Plan Review Stops For Permit 01070579
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2001-10-15 Cont ID  
Sent By jwitmer Date 2001-10-15 Time 14:06 Rev Time 1.50
Received By jwitmer Date 2001-10-15 Time 14:06 Sent To  
Notes
2001-10-15 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01070579
 REVISION #4
  
 1)- UNSAT:
 SBC 1004.3.5.4. AREA OF REFUGE, IS TO
 BE SEPERATED BY A 1 HR SEPERATION,
 PANEL "B" NOT TO BE IN "AREA OF REFUGE"
 SBC 704.2.1.5.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-09-07 Cont ID  
Sent By jwitmer Date 2001-09-07 Time 08:48 Rev Time 1.00
Received By jwitmer Date 2001-09-07 Time 08:48 Sent To  
Notes
2001-09-07 00:00:009/06/01 MEETING WITH ARCH BOB KUOPPALA
 MIKE CARCELLO & MYSELF TO GO OVER THE
 REQUIREMENTS OF AREA OF REFUGE ARCH. TO
 RED LINE PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-08-29 Cont ID  
Sent By jwitmer Date 2001-08-29 Time 07:07 Rev Time 1.75
Received By jwitmer Date 2001-08-29 Time 07:07 Sent To  
Notes
2001-08-29 00:00:00PLAN REVIEW
 PERMIT # 01070579
 423 4TH ST
 CONT: SISCA CONSTRUCTION
 TEL: (561) 309-7175
  
 1)- 3RD FLOOR STAIRS TO THE EXTERIOR:
 SBC 1007.4.2."THE WIDTH OF THE LANDING
 SHALL BE NOT LESS THAN THE WIDTH OF THE
 STAIRWAY THEY SERVE. EVERY LANDING SHALL
 HAVE A MINIMUM DIMENSION IN THE DIRECTIO
 N OF TRAVEL EQUAL TO THE WIDTH OF THE
 STAIRWAY." THE FIRE MARSHALL USES THE
 LIFE SAFETY CODE, THE BUILDING DEPART-
 MENT USES THE STANDARD BUILDING CODE. WH
 EN THERE IS A DIFFERENCE IN CODES THE
 MOST STRINGENT CODE IS ENFORCED.
  
 2)-FLOOR PENETRATIONS, SBC705.6.1
 THROUGH PENETRATIONS OF FIRE RATED HORI-
 ZONTAL ASSEMBLIES (FLOOR) SHALL COMPLY
 WITH 705.6.1.1 OR 705.6.1.2. SHOW COMPLI
 ANCE. THERE ISVERTICAL PIPING RAIN
 WATER LITERS THAT ARE ON THE 3RD & 2ND
 FLOORS, IF THEY DO NOT GO THROUGH THE
 FLOOR WHERE DO THEY GO ?
  
 AREA OF REFUGE SBC 1004.3.2.1 SHOW COM-
 PLIANCE, A COPY OF THE CODE COMMENTARY
 IS ATTACHED TO GIVE EXAMPLES OF AREA OF
 REFUGE.
  
 FLORIDA ACCESIBILITY CODE 4.1.6(K III)
 3RD FLOOR STAIR TO THE ROOF PROVIDE
 VERTICAL ACCESSIBILITY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-08-07 Cont ID  
Sent By jwitmer Date 2001-08-07 Time 14:06 Rev Time 6.00
Received By jwitmer Date 2001-08-07 Time 14:06 Sent To  
Notes
2001-08-07 00:00:00BUILDING PLAN REVIEW
 PERMIT # 0107579
 423 4TH STREET 2ND & 3RD FL
  
 CONT: SISCA CONSTRUCTION
 TEL: (561) 309-7175
  
 1)- EXTERIOR STEEL STAIRS : SBC 1006.2.4
 EXTERIOR STAIRS SHALL BE SEPERATED FROM
 THE INTERIOR OF THE BUILDINGBY WALLS
 WITH A FIRE RESISTANCE RATING OF NOT
 LESS THAN 1 HR, WITH FIXED OR SELF-CLOS-
 ING OPENING PROTECTIVES AS REQUIRED FOR
 ENCLOSED STAIRS.THIS PROTECTION SHALL
 EXTEND VERTICALLY FROM THE GROUND TO A
 POINT 10 FT. ABOVE THE UPPER MOST LAND-
 ING OR THE ROOF LINE, WHICHEVER IS LOWER
 AND HORIZONTALLY 10 FT. FROM EACH SIDE
 OF THE STAIRWAY. OPENINGS WITHIN 10 FT
 HORIZONTAL EXTENSION OF THE PROTECTED
 WALLS BEYOND THE STAIRWAY SHALL BE
 FIXED 3/4 HR ASSEMBLIES.
  
 2)- 3RD FLOOR STAIRS TO EXTERIOR:
 SBC 1007.4.2, THE WIDTH OF LANDINGS
 SHALL BE NOT LESS THAN THE WIDTH OFTHE
 STAIRWAYS THEY SERVE. EVERY LANDING
 SHALL HAVE A MINIMUM DIMENSION IN THE
 DIRECTION OF TRAVEL EQUAL TO THE WIDTH
 OF THE STAIRWAY.
  
 3)- PENETRATIONS, SBC 705.6.1: THROUGH
 PENETRATIONS OF FIRE RATED HORIZONTAL AS
 SEMBLIES SHALL COMPLY WITH 705.6.1.1 OR
 705.6.1.2. SHOW COMPLIANCE.
  
 4)- SBC TABLE 803.3 INTERIOR MINIMUM
 FINISH CLASSIFICATION FOR WALLS &CEIL-
 ING.
  
 5)- RESTROOMS: SBC 1204.2: PUBLIC REST-
 ROOMS SHALL BE LINED WITH AN NONABSORB-
 ANT MATERIALFLOOR AND WALLS TO A HEIGTH
 OF 4'-0".
  
 6)- SBC 104.2.2 ADDITIONAL INFORMATION
 REQUIRED, NEW CHASE PARTITION SHOW
 UL RATING OR GYPSUM ASSOC RATING.
  
 7)- OFFICE 201/202 FL ACCESIBILITY CODE
 4.13.6 MANEUVERING CLEARENCES AT DOORS,
 SHOW HOW YOU ARE GOING TO ACHIEVE CODE
 COMPLIANCE, SEE ATTACHMENT. THE SAME SIS
 TUATION HAPPENS FOR DOOR 5 INTO THE
 STAFF LOUNGE.OFFICE 208 & 301 REQUIRE
 THE 18" SIDE CLEARENCE PLAN INDICATES
 17".
  
 8)- AREA OF REFUGE SBC 1004.3.2.1 SHOW
 COMPLIANCE FOR 2ND & 3RD FLOOR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-10-10 Cont ID  
Sent By dpalmer Date 2001-10-10 Time 21:13 Rev Time 0.00
Received By dpalmer Date 2001-10-10 Time 21:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-08-30 Cont ID  
Sent By dpalmer Date 2001-08-30 Time 09:23 Rev Time 0.00
Received By dpalmer Date 2001-08-30 Time 09:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-07 Cont ID  
Sent By dpalmer Date 2001-08-07 Time 20:24 Rev Time 0.00
Received By dpalmer Date 2001-08-07 Time 20:24 Sent To  
Notes
2001-08-07 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT BRANCH CIRCUIT
 #`S NEED TO BE SHOWN ON PLANS. PLEASE
 NOTE THAT OUTLET CIRCUITS ARE SHOWN BUT
 NOT FOR LIGHTING SHOWN.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATING IS SHOWN FOR
 PANEL BUT NEEDED FOR MAIN DISCONNECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-09-07 Cont ID  
Sent By jwitmer Date 2001-09-07 Time 08:51 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-10-09 Cont ID  
Sent By mcarsill Date 2001-10-09 Time 10:19 Rev Time 0.00
Received By mcarsill Date 2001-10-09 Time 10:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-09-06 Cont ID  
Sent By mcarsill Date 2001-09-06 Time 14:42 Rev Time 0.00
Received By mcarsill Date 2001-09-06 Time 14:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-08-27 Cont ID  
Sent By mcarsill Date 2001-08-27 Time 16:48 Rev Time 0.00
Received By mcarsill Date 2001-08-27 Time 16:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-07-25 Cont ID  
Sent By mcarsill Date 2001-07-25 Time 14:01 Rev Time 0.00
Received By mcarsill Date 2001-07-25 Time 14:01 Sent To  
Notes
2001-07-25 00:00:001) PLANS NEED TO CLEARLY IDENTIFY FIRE
 RATED WINDOWS LOCATED WITHIN 10 FEET OF
 THE NEW METAL FIRE STAIRS LOCATED ON
 THE NORTH SIDE OF THE BUILDING. IT IS
 KNOWN THAT THE STAIRS HAVE BEEN
 INSTALLED BUT IT IS NOT KNOWN IF THE
 RATED WINDOWS HAVE ALSO BEEN INSTALLED.
 2) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 3) PLEASE PROVIDE DETAILS ON EXISTING
 ELEVATOR. IS THE ELEVATOR EQUIPPED
 WITH PHASE ONE AND PHASE TWO ELEVATOR
 RECALL AND WHAT IS THE TRAVEL DISTANCE
 FOR IT.
 4) PLEASE PROVIDE MORE DETAILS ON STEPS.
 WHAT DIRECTION DO YOU GO. UP OR DOWN.
 IF YOU TRAVEL UPWARD, DO YOU STAND ON
 A STEP AND OPEN THE DOOR OR IS THERE A
 LANDING.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-10-22 Cont ID  
Sent By ndenmark Date 2001-10-22 Time 10:53 Rev Time 0.33
Received By ndenmark Date 2001-10-22 Time 10:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-08-30 Cont ID  
Sent By hmoser Date 2001-08-30 Time 16:00 Rev Time 0.50
Received By hmoser Date 2001-08-30 Time 16:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-13 Cont ID  
Sent By pkrauss Date 2001-08-13 Time 09:10 Rev Time 0.45
Received By hmoser Date 2001-08-13 Time 08:58 Sent To  
Notes
2001-08-13 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE MANUFACTURER/ENGINEER
 DETAIL FOR CONDENDER UNIT STANDS.
 CONDENSER UNIT STANDS SHALL BE A
 MINIMUM OF 18" FROM ROOF SURFACE TO
 BOTTOM OF SUPPORT RAIL AS PER AMENDED
 1997 SMC 304.2.5.
  
 PLEASE INDICATE ON PLAN CONDENSATE
 DRAIN LINES AND WHERE THEY TERMINATE
 INTO EXISTING CONDENSATE.INDICATE
 MATERIAL FOR CONDENSATE INSULATION.
  
 INDICATE LOCATION OF AIR HANDLER UNITS,
 ARE THEY IN A CLOSET, ON A STAND OR
 HANGING.IF SUSPENDED INDICATE METHOD
 OF SUPPORT.DRAIN PANS WITH OVERFLOW
 PROTECTION REQUIRED AS PER 1997 SMC
 304.8.6.1.
  
 PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2.
  
 INDICATE WHAT GAUGE OF SHEET METAL WILL
 BE USED FOR EXHAUST DUCT.
  
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-10-22 Cont ID  
Sent By kstevens Date 2001-10-22 Time 10:22 Rev Time 0.50
Received By kstevens Date 2001-10-22 Time 10:22 Sent To  
Notes
2001-10-22 00:00:00NO CHANGES FOR PLUMBING NOTED ON REVIS-
 IONS.
  
 KSTEVENS

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-08-27 Cont ID  
Sent By pschmitz Date 2001-08-27 Time 15:03 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-08-27 00:00:00SEE REVISED SHTS. PES

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-02 Cont ID  
Sent By jleech Date 2001-08-02 Time 19:43 Rev Time 1.75
Received By jleech Date 2001-08-02 Time 19:43 Sent To  
Notes
2001-08-02 00:00:00DENIED;
 1.HANDICAP TOILET MEASUREMENT OFF FINISH
 WALL SHALL BE 18". FACBC FIG.28.
 2.DRINKING FOUNTAIN TO COMPLY WITH 4.1.3
 AND 4.15.
 3.MEN'S ROOM SHOULD HAVE A FLOOR DRAIN
 ALSO.
 4.FLOOR DRAINS SHALL HAVE TRAP PRIMERS
 SPC SEC 409.4.1.1.
 5.DRINKING FOUNTAIN MAXIMUM HIGHTH TO
 ORIFICE IS 36" FACBC FIG. 27(A).
 6.NOTE 8, ALL WATER HAMMER ARRESTERS TO
 BE ENGINEERED PER SPC SEC. 607.8.2
 AND 607.8.3. LOCATE PER MANUFACTOR
 RECOMMENDATIONS.
 7.NOTE 10, BOTTLED WATER COOLER IS NOT
 A PLUMBING FIXTURE AND CAN NOT BE USED
 AS AN ALTERNATE METHOD. SEE TABLE 407
 UNDER MISCELLANEOUS FIXTURES. ALSO SEE
 CHAPTER 2 DEFINITIONS "PLUMBING
 FIXTURES.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 1 Status N Date 2001-09-07 Cont ID  
Sent By jwitmer Date 2001-09-07 Time 08:51 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***