Plan Review Details - Permit 01070355
Plan Review Stops For Permit 01070355
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-08-22 Cont ID  
Sent By jwitmer Date 2001-08-22 Time 10:28 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-08-02 Cont ID  
Sent By jwitmer Date 2001-08-02 Time 13:47 Rev Time 1.50
Received By jwitmer Date 2001-08-02 Time 13:47 Sent To  
Notes
2001-08-02 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01070355
 1325 N CONGRESS
  
 CONT: MHS CONTRACTING
 TEL: 586-7063
  
 SBC= STANDARD BUILDING CODE
 1)- SBC 1012.5 DOORS OPENING ONTO EXIT
 ACCESS CORRIDORS, SHALL NOT REDUCE THE
 WIDTH OF THE CORRIDOR TO LESS THAN 1/2
 OF THE WIDTH DURING THE OPENING PROCESS.
 A- HALL CLOSET
 B- 2ND EGRESS IN THE WORK AREA (SINGLE
 DOOR)
  
 2)- SBC 803.3: INTERIOR FINISH CLASSIF-
 ICATION, SEE TABLE 803.3
  
 3)- SBC 903.2 FIRE SPRINKLER PLANS & LAY
 OUT ARE MISSING FROM THE PLANS.
  
 4)- SBC 1204.2 THE WALLS & FLOORS OF ALL
 PUBLIC RESTROOMS SHALL BE LINED WITH
 NONABSORBANT MATERIALS TO A HEIGTH OF
 4'-0".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-08-27 Cont ID  
Sent By dpalmer Date 2001-08-27 Time 11:40 Rev Time 0.00
Received By dpalmer Date 2001-08-27 Time 11:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-08-06 Cont ID  
Sent By dpalmer Date 2001-08-06 Time 13:44 Rev Time 0.00
Received By dpalmer Date 2001-08-06 Time 13:44 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-08-07 Cont ID  
Sent By pkrauss Date 2001-08-07 Time 12:06 Rev Time 0.10
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-08-17 Cont ID  
Sent By mcarsill Date 2001-08-17 Time 16:29 Rev Time 0.00
Received By mcarsill Date 2001-08-17 Time 16:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-07-10 Cont ID  
Sent By mcarsill Date 2001-07-10 Time 10:54 Rev Time 0.00
Received By mcarsill Date 2001-07-10 Time 10:54 Sent To  
Notes
2001-07-10 00:00:001) ANOTHER ILLUMINATED EXIT SIGN IS
 REQUIRED TO DIRECT PERSONS TO EXIT
 CORRIDOR LOCATED BETWEEN UNISEX BATHROOM
 204 AND NEW WORK ROOM 203. ALSO AN
 EMERGENCY LIGHT IS NECESSARY.
 2) INTERIOR FINISHES SHALL COMPLY WITH
 THE STANDARD BUILDING CODE 1997 EDITION
 TABLE 803.3 AND THE LIFE SAFETY CODE
 1985 EDITION, SECTION 27-3.3.
 3) FURNITURE PLAN INDICATES A WORK
 STATION AND CHAIR LOCATED NEAR EXIT
 SIGN AND EMERGENCY LIGHT NORTH OF NEW
 WORK ROOM, PLEASE CLARIFY.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-08-28 Cont ID  
Sent By pkrauss Date 2001-08-28 Time 13:03 Rev Time 0.50
Received By pkrauss Date 2001-08-28 Time 12:49 Sent To  
Notes
2001-08-28 00:00:00******************PROVISO***************
  
  
 PLAN SHEET M-1 INDICATES A RETURN IN THE
 BATHROOM AS PER 1997 SMC 503.3.1, AIR
 FROM TOILETS, BATHROOMS AND LAVATORIES
 SHALL NOT BE RECIRCULATED.
  
 NOTE:NO COMBUSTIBLES ABOVE THE
 CEILING IN THE RETURN AIR PLENUM.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-08-07 Cont ID  
Sent By pkrauss Date 2001-08-07 Time 11:38 Rev Time 0.45
Received By pkrauss Date 2001-08-07 Time 11:35 Sent To  
Notes
2001-08-07 00:00:00*******************DENIED***************
  
  
 INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-08-24 Cont ID  
Sent By kstevens Date 2001-08-24 Time 10:15 Rev Time 1.00
Received By kstevens Date 2001-08-24 Time 10:15 Sent To  
Notes
2001-08-24 00:00:00PROVISO...
  
  
 PLUMBING CONTRACTOR SHALL SUPPLY SANIT-
 ARY RISER DIAGRAM AND WATER RISER DIA-
 GRAM FOR REVIEW BEFORE PLUMBING PERMIT
 IS ISSUED.
  
 PLEASE CONTACT KEN STEVENS FOR ANY MORE
 INFORMATION. (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-07-22 Cont ID  
Sent By jleech Date 2001-07-22 Time 10:46 Rev Time 0.75
Received By jleech Date 2001-07-22 Time 10:46 Sent To  
Notes
2001-07-22 00:00:00DENIED;
  
 1.SHOW DIMENSION OF BATHROOM ON PLANS.
  
 2.PAGE N-3 (10) SHOR BATHROOM CONFIGURA-
 TION TO BE USED. IF (A) SHOW WIDTH
 DIMENSION.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369

Review Stop Z ZONING
Rev No 1 Status N Date 2001-08-07 Cont ID  
Sent By pkrauss Date 2001-08-07 Time 12:06 Rev Time 0.10
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***