Plan Review Stops For Permit 01070198 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2001-12-17 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2001-12-17 |
Time |
13:36 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-12-17 00:00:00 | FOUNDATION ONLY |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2001-10-24 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2001-10-24 |
Time |
16:49 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-10-24 00:00:00 | THE LOCATION OF THE TWO STAIR SHAFTS | | DOES NOT MEET THE DISTANCE SEPARATION | | REQUIREMENTS OF SBC 1004.1.1 AS SHOWN | | ON SHEETS A2.03 AND A 2.06.PLEASE | | REVISE AS NECESSARY. | | | | SINCE THE STAIR SHAFTS ARE SHEAR WALLS | | AND THEIR RELOCATION WILL EFFECT THE | | STEEL PLACEMENT OF THE FOUNDATION PAD, | | THIS ISSUE MUST BE RESOLVED BEFORE A | | FOUNDATION PERMIT CAN BE ISSUED. | | | | A THRESHOLD INSPECTOR IS REQUIRED AND | | IMPACT FEES MUST BE PAID TO THE COUNTY | | AS CITED IN THE EARLIER CHECKLIST(S) AND | | DEMONSTRATION OF COMPLIANCE WITH SBC | | 1803.2. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2001-10-04 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2001-10-04 |
Time |
13:07 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-10-04 00:00:00 | PLEASE PROVIDE A RECENT PROPERTY SURVEY. | | | | THE CRAVEN THOMPSON CIVIL PLANS TITLE | | SHEET CALLS OUT AN ADDRESS OF 915 S | | DIXIE HWY.WHY? | | | | THE PLANS ARE MOSTLY INCOMPLETE AND A | | CLOSE AND CRITICAL PLAN REVIEW FOR CODE | | COMPLIANCE IS NOT POSSIBLE. IS THE | | DESIGN OF THIS BUILDING COMPLETED YET? | | | | | | PROVIDE ADDITIONAL INFORMATION ON THE | | WATERPROOFING METHODS. SEE SBC 1814.2 | | WHAT IS A "MUD BED" ? | | | | THE LOBBY LEVEL IS SHOWN AT 11.0' NGVD | | AND THE 1ST PARKING LEVEL AT 13'-10". | | PLEASE CLARIFY THE DESIGN INTENT. | | ALSO REVIEW THE HC CODE FOR PARKING | | GARAGE CLEAR HEIGHT. | | | | DIMENSIONS TO LOCATE THE COLUMNS ON | | SHEET S-01, OR OTHERS, ARE NOT READILY | | DISCERNIBLE. | | | | IS THERE MORE DESCRIPTIVE DETAIL | | AVAILABLE FOR THE STRUCTURAL COMPONENTS | | SHOWN ASW-1, W-1A AND W-2? | | | | SHEET S-01 GRID LINE 4 SHOWS THE 15 DEG | | ANGLE COMMENCING AT AN INDETERMINATE | | POINT. | | | | THE RWDI TEST REPORT REFERENCES ASCE | | 7-93.SBC 97 INVOKES ASCE 7-95. | | | | WHAT RECOGNIZED ACCREDITATIONS DOES THE | | WIND TUNNEL TESTING FACILITY HAVE? | | | | THE THRESHOLD INSPECTION PLAN REFERENCES | | THE SOUTH FLORIDA BUILDING CODE ON PAGE | | 3.PLEASE CHANGE OR REVISE TO INCLUDE | | THE 1997 STANDARD BUILDING CODE, SBCCI. | | | | PLEASE DEMONSTRATE COMPLIANCE WITH SBC | | 1803.2 FOR THE ADJOINING PROPERTY | | | | SKETCHES IN THE RWDI REPORT INDICATE | | THERE MAY BE TABLE 600 CONFLICTS WITH | | THE WALL OPENINGS, AND THE STAIR | | LOCATIONS MAY NOT MEET THE 1/2 DIAGONAL | | DISTANCE REQUIREMENT OF SBC 1004.1.4. | | | | ON THRESHOLD BUILDINGS, 3 SETS OF PLANS | | AND INFORMATION ARE REQUIRED. | | | | GIVEN THE 100% LOT COVERAGE, HAS THE | | MOBILIZATION AND LOCATION OF MATERIALS | | AND EQUIPMENT BEEN ADDRESSED?CONTACT | | THE CITY ENGINEER AT 659-8040 FOR USE | | OF PUBLIC RIGHT OF WAY INCLUDING THE | | PLACEMENT OF THE OIL INTERCEPTOR SHOWN | | ON SHEET P-1. | | | | HOW WILL ELECTRICAL POWER BE DELIVERED | | TO THE SUMP PUMPS SHOWN ON SHEET P-1 | | | | WHERE IS THE PERMIT APPLICATION, AND ITS | | ATTENDANT PLANS, FOR THE BUILDING | | PROPER?SEE SBC 104.4.3. | | | | BEFORE ANY PERMITS TO CONSTRUCT MAY BE | | ISSUED IMPACT FEES MUST BE PAID TO PALM | | BEACH COUNTY, THE PERMIT PLANS STAMPED | | BYTHAT OFFICE AND A COPY OF THE PAID | | RECEIPT ATTACHED TO THE PERMIT | | APPLICTION. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2001-07-31 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2001-07-31 |
Time |
10:25 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2001-07-30 |
Time |
13:36 |
Sent To |
|
|
Notes |
2001-07-31 00:00:00 | A SITE PLAN IS NECESSARY TO LOCATE THE | | BUILDING ON THE PROPERTY. | | | | THE 14" DIA. AUGERCAST PILE DEPTHS WILL | | EXCEED 30 TIMES THEIR DIAMETER AND MUST | | BE INSTALLED UNDER THE DIRECT | | SUPERVISION OF AN ENGINEER.PLEASE | | PROVIDE AFFIRMATION OF THIS.SEE SBC | | 1809.2.2. | | | | SHEET S16 "SPECIALTY ENGINEERING NOTES" | | CITES THE SFBC AS DOES S17 UNDER | | STRUCTURAL LOADING.PROVIDE | | AFFIRMATION THAT THE DESIGN WILL COMPLY | | WITH SBCCI, 1997 AND ASCE 7-95.PLEASE | | PROVIDE A COPY OF THE WIND TUNNEL | | TESTING AND THE SOIL INVESTIGATION | | RECOMMENDATIONS. | | | | PROVIDE A THRESHOLD INSPECTION PLAN AND | | CONTACT DON NEELY ASSISTANT BUILDING | | OFFICIAL TO COORDINATE THE THRESHOLD | | INSPECTOR.561-659-8096 X 8333. | | | | PLEASE PROVIDE A DETAIL OR WRITTEN | | NARRATIVE ON THE METHOD OF INSTALLING | | THE AUGER CAST THROUGH THE 5' THICK | | FOUNDATION MAT AS SHOWN IN SECTION 5/S2. | | | | SHEET S17 THE LIVE LOADS ARE NOT CLEAR, | | (TYPO)THE PLYWOOD ROOF SHEATHING SHOWN | | IS NOT ALLOWED IN TYPE I OR II | | CONSTRUCTION.SEE SBC 603 & 604. | | | | SHOW THE DESIGN FOUNDATION CAPACITY AND | | HOW IT WAS DETERMINED. | | | | BEFORE A PERMIT TO CONSTRUCT MAY BE | | ISSUED IMPACT FEES MUST BE PAID TO PALM | | BEACH COUNTY, THE PERMIT PLANS STAMPED | | BY THEM AND A COPY OF THE RECEIPT | | ATTACHED TO THE PERMIT APPLICATION. | | CALL 561-233-5025 FOR MORE INFORMATION. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
N |
Date |
2001-10-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-10-01 |
Time |
19:37 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-10-01 |
Time |
19:37 |
Sent To |
|
|
Notes |
2001-10-01 00:00:00 | ********* NOTE****** | | | | 1)NOTE: PLEASE NOTE THAT AS PER LETTER | | FROM CONTRACTOR, THEIR WILL BE NO | | ELECTRICAL INSTALLED DURING FOUNDATION | | STAGE. | | | | DV PALMER |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2001-07-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-07-30 |
Time |
20:03 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-07-30 |
Time |
20:03 |
Sent To |
|
|
Notes |
2001-07-30 00:00:00 | **************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE THATNOTHING WAS | | SUBMITTED FOR REVIEW FOR ELECTRICAL | | IN FOUNDATION?? | | PERMIT APPLICATION IS FOR FOUNDATION | | PERMIT? | | | | PLEASE SUBMIT PLANS FOR REVIEW, IF THERE | | ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELELCTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
P |
Date |
2001-09-26 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2001-09-26 |
Time |
13:58 |
Rev Time |
3.00 |
Received By |
mamini |
Date |
2001-09-26 |
Time |
13:58 |
Sent To |
|
|
Notes |
2001-09-26 00:00:00 | PASSED WITH PROVISOS : | | 1. PLEASE SUBMIT 2 COPIES OF CIVIL PLANS | | TO PUBLIC UTILITIES ENGINEERING FOR | | APPROVAL OF TIE-INS, TYPE, MATIREALS AND | | LOCATION OF BACKFLOW PREVENTERS, ATT: | | MANNY GONZALEZ,659-8040 | | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2001-07-06 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2001-07-06 |
Time |
14:52 |
Rev Time |
3.00 |
Received By |
mamini |
Date |
2001-07-06 |
Time |
14:52 |
Sent To |
|
|
Notes |
2001-07-06 00:00:00 | FALIED: | | 1. INSUFFICENT INFORMATION FOR CIVIL | | ENGINEERING REVIEW, PLEASE SUBMIT CIVIL | | PLANS SO WE CAN REVIEW THE UNDERGROUND | | UTILITY WORKS. | | 2. PLEASE PROVIDE STORM WATER | | CALCULATION FOR OUR REVIEW AND APPROVAL. | | 3. PLEASE PROVIDE POLLUTION PREVENTION | | PLANS FOR ENTIRE SITE.POLLUTION | | PREVENTION PLANS SHOULD BE INSTALLED IN | | THE FIELD PRIOR TO ANY EARTH WORKS. | | 4. ANY WORK WITHIN PUBLIC R.O.W WILL | | REQUIRE A SEPARATE PERMIT THROUGH | | OFFICE OF CITY ENGINEER, 659-8040 | | 5. CITY STANDARDS AND DETAILS MAY BE | | OBTAINED FROM PUBLIC UTILITIES ENGINEER- | | ING SERVICES DEPARTMENT, 659-8040 | | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
N |
Date |
2001-12-18 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-12-18 |
Time |
11:16 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-12-18 |
Time |
11:16 |
Sent To |
|
|
Notes |
2001-12-18 00:00:00 | FOUNDATION ONLY. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2001-09-24 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-09-24 |
Time |
12:58 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-09-24 |
Time |
12:58 |
Sent To |
|
|
Notes |
2001-09-24 00:00:00 | 1) ELECTRONIC SWITCHES WILL BE REQUIRED | | ON THE O.S.& Y VALVES. | | 2) SINCE THE BUILDING IS A HIGH-RISE | | BUILDING, TWO FIRE DEPARTMENT | | CONNECTIONS WILL BE REQUIRED. NO FIRE | | HYDRANTS SHOWN ON PLANS. ACCORDING TO | | EVAN ROSENBLATT OF SUFFOLK, FIRE | | HYDRANTS ARE LOCATED ON THE NORTH | | SIDE OF THE BUILING. HE WAS ADVISED THAT | | THE FDC'S ARE TO BE WITHIN 150 FEET OF | | FIRE HYDRANTS. | | ACCORDING TO MR. ROSENBLATT, NO GAS | | SERVICE WILL BE PROVIDED. | | 3) PLEASE BE ADVISED THAT 50 PERCENT | | OF THE EXITS ARE REQUIRED TO DISCHARGE | | DIRECTLY TO THE EXTERIOR EXCLUSIVE OF | | HORIZONTAL EXITS. | | 4) A TEMPORARY STANDPIPE WILL BE | | REQUIRED FOR THE BUILDING WHEN IS IS | | UNDER CONSTRUCTION. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2001-07-09 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-07-09 |
Time |
12:48 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-07-09 |
Time |
12:47 |
Sent To |
|
|
Notes |
2001-07-09 00:00:00 | 1) NO UNDEGROUND UTILITIES SHOWN | | ON DRAWINGS. ARE GAS, ELECTRIC, WATER, | | SEWER, OR FIRE PROTECTION LINES PRESENT. | | 2) NO FIRE HYDRANTS SHOWN ON THE | | DRAWINGS. | | 3) WHERE ARE FUTURE CONNECTIONS TO | | THE CITY WATER SUPPLY FOR FIRE | | PROTECTION TO BE MADE. | | 4) COULD NOT LOCATE FIRE PUMP OR | | LOCATION OF PROPOSES FIRE PUMP. WHERE | | WILL THE FIRE PROTECTION SERVICE ENTER | | THE BUILDING. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2001-08-01 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2001-08-01 |
Time |
11:09 |
Rev Time |
0.50 |
Received By |
pkrauss |
Date |
2001-08-01 |
Time |
11:09 |
Sent To |
|
|
Notes |
2001-08-01 00:00:00 | *********************DENIED************* | | | | | | INSUFFICIENT INFORMATION FOR MECHANICAL | | REVIEW.PLEASE SUBMIT PLANS WITH | | MECHANICAL PERMIT APPLICATION. | | | | | | NOTE:SHOULD ANY MECHANICAL PIPING BE | | INSTALLED WITH FOUNDATION, PLANS | | AND PERMIT MUST BE APPROVED. | | | | SEE PLUMBING COMMENTS ON THE A/C | | CONDENSATE DRAINS. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2002-01-10 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2002-01-10 |
Time |
16:26 |
Rev Time |
2.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-01-10 00:00:00 | PROVISO: FOUNDATION ONLY, PES | 2001-12-19 00:00:00 | PLUMBING PLAN REVIEW, FOUNDATION ONLY | | APPROVED.PES |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2001-10-26 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2001-10-26 |
Time |
18:34 |
Rev Time |
2.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-10-26 00:00:00 | PLUMBING PLAN REVIEW, FOUNDATION ONLY. | | APPROVED WITH PREVIOUS NOTES 07-31-01 | | SEE SHTS S-01,02,P-1,P-2 AREA OF WORK. | | BUILDING PERMIT 01101288 | | END OF COMMENTS PAUL SCHMITZ | | QUESTIONS561-659-8096X8233 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2001-10-05 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-10-05 |
Time |
10:11 |
Rev Time |
1.00 |
Received By |
pschmitz |
Date |
2001-10-05 |
Time |
10:11 |
Sent To |
|
|
Notes |
2001-10-05 00:00:00 | DENIED | | | | UNABLE TO DO PLUMBING PLAN REVIEW WITH- | | OUT ALL INFORMATION REQUESTED. PLEASE | | SUBMIT ALL INFORMATION FOR PLAN REVIEW. | | SEE ATTACHED SHEET. | | | | REVIEW BY KEN STEVENS | | (561) 569-8096 EXT 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2001-07-31 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2001-07-31 |
Time |
07:28 |
Rev Time |
3.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-08-01 00:00:00 | PLUMBING PLAN REVIEW FOUNDATION PERMIT | | DENIED. | | (1) INFORMATION NEEDED TO REVIEW PLANS | | FOR A FOUNDATION PERMIT ONLY. | | (A) SHT'S S-01.02,P-1,P-2. | | (A) GARAGE DRAINS: TOTAL LOAD FROM UPPER | | FLOORS, SQUARE FOOTAGE,PIPE SIZES. | | (B)SANITARY SEWER: TOTAL LOAD IN FIXTURE | | UNITS,FROM UPPER FLOORS.WITH PIPE SIZES. | | (C) COMMON A/C CONDENSATE SYSTEM: LOAD | | FROM UPPER FLOORS WITH PIPE SIZES. | | CONNECT TO STORM DRAIN OUTSIDE OF BUILD- | | ING WITH A RELIEF VENT.MCWPC-94/804.4(6) | | (D) OIL SEPERATOR SIZED FOR LOAD ON | | SYSTEM,TO BE APPR BY WPB.ENGINEERING. | | (E) BACKFLOW PREVENTER LOCATION IN BUILD | | ING TO BE APPROVED BY WPB UTILITIES DEPT | | (F) IF ANY OF THE ABOVE COMMENTS ARE NOT | | IN THE FOUNDATION,PLEASE INDICATE WERE | | THEY ARE LOCATED IN THE BUILDING. | | END OF COMMENTS PAUL SCHMITZ | | QUESTIONS561-659-8096X8233 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2001-11-16 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2001-11-16 |
Time |
15:53 |
Rev Time |
0.25 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2001-08-16 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2001-08-16 |
Time |
11:25 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-08-16 00:00:00 | CITY PLANNER,JOE MINICOZZI IS REQUESTING | | THE SITE PLAN ON SURVEY LINES. | | | | L MARTINEZ |
|
|