1.50 |
Received By |
jwitmer |
Date |
2001-10-15 |
Time |
14:06 |
Sent To |
|
|
Notes |
2001-10-15 00:00:00 | BUILDING PLAN REVIEW | | PERMIT # 01070579 | | REVISION #4 | | | | 1)- UNSAT: | | SBC 1004.3.5.4. AREA OF REFUGE, IS TO | | BE SEPERATED BY A 1 HR SEPERATION, | | PANEL "B" NOT TO BE IN "AREA OF REFUGE" | | SBC 704.2.1.5. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561) 659-8096 X 8412 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2001-09-07 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-09-07 |
Time |
08:48 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
2001-09-07 |
Time |
08:48 |
Sent To |
|
|
Notes |
2001-09-07 00:00:00 | 9/06/01 MEETING WITH ARCH BOB KUOPPALA | | MIKE CARCELLO & MYSELF TO GO OVER THE | | REQUIREMENTS OF AREA OF REFUGE ARCH. TO | | RED LINE PLANS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2001-08-29 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-08-29 |
Time |
07:07 |
Rev Time |
1.75 |
Received By |
jwitmer |
Date |
2001-08-29 |
Time |
07:07 |
Sent To |
|
|
Notes |
2001-08-29 00:00:00 | PLAN REVIEW | | PERMIT # 01070579 | | 423 4TH ST | | CONT: SISCA CONSTRUCTION | | TEL: (561) 309-7175 | | | | 1)- 3RD FLOOR STAIRS TO THE EXTERIOR: | | SBC 1007.4.2."THE WIDTH OF THE LANDING | | SHALL BE NOT LESS THAN THE WIDTH OF THE | | STAIRWAY THEY SERVE. EVERY LANDING SHALL | | HAVE A MINIMUM DIMENSION IN THE DIRECTIO | | N OF TRAVEL EQUAL TO THE WIDTH OF THE | | STAIRWAY." THE FIRE MARSHALL USES THE | | LIFE SAFETY CODE, THE BUILDING DEPART- | | MENT USES THE STANDARD BUILDING CODE. WH | | EN THERE IS A DIFFERENCE IN CODES THE | | MOST STRINGENT CODE IS ENFORCED. | | | | 2)-FLOOR PENETRATIONS, SBC705.6.1 | | THROUGH PENETRATIONS OF FIRE RATED HORI- | | ZONTAL ASSEMBLIES (FLOOR) SHALL COMPLY | | WITH 705.6.1.1 OR 705.6.1.2. SHOW COMPLI | | ANCE. THERE ISVERTICAL PIPING RAIN | | WATER LITERS THAT ARE ON THE 3RD & 2ND | | FLOORS, IF THEY DO NOT GO THROUGH THE | | FLOOR WHERE DO THEY GO ? | | | | AREA OF REFUGE SBC 1004.3.2.1 SHOW COM- | | PLIANCE, A COPY OF THE CODE COMMENTARY | | IS ATTACHED TO GIVE EXAMPLES OF AREA OF | | REFUGE. | | | | FLORIDA ACCESIBILITY CODE 4.1.6(K III) | | 3RD FLOOR STAIR TO THE ROOF PROVIDE | | VERTICAL ACCESSIBILITY. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2001-08-07 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-08-07 |
Time |
14:06 |
Rev Time |
6.00 |
Received By |
jwitmer |
Date |
2001-08-07 |
Time |
14:06 |
Sent To |
|
|
Notes |
2001-08-07 00:00:00 | BUILDING PLAN REVIEW | | PERMIT # 0107579 | | 423 4TH STREET 2ND & 3RD FL | | | | CONT: SISCA CONSTRUCTION | | TEL: (561) 309-7175 | | | | 1)- EXTERIOR STEEL STAIRS : SBC 1006.2.4 | | EXTERIOR STAIRS SHALL BE SEPERATED FROM | | THE INTERIOR OF THE BUILDINGBY WALLS | | WITH A FIRE RESISTANCE RATING OF NOT | | LESS THAN 1 HR, WITH FIXED OR SELF-CLOS- | | ING OPENING PROTECTIVES AS REQUIRED FOR | | ENCLOSED STAIRS.THIS PROTECTION SHALL | | EXTEND VERTICALLY FROM THE GROUND TO A | | POINT 10 FT. ABOVE THE UPPER MOST LAND- | | ING OR THE ROOF LINE, WHICHEVER IS LOWER | | AND HORIZONTALLY 10 FT. FROM EACH SIDE | | OF THE STAIRWAY. OPENINGS WITHIN 10 FT | | HORIZONTAL EXTENSION OF THE PROTECTED | | WALLS BEYOND THE STAIRWAY SHALL BE | | FIXED 3/4 HR ASSEMBLIES. | | | | 2)- 3RD FLOOR STAIRS TO EXTERIOR: | | SBC 1007.4.2, THE WIDTH OF LANDINGS | | SHALL BE NOT LESS THAN THE WIDTH OFTHE | | STAIRWAYS THEY SERVE. EVERY LANDING | | SHALL HAVE A MINIMUM DIMENSION IN THE | | DIRECTION OF TRAVEL EQUAL TO THE WIDTH | | OF THE STAIRWAY. | | | | 3)- PENETRATIONS, SBC 705.6.1: THROUGH | | PENETRATIONS OF FIRE RATED HORIZONTAL AS | | SEMBLIES SHALL COMPLY WITH 705.6.1.1 OR | | 705.6.1.2. SHOW COMPLIANCE. | | | | 4)- SBC TABLE 803.3 INTERIOR MINIMUM | | FINISH CLASSIFICATION FOR WALLS &CEIL- | | ING. | | | | 5)- RESTROOMS: SBC 1204.2: PUBLIC REST- | | ROOMS SHALL BE LINED WITH AN NONABSORB- | | ANT MATERIALFLOOR AND WALLS TO A HEIGTH | | OF 4'-0". | | | | 6)- SBC 104.2.2 ADDITIONAL INFORMATION | | REQUIRED, NEW CHASE PARTITION SHOW | | UL RATING OR GYPSUM ASSOC RATING. | | | | 7)- OFFICE 201/202 FL ACCESIBILITY CODE | | 4.13.6 MANEUVERING CLEARENCES AT DOORS, | | SHOW HOW YOU ARE GOING TO ACHIEVE CODE | | COMPLIANCE, SEE ATTACHMENT. THE SAME SIS | | TUATION HAPPENS FOR DOOR 5 INTO THE | | STAFF LOUNGE.OFFICE 208 & 301 REQUIRE | | THE 18" SIDE CLEARENCE PLAN INDICATES | | 17". | | | | 8)- AREA OF REFUGE SBC 1004.3.2.1 SHOW | | COMPLIANCE FOR 2ND & 3RD FLOOR. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561) 659-8096 X8412 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2001-10-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-10-10 |
Time |
21:13 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-10-10 |
Time |
21:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2001-08-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-08-30 |
Time |
09:23 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-08-30 |
Time |
09:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-08-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-08-07 |
Time |
20:24 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-08-07 |
Time |
20:24 |
Sent To |
|
|
Notes |
2001-08-07 00:00:00 | *************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE THAT BRANCH CIRCUIT | | #`S NEED TO BE SHOWN ON PLANS. PLEASE | | NOTE THAT OUTLET CIRCUITS ARE SHOWN BUT | | NOT FOR LIGHTING SHOWN. | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | PLEASE NOTE THAT AIC RATING IS SHOWN FOR | | PANEL BUT NEEDED FOR MAIN DISCONNECT. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2001-09-07 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-09-07 |
Time |
08:51 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2001-10-09 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-10-09 |
Time |
10:19 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-10-09 |
Time |
10:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2001-09-06 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-09-06 |
Time |
14:42 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-09-06 |
Time |
14:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2001-08-27 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-08-27 |
Time |
16:48 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-08-27 |
Time |
16:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2001-07-25 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-07-25 |
Time |
14:01 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-07-25 |
Time |
14:01 |
Sent To |
|
|
Notes |
2001-07-25 00:00:00 | 1) PLANS NEED TO CLEARLY IDENTIFY FIRE | | RATED WINDOWS LOCATED WITHIN 10 FEET OF | | THE NEW METAL FIRE STAIRS LOCATED ON | | THE NORTH SIDE OF THE BUILDING. IT IS | | KNOWN THAT THE STAIRS HAVE BEEN | | INSTALLED BUT IT IS NOT KNOWN IF THE | | RATED WINDOWS HAVE ALSO BEEN INSTALLED. | | 2) PLEASE PROVIDE INTERIOR FINISH | | CLASSIFICATION INFORMATION FOR WALLS | | AND CEILINGS. | | 3) PLEASE PROVIDE DETAILS ON EXISTING | | ELEVATOR. IS THE ELEVATOR EQUIPPED | | WITH PHASE ONE AND PHASE TWO ELEVATOR | | RECALL AND WHAT IS THE TRAVEL DISTANCE | | FOR IT. | | 4) PLEASE PROVIDE MORE DETAILS ON STEPS. | | WHAT DIRECTION DO YOU GO. UP OR DOWN. | | IF YOU TRAVEL UPWARD, DO YOU STAND ON | | A STEP AND OPEN THE DOOR OR IS THERE A | | LANDING. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2001-10-22 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2001-10-22 |
Time |
10:53 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
2001-10-22 |
Time |
10:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2001-08-30 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2001-08-30 |
Time |
16:00 |
Rev Time |
0.50 |
Received By |
hmoser |
Date |
2001-08-30 |
Time |
16:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2001-08-13 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-08-13 |
Time |
09:10 |
Rev Time |
0.45 |
Received By |
hmoser |
Date |
2001-08-13 |
Time |
08:58 |
Sent To |
|
|
Notes |
2001-08-13 00:00:00 | *******************DENIED*************** | | | | | | PLEASE PROVIDE MANUFACTURER/ENGINEER | | DETAIL FOR CONDENDER UNIT STANDS. | | CONDENSER UNIT STANDS SHALL BE A | | MINIMUM OF 18" FROM ROOF SURFACE TO | | BOTTOM OF SUPPORT RAIL AS PER AMENDED | | 1997 SMC 304.2.5. | | | | PLEASE INDICATE ON PLAN CONDENSATE | | DRAIN LINES AND WHERE THEY TERMINATE | | INTO EXISTING CONDENSATE.INDICATE | | MATERIAL FOR CONDENSATE INSULATION. | | | | INDICATE LOCATION OF AIR HANDLER UNITS, | | ARE THEY IN A CLOSET, ON A STAND OR | | HANGING.IF SUSPENDED INDICATE METHOD | | OF SUPPORT.DRAIN PANS WITH OVERFLOW | | PROTECTION REQUIRED AS PER 1997 SMC | | 304.8.6.1. | | | | PROVIDE AIR BALANCE SCHEDULE TO SHOW | | COMPLIANCE WITH 1997 SMC 501.2. | | | | INDICATE WHAT GAUGE OF SHEET METAL WILL | | BE USED FOR EXHAUST DUCT. | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2001-10-22 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-10-22 |
Time |
10:22 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2001-10-22 |
Time |
10:22 |
Sent To |
|
|
Notes |
2001-10-22 00:00:00 | NO CHANGES FOR PLUMBING NOTED ON REVIS- | | IONS. | | | | KSTEVENS |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2001-08-27 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2001-08-27 |
Time |
15:03 |
Rev Time |
1.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-08-27 00:00:00 | SEE REVISED SHTS. PES |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-08-02 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-08-02 |
Time |
19:43 |
Rev Time |
1.75 |
Received By |
jleech |
Date |
2001-08-02 |
Time |
19:43 |
Sent To |
|
|
Notes |
2001-08-02 00:00:00 | DENIED; | | 1.HANDICAP TOILET MEASUREMENT OFF FINISH | | WALL SHALL BE 18". FACBC FIG.28. | | 2.DRINKING FOUNTAIN TO COMPLY WITH 4.1.3 | | AND 4.15. | | 3.MEN'S ROOM SHOULD HAVE A FLOOR DRAIN | | ALSO. | | 4.FLOOR DRAINS SHALL HAVE TRAP PRIMERS | | SPC SEC 409.4.1.1. | | 5.DRINKING FOUNTAIN MAXIMUM HIGHTH TO | | ORIFICE IS 36" FACBC FIG. 27(A). | | 6.NOTE 8, ALL WATER HAMMER ARRESTERS TO | | BE ENGINEERED PER SPC SEC. 607.8.2 | | AND 607.8.3. LOCATE PER MANUFACTOR | | RECOMMENDATIONS. | | 7.NOTE 10, BOTTLED WATER COOLER IS NOT | | A PLUMBING FIXTURE AND CAN NOT BE USED | | AS AN ALTERNATE METHOD. SEE TABLE 407 | | UNDER MISCELLANEOUS FIXTURES. ALSO SEE | | CHAPTER 2 DEFINITIONS "PLUMBING | | FIXTURES. | | | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT. 8369 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2001-09-07 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-09-07 |
Time |
08:51 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|